Bulletin 700-R -RM Sealed Switch Relays
| Product Overview |
|
Bulletin 700-R, -RM — Sealed Switch Relays
- Sealed contacts
- Extremely long mechanical and electrical life
- Hazardous locations Class 1, Div 2 Groups A, B, C, D
- Harsh environments
- Suitable for applications with shock and vibration
- High reliability circuit integrity
Standards Compliance and Certifications
- UL Listed (File No. E10314) (Guide No. NOIV) per UL 508
- CSA Certified
(File No. LR11924)
- CE Certified
Product Selection
| Build a Catalog Number |
Ä Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage code from the table below to complete the Cat. No. Example: Cat. No. 700-R000Ä becomes Cat. No. 700-R000A24. For other coil voltages, contact your local Rockwell Automation sales office or Allen-Bradley distributor.
| Type of Relay | [V] | Coil Volts | |||||||
| 24 | 48 | 110 | 115-125 | 120 | 220 | 230-250 | 240 | ||
| AC | 25 Hz | — | — | C11 | — | C1 | — | — | C2 |
| 50 Hz | B24 | B48 | A1 | — | — | A2 | — | — | |
| 60 Hz | A24 | A48 | — | — | A1 | — | — | A2 | |
| DC | — | Z24 | Z48 | — | Z1 | — | — | Z2 | — |
| Arrangement displays all N.O. contacts. | |||||||||
| ♣ Polarity must be observed for DC voltage (700 DC) relays. | |||||||||
| ∆ Location of contacts in 2-pole relays. | |||||||||
| ♦ Location of contacts in 6-pole relays. | |||||||||
Ä Coil Voltage Code
The Cat. No. as listed is incomplete. Select a voltage code from the table below to complete the Cat. No. Example: Cat. No. 700-RM000Ä becomes Cat. No. 700-RM000A24. For other coil voltages, contact your local Rockwell Automation sales office or Allen-Bradley distributor.
| Type of Relay | [V] | Coil Volts | |||||||
| 24 | 48 | 110 | 115-125 | 120 | 220 | 230-250 | 240 | ||
| AC | 25 Hz | — | — | C11 | — | C1 | — | — | C2 |
| 50 Hz | B24 | B48 | A1 | — | — | A2 | — | — | |
| 60 Hz | A24 | A48 | — | — | A1 | — | — | A2 | |
| DC | — | Z24 | Z48 | — | Z1 | — | — | Z2 | — |
| Arrangement displays all N.O. contacts. | |||||||||
| ♣ Location of contacts in 6-pole relays. | |||||||||
| ∆ Polarity must be observed for DC voltage (700 DC) relays. | |||||||||
| ♦ Location of contacts in 2-pole relays. | |||||||||
Accessories
Accessories for Bulletin 700-R, -RM Relays
|
Description | Pkg. Quantity | Cat. No. | |||
| Relay Rail Simplifies panel layout. These indexed strips are easily cut to the required length and bolted, riveted, or spot-welded in place. Relays are installed adjacent to one another on the mounting strip with the captive mounting screws provided. Rows of relays on Relay Rail form their own wiring trough. Can be used with the following relays: 700P, 700-PK, 700PH, 700S-P, 700N, 700-R, 700-RTC |
4 Relays per Strip | 5 | 700-MP4 | |||
| 8 Relays per Strip | 5 | 700-MP8 | ||||
| 12 Relays per Strip | 5 | 700-MP12 | ||||
| 16 Relays per Strip | 5 | 700-MP16 | ||||
|
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m |
10 | 199-DR1 | |||
| Cat. No. 199-DR1 | ||||||
|
DIN Rail Adapter Can be used with the following relays: Bulletin 700P, 700-PK, 700-PH, 700S-P, 700-N, 700-R, 700-RTC |
1 | 700-DRA | |||
|
Front Deck A front deck can be attached to Bulletin 700 2-, 3-, or 4-pole AC and DC Type R or RM relays. |
Front Deck with one N.O. Contact Cartridge (700-R Relay) |
1 | 700-RA10 | ||
| Front Deck with one N.C. Contact Cartridge (700-R Relay) |
1 | 700-RA01 | ||||
| Front Deck with one N.O. Contact Cartridge (700-RM Relay) |
1 | 700-RB10 | ||||
| Front Deck with one N.C. Contact Cartridge (700-RM Relay) |
1 | 700-RB01 | ||||
|
Contact Cartridges These cartridges are used to increase the number of poles of a relay. A dummy cartridge is also available to fill empty space not occupied by a contact cartridge. |
N.O. Contact Cartridge - Green (700-R Relay) |
1 | 700-CR5 | ||
| N.C. Contact Cartridge - Yellow (700-R Relay) |
1 | 700-CR6 | ||||
|
N.O. Contact Cartridge - Blue (700-RM Relay) |
1 | 700-CR7 | |||
| N.C. Contact Cartridge - Red (700-RM Relay) |
1 | 700-CR8 | ||||
| Cat. No. 700-CR5 |
Cat. No. 700-CR6 |
Cat. No. 700-CR9 |
DUMMY Cartridge - Black (700-R and -RM Relays) |
1 | 700-CR9 | |
|
Surge Suppressor When the circuit to a DC operating coil is opened, the inductive energy stored in the coil can generate very high transient voltages. With the addition of the appropriate surge suppressor, the stored energy is absorbed and dissipated limiting the voltage spikes. A surge suppressor is not required with AC 700-R or -RM relays because the AC operating coil transients are suppressed by a full wave rectifier connected to the coil. |
12V DC (700-R Relay) | 1 | 199-FSMA9 | ||
| 12V DC (700-RM Relay) | 2 | |||||
| 24V DC (700-R Relay) | 1 | |||||
| 24V DC (700-RM Relay) | 2 | |||||
| 48V DC (700-R Relay) | 1 | |||||
| 48V DC (700-RM Relay) | 2 | |||||
| 115…125V DC (700-R Relay) | 1 | 199-FSMA10 | ||||
| 115…125V DC (700-RM Relay) | 2 | |||||
| 230…250V DC (700-R Relay) | 1 | 199-FSMA11 | ||||
| 230…250V DC (700-RM Relay) | 2 | |||||
|
Bulletin 700-PS Solid-State Timing Unit You can attach a Bulletin 700-PS solid-state timing unit to 4-pole 700-R or -RM relays. An adaptor kit, Cat. No. 700-N26, is required. See Accessories for description. |
|||||
| Bulletin 852S Solid-State Timing Unit You can attach a Bulletin 852S solid-state timing unit to 4-pole 700-R or -RM relays. |
||||||
Specifications
Application Data Because of the inherent characteristics of this device, the normally open contacts may close before the normally closed contacts open on energization and the normally closed contacts may close before the normally open contacts open on de-energization.
Note: For Bul. 700-RM, energizing both the latch and unlatch coil together will cause the relay to be energized and both latch and unlatch coils can be operated together continuously.
Ratings
| AC Voltage | DC Voltage | ||||||||
| NEMA Rating Designation |
Voltage | Make | Break | Continuous Carrying Current [A] | NEMA Rating Designation |
Volts DC | Make/Break | Continuous Carrying Current [A] |
|
| B300 | Up to 300V AC | 120V | 30 | 3 | 5 | NEMA P300 | 46…300 | 138 VA | 5 |
| 240V | 15 | 1.5 | |||||||
| C600 | Above 300V AC | 480V | 7.5 | 0.75 | 2.5 | 5…46 | 3 A | 5 | |
| 600V | 6.0 | 0.60 | |||||||
Maximum Allowable Off-State Leakage Current
| Voltage | Maximum Off-State Leakage Current [mA] |
Maximum Off-State Leakage Current [mA] |
| Type R | Type RM | |
| 24V DC | 23 | 8 |
| 24V AC | 23 | 8 |
| 120V AC | 5 | 2 |
Relay Data
| Type | 700-R | 700-RM | |
| Contact Arrangement | Up to 8 poles, available in any combination of N.O. or N.C. contacts | Up to 8 poles, available in any combination of N.O. or N.C. contacts | |
| Contact Material | W (tungsten in a controlled gas atmosphere) | W (tungsten in a controlled gas atmosphere) | |
| Coil Voltage Range | 24…250V AC 24…250V DC |
24…250V AC 24…250V DC |
|
| Coil Power |
Sealed Voltage Range: 15… +10% |
5.5 VA, 50/60 Hz 5.5 W DC |
1.7 VA, 50/60 Hz (latch or unlatch) 1.7 W DC |
| Inrush | 5.5 VA, 50/60 Hz 5.5 W DC |
1.7 VA, 50/60 Hz (latch or unlatch) 1.7 W DC |
|
| Pickup Time | 30 ms | 75 ms min. latch pulse | |
| Dropout Time | 30 ms | 75 ms min. unlatch pulse | |
| Operating Temperature | 40…+60 °C (40…+140 °F) | 40…+60 °C (40…+140 °F) | |
| Mounting | Panel mount | Panel mount | |
Bulletin 700-R Operating Coils
Approximate Dimensions
Dimensions are shown in millimeters (inches) shown. Dimensions are not intended to be used for manufacturing purposes.
|
|
|
|
|
|
|
Secure the mounting strip with 2 screws at each end relay position. Use a minimum of one screw at the 3rd, 5th, 7th, etc., relay positions. Alternate between upper and lower horizontal slots.
|
| Bulletin 700-R, -RM Relays | ||||||||||||||
| Type of Relay | No. of Poles |
Open Type Without Enclosures |
Approx. Ship Wt. [kg (lb)] |
Type 1 General Purpose Enclosure |
Approx. Ship Wt. [kg (lb)] |
|||||||||
| Drawing Number |
A Wide |
B High |
C Deep |
D | A Wide |
B High |
C Deep |
D | E | |||||
| R | Bulletin 700 and Bulletin 700DC |
2…4 | 1 | 55.56 (2-3/16) |
88.90 (3-1/2) |
92.25 (3-3/8) |
79.38 (3-1/8) |
0.91 (2) |
104.78 (4-1/8) |
185.74 (7-5/16) |
103.19 (4-1/16) |
146.05 (5-3/4) |
85.73 (3-3/8) |
1.81 (4) |
| 5…8 | 2 | 55.56 (2-3/16) |
88.90 (3-1/2) |
111.13 (4-3/8) |
79.38 (3-1/8) |
1.02 (2-1/4) |
112.71 (4-7/16) |
228.60 (9) |
120.65 (4-3/4) |
206.38 (8-1/8) |
92.08 (3-5/8) |
2.49 (5) |
||
| R with Bulletin 852S Timer |
Bulletin 700 and Bulletin 700DC |
2…4 | 3 | 55.56 (2-3/16) |
88.90 (3-1/2) |
165.1 (6-1/2) |
79.38 (3-1/8) |
1.25 (2-3/4) |
— | — | — | — | — | — |
| RM | Bulletin 700 and Bulletin 700DC |
2…4 | 1 | 55.56 (2-3/16) |
88.90 (3-1/2) |
95.25 (3-3/8) |
79.38 (3-1/8) |
0.91 (2) |
104.78 (4-1/8) |
185.74 (7-5/16) |
103.19 (4-1/16) |
146.05 (5-3/4) |
85.73 (3-3/8) |
1.81 (4) |
| 5…8 | 2 | 55.56 (2-3/16) |
89.90 (3-1/2) |
111.13 (4-3/8) |
79.38 (3-1/8) |
1.02 (2-1/4) |
112.71 (4-7/16) |
228.60 (9) |
120.65 (4-3/4) |
206.38 (8-1/8) |
92.08 (3-5/8) |
2.49 (5) |
||
| RM with Bulletin 852S Timer |
Bulletin 700 and Bulletin 700DC |
2…4 | 3 | 55.56 (2-3/16) |
88.90 (3-1/2) |
165.1 (6-1/2) |
79.38 (3-1/8) |
1.25 (2-3/4) |
— | — | — | — | — | — |