Bulletin 700-CF Control Relay

Product Overview


Click to enlarge - 700-CF40E_GS


Bulletin 700-CF — Control Relay


Standards Compliance


Certifications


Product Selection

Build a Catalog Number


4-Pole AC Coil Voltage (Ratings for 700-CF Only)

AC-12 AC-15 Connection
Diagrams
Contacts Standard
Contacts
Cat. No.‡ 
Gold Plated
Bifurcated
Contacts
Cat. No.⋆ 
Master
Contacts
Cat. No.⋆ 
Ith [A] Ie [A] Click to enlarge - 700CF-186-2 Click to enlarge - 700SCF-197-6
40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V N.O. N.C.
20 20 10 10 10 6 2.5 1 1 Click to enlarge - 700CF-186-4 2 2 700-CF220Ä 700-CFB220Ä 700-CFM220Ä
Click to enlarge - 700CF-186-5 3 1 700-CF310Ä 700-CFB310Ä 700-CFM310Ä
Click to enlarge - 700CF-186-6 4 0 700-CF400Ä 700-CFB400Ä 700-CFM400Ä
Click to enlarge - 700CF-186-7 0 4 700-CF040Ä 700-CFB040Ä
  
⋆ All Cat. Nos. are factory-stocked.
‡  For spring clamp terminals, insert R after 700-C. Example: Cat. No. 700-CRF220D.

Ä AC Coil Voltage Code

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700-CF220Ä becomes Cat. No. 700-CF220D for 120V, 60 Hz

[V] 12 24 32 36 42 48 100 100...
110
110 120 127 200 200...
220
208 208...
240
220...
230
230 230...
240
240 277 347 380 380...
400
400 400...
415
440 480 500 550 600
50 Hz R K V W X Y KP D P S KG L F VA T N G B M C
60 Hz Q J V X KP D KG H L A T I E N B C
50/60 Hz KJ KY KP KD KG KL KL KF KA KN KB
  

4-Pole DC Coil Voltage (Ratings for 700-CF Only)

AC-12 AC-15 Connection
Diagrams
Contacts Standard
Contacts
Cat. No.§ 
Gold Plated
Bifurcated
Contacts
Cat. No.⋆ 
Master
Contacts
Cat. No.⋆ 
Ith [A] Ie [A] Click to enlarge - 700CF-186-2 Click to enlarge - 700SCF-197-6
40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V N.O. N.C.
20 20 10 10 10 6 2.5 1 1 Click to enlarge - 700CF-186-10 2 2 700-CF220Ä 700-CFB220Ä 700-CFM220Ä
Click to enlarge - 700CF-186-11 3 1 700-CF310Ä 700-CFB310Ä 700-CFM310Ä
Click to enlarge - 700CF-186-12 4 0 700-CF400Ä 700-CFB400Ä 700-CFM400Ä
  
⋆ All Cat. Nos. are factory-stocked.
§ For spring clamp terminals, insert R after 700-C. Example: Cat. No. 700-CRF220ZJ.

⋆  Ratings for Bulletin 700-CFB and 700-CFM are on Specifications

Ä DC Coil Voltage Code♣ 

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. example: Cat. No. 700-CF220Ä becomes Cat. No. 700-CF220ZJ for 24V DC

[V] 9 12 24 36 48 48...72 60 64 72 80 110 110...125 115 125 220 220...250 230 250
Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
Standard diode DJ
Electronic with diode EQ EJ EY ED EA
  
♣ When ordering DJ coil with built-in surge suppression, the DJ is not polarity sensitive. Drop out time: 14…20 ms.

6- and 8-Pole Relays

Click to enlarge - 700CFZ-1420
Cat. No. 700-CFZ1420


Click to enlarge - 700CFZ-0530
Cat. No. 700-CFZ0530


Control Relays with Overlapping Side-Mounted Contacts

AC-12 AC-15 Left
Aux.
Relay
Arrangement
Right
Aux.
Contacts Overlapping
Side-Mounted
Contacts
Cat. No.
Ith [A] Ie [A]
  40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V N.O. N.C. N.O. N.C.
Main
Relay
20 20 10 10 10 6 2.5 1 1 Click to enlarge - 700CF-187-5 4 0 1 1 700-CFZ1510Ä
Click to enlarge - 700CF-187-4 3 1 1 1 700-CFZ1420Ä
Side
Contacts
10 10 6 6 5 3 1.6 1 1 Click to enlarge - 700CF-187-5 2 2 1 1 700-CFZ1330Ä
Click to enlarge - 700CF-187-6 4 0 2 2 700-CFZ2620Ä
Click to enlarge - 700CF-187-7 3 1 2 2 700-CFZ2530Ä
Click to enlarge - 700CF-187-8 2 2 2 2 700-CFZ2440Ä
  
  

Control Relays with Standard Side-Mounted Contacts

AC-12 AC-15 Left
Aux.
Relay
Arrangement
Right
Aux.
Contacts Standard
Side-Mounted
Contacts
Cat. No.
Ith [A] Ie [A]
  40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V N.O. N.C. N.O. N.C.
Main
Relay
20 20 10 10 10 6 2.5 1 1 Click to enlarge - 700CF-187-9 4 0 1 1 700-CFZ0510Ä
Click to enlarge - 700CF-187-10 3 1 1 1 700-CFZ0420Ä
Click to enlarge - 700CF-187-11 2 2 1 1 700-CFZ0330Ä
Side
Contacts
10 10 6 6 5 3 1.6 1 1 Click to enlarge - 700CF-187-12 4 0 2 2 700-CFZ0620Ä
Click to enlarge - 700CF-187-13 3 1 2 2 700-CFZ0530Ä
Click to enlarge - 700CF-187-14 2 2 2 2 700-CFZ0440Ä
  
⋆ All Cat. Nos. are factory stocked.
  

Ä AC Coil Voltage Code

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700-CFZ0510Ä becomes Cat. No. 700-CFZ0510F.

[V] 12 24 32 36 42 48 100 100...
110
110 120 127 200 200...
220
208 208...
240
220...
230
230 230...
240
240 277 347 380 380...
400
400 400...
415
440 480 500 550 600
50 Hz R K V W X Y KP D P S KG L F VA T N G B M C
60 Hz Q J V X KP D KG H L A T I E N B C
50/60 Hz KJ KY KP KD KG KL KL KF KA KN KB
  

Assignment of Contacts

Device Combinations in Accordance with IEC 60947-1 / -4-1

Auxiliary Contact Blocks Control Relays 700-CF (AC and DC Control)
  Circuit Diagram Control 700-CFÄ220 700-CFÄ310 700-CFÄ400
Click to enlarge - 700-CF_220_Dia Click to enlarge - 700-CF_310_Dia Click to enlarge - 700-CF_400_Dia
Front Mounting ⋆   
100-FA02 Click to enlarge - 100-FA02_Dia AC/DC 22E + 02E = 24Y 31E + 02E = 33Y 40E + 02E = 42Y
100-FA11 Click to enlarge - 100-FA11_Dia AC/DC 22E + 11E = 33Y 31E + 11E = 42Y 40E + 11E = 51Y
100-FA20 Click to enlarge - 100-FA20_Dia AC/DC 22E + 20E = 42Y 31E + 20E = 51Y 40E + 20E = 60Y
100-FA22 Click to enlarge - 100-FA22_Dia AC/DC 22E + 22E = 44Y 31E + 22E = 53Y 40E + 22E = 62Y
100-FA31 Click to enlarge - 100-FA31_Dia AC/DC 22E + 31E = 53Y 31E + 31E = 62Y 40E + 31E = 71Y
100-FA40 Click to enlarge - 100-FA40_Dia AC/DC 22E + 40E = 62Y 31E + 40E = 71Y 40E + 40E = 80Y
100-FAL22 Click to enlarge - 100-FAL22_Dia AC/DC 22E + L22E = L44Y 31E + L22E = L53Y 40E + L22E = L62Y
  
⋆ Control relay and auxiliary contact block AC/DC max. 4 N. C.

Accessories

Auxiliary Contacts

  Description N.O. N.C. Connection Diagrams For Use With Standard
Contacts‡ 
Bifurcated
Contacts
Cat. No. Cat. No.
Click to enlarge - 700CF-188-1 Auxiliary Contact Blocks for Front Mounting§ 
2- and 4-pole
Quick and easy mounting without tools
Electronic-compatible contacts down to 17V, 5 mA
Mechanically linked performance between N.O. and N.C. poles and to the main relay poles (except for L types)
Models with equal function with several terminal numbering choices
1L = Late break N.C./early make N.O.
Bifurcated version for switching down to 5V, 3 mA
0 2 Click to enlarge - 700CF-188-3 700-CF 100-FA02 100-FAB02
1 1 100-FA11 100-FAB11
2 0 100-FA20 100-FAB20
1L 1L 100-FAL11
0 4 100-FA04 100-FAB04
Click to enlarge - 700CF-188-2 1 3 100-FA13 100-FAB13
2 2 100-FA22 100-FAB22
3 1 100-FA31 100-FAB31
4 0 100-FA40 100-FAB40
1+1L 1+1L 100-FAL22
  
‡  For spring clamp terminals, insert CR after 100-. Example: Cat. No. 100-CRFA02.

  Description N.O. N.C. Connection Diagrams For Use With Cat. No.
Click to enlarge - 700CF-188-4 Auxiliary Contact Blocks for Side Mounting without Sequence Terminal Designations§ 
1- and 2-pole
Two-way numbering for right or left mounting on the contactor
Quick and easy mounting without tools
Electronic-compatible contacts down to 17V, 10 mA
Mirror contact performance to the main relay poles
1L = Late break N.C./early make N.O.
0 1 Click to enlarge - 700CF-188-6 700-CF 100-SA01
1 0 100-SA10
0 2 100-SA02
1 1 100-SA11
2 0 100-SA20
1L 1L 100-SAL11
Click to enlarge - 700CF-188-5
  
§  For maximum no. of contacts: Refer to the following tables.

700-CF (AC and DC electronic coils), vertical mounting, 60 °C♦ 
Cat. No.
700…
Max. N.O.
Side Aux.
Max. N.C.
Side Aux.
Max. N.O.
Front Aux.
Max. N.C.
Front Aux.
Max. N.O.
Front + Side
Aux.
Max. N.C.
Front + Side
Aux.
Max. N.O. + N.C.
Front +
Side Aux.
CF400 2 4 4 4 6 7 8
CF310 2 4♣  4 4∆  6 5 8
CF220 4 4♣  4 2 8 5 8
CF040 2 2 4 0 6 2 6
  
♣ With no front auxiliary contacts installed. Otherwise 3 N.C. Maximum
∆ With no side auxiliary contacts installed. Otherwise 3 N.C. Maximum
♦ For other operating conditions, please contact your local Rockwell Automation sales office or Allen‑Bradley distributor.

700-CF (DC conventional coils), vertical mounting, 60 °C ♦ 
Cat. No.
700…
Max. N.O.
Side Aux.
Max. N.C.
Side Aux.
Max. N.O.
Front Aux.
Max. N.C.
Front Aux.
Max. N.O.
Front +
Side Aux.
Max. N.C.
Front +
Side Aux.
Max.
N.O. + N.C.
Front +
Side Aux.
CF400 2 2 4 4∆  6 5 8
CF310 2 2 4 4∆  6 5 8
CF220 2 2 4 2 6 4 8
  
∆ With no side auxiliary contacts installed. Otherwise 3 N.C. Maximum
♦ For other operating conditions, please contact your local Rockwell Automation sales office or Allen‑Bradley distributor.

♦ Side or front mounted auxiliary contacts only, not both.


Control Modules

  Description Connection Diagrams Reset Time Repeat Accuracy Delay For Use With Cat. No.
Click to enlarge - 700CF-189-1 Pneumatic Timing Modules⋆  ON-Delay
Pneumatic timing element contacts switch after the delay time. The contacts on the main control relay continue to operate without delay.
Click to enlarge - 700CF-189-2 25…90 ms for AC Coils

47…85 ms
for DC coils
+/-10% 0.3…30 s 700-CF all⋆  100-FPTA30
1.8…180 s 100-FPTA180
Pneumatic Timing Modules OFF-Delay
Pneumatic timing element contacts switch after the delay time. The contacts on the main control relay continue to operate without delay.
Click to enlarge - 700CF-189-3 0.3…30 s 100-FPTB30
1.8…180 s 100-FPTB180
Click to enlarge - 100-ETA3 L_gs- Electronic Timing Modules — On-Delay
Delay of the control relay coil assembly.
The control relay is energized at the end of the delay time.
Click to enlarge - 100-C_104-C-87-5 100 ms +/-1% 0.1…3 s 700-CF
110…240V AC
110…250V DC
coils
100-ETA3
1…30 s 100-ETA30
10…180 s 100-ETA180
0.1…3 s 700-CF
24…48V DC
coils
100-ETAZJ3
1…30 s 100-ETAZJ30
10…180 s 100-ETAZJ180
Click to enlarge - 100-ETB3 L_gs Electronic Timing Modules — Off-Delay
Delay of the control relay coil assembly.
After interruption of the control signal, the control relay is deenergized at the end of the delay time.
Click to enlarge - 100-C_104-C-87-6 100 ms +/-1% 0.3…3 s 700-CF
110…240V AC
coils
100-ETB3
1…30 s 100-ETB30
10…180 s 100-ETB180
0.3…3 s 700-CF
24V AC
coils
100-ETBKJ3
1…30 s 100-ETBKJ30
Cat. No. 100-ETB30 10…180 s 100-ETBKJ180
  
⋆ On-Delay modules cannot be used with side-mounted auxiliary contacts on DC coil relays.

  Description Connection
Diagrams
For Use With Cat. No.
Click to enlarge - 700CF-190-1 Mechanical Latch
Following relay latching, the relay coil is immediately de-energized (off) by the N.C. auxiliary contact (65-66).
Electrical or manual release
1 N.O. + 1 N.C. auxiliary contacts
Click to enlarge - 700CF-190-2 700-CF with AC coils 100-FL11Ä
Cat. No. 100-FLÄ
 
‡ All Cat. Nos. are factory stocked.
  

  Description Connection
Diagrams
For Use With Cat. No.‡ 
Click to enlarge - Relays_Timers-21-2 Surge Suppressors
For limitation of coil switching transients.
Plug-in, coil mounted
RC Module
AC Operating
Mechanism
24…48V
50/60 Hz
Click to enlarge - 700CF-190-4 700-CF with AC coils 100-FSC48
110…280V
50/60 Hz
100-FSC280
380…480V
50/60 Hz
100-FSC480
Varistor Module
AC/DC Operating
Mechanism
12…55V AC/
12…77V DC
Click to enlarge - 700CF-190-5 700-CF all 100-FSV55
56…136V AC/
78…180V DC
100-FSV136
137…277V AC/
181…350V DC
100-FSV277
278…575V AC 100-FSV575
Diode Module
DC Operating
Mechanism
Dropout Time
70…95 ms
12…250V DC Click to enlarge - 700CF-190-6 700-CF with DC coils 100-FSD250
  
‡ All Cat. Nos. are factory stocked.
  
‡  For spring clamp terminals, insert CR after 100-. Example: Cat. No. 100-CRFSC48.

Ä Coil Voltage Code

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 100-FL11Ä becomes Cat. No. 100-FL11J.§ 

[V] 24 48 100 110 120 230...240 240 277 380...400 400...415 440 480
50 Hz K Y KP D VA T N G B
60 Hz J D A T N B
  
§ For special voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

  Description (Relays) Connection
Diagrams
For Use With (Relays) Cat. No.
Click to enlarge - Relays_Timers-21-3 DC Interface (electronic)
Interface between the DC control signal (PLC) and the AC operating mechanism of the control relay.
Control (input) voltage
12V DC
18…30V DC (24V nominal)
48V DC
Requires no additional surge suppression on the relay coils
Input:
18…30V DC
Output:
110…240V AC
Click to enlarge - 700CF-191-2 700-CF with 110…240V AC
coils
100-JE
Input:
12V DC
Output:
110…240V AC
100-JE12
Input:
48V DC
Output:
110…240V AC
100-JE48
Cat. No. 100-JE
  
⋆ All Cat. Nos. are factory stocked.
  

  Cat. No. 100-JE Cat. No. 100-JE12 Cat. No. 100-JE48
Electrical
Input Voltage 24V DC 12V DC 48V DC
Input Voltage Range 18…30V DC 6…12V DC 35…48V DC
Output Voltage 110…240V AC 110…240V AC 110…240V AC
Power Consumption 0.1…0.4 W 0.02…0.12 W 0.2…0.5 W
Minimum Actuation 5V DC, 2 mA DC 5V DC, 2 mA DC 5V DC, 2 mA DC
Mechanical
Finger Protection IP20 IP20 IP20
Pickup Time 0…10 ms + pickup time of the
contactor
0…10 ms + pickup time of the
contactor
0…10 ms + pickup time of the
contactor
Dropout Time 0…10 ms + dropout time of the contactor 0…10 ms + dropout time of the contactor 0…10 ms + dropout time of the contactor
Max. Cycles Per Second 2⋆  2⋆  2⋆ 
Isolation/Breakdown Voltage In: 50V, Out: 250V In: 50V, Out: 250V In: 50V, Out: 250V
Rated Impulse Withstand Voltage 4 kV 4 kV 4 kV
Environmental
Ambient Temperature Range -25…60 °C -25…60 °C -25…60 °C
Storage Temperature Range -50…+80 °C -50…80 °C -50…80 °C
Operating Life 100+ million ops 100+ million ops 100+ million ops
Construction
Wire Size Range Flexible wire 1 Wire 0.5…2.5 mm2 0.5…2.5 mm2 0.5…2.5 mm2
2 Wire 0.75…2.5 mm2 0.75…2.5 mm2 0.75…2.5 mm2
Solid wire 1 Wire 1.0…2.5 mm2 1.0…2.5 mm2 1.0…2.5 mm2
2 Wire 1.0…2.5 mm2 1.0…2.5 mm2 1.0…2.5 mm2
Solid and Stranded 18…14 AWG 18…14 AWG 18…14 AWG
Tightening Torque 1…1.5 N•m/7…15 lb•in 1…1.5 N•m/7…15 lb•in 1…1.5 N•m/7…15 lb•in
Type of Light LED LED LED
  
⋆ To consider the maximum operations/hour of the relays.

Assembly Components

  Description For Use With Pkg. Quantity⋆  Cat. No.
Click to enlarge - 700CF-192-1 Protective Covers
Provides protection against unintended manual operation
700-CF all 1 100-SCCA
Cat. No. 100-SCCA
Click to enlarge - 700CF-192-2 Protective Covers
  • Provides protection against unintended manual operation

  • For contactors and front-mounted auxiliary contacts, pneumatic timers, and latches
  • 100-FA, -FB, -FC, -FP, -FL; 10 100-SCFA
    Cat. No. 100-SCFA
      
    ⋆ All Cat. Nos. are factory stocked.
      

    Marking Systems

    Uniform labelling materials for contactors, motor startup equipment, relays, and circuit breakers.

      Description Pkg. Quantity⋆  Cat. No.
    Click to enlarge - 700CF-192-3 Label Sheet
    105 self-adhesive paper labels each, 6 x 17 mm
    10 100-FMS
    Click to enlarge - 700CF-192-4 Marking Tag Sheet
    160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover
    10 100-FMP
    Transparent Cover
    To be used with marking tag sheets
    100 100-FMC
    Click to enlarge - 700CF-192-5 Marking Tag Adapters
    To be used with marking tag: System V4/V5
    100 100-FMA1
    System 1492 W 100-FMA2
      
      
    ⋆ Must be ordered in multiples of package quantities.

    Coils

      AC Coil Code AC Voltages Cat. No.
    700-CF
    DC Coil Code DC Voltages Cat. No.
    700-CF
    50Hz 60Hz 50/60Hz
    Click to enlarge - 700CF-192-6 Q 12V TA006 ZR 9V TA766
    R 12V TA404 ZQ 12V TA708
    J 24V TA013 DJ 24V Diode TA714M
    K 24V TA407 ZJ 24V TA714
    KJ 24V TA855 ZW 36V TA719
    V 32V 36V TA481 ZY 48V TA724
    W 36V TA410 ZZ 60V TA774
    X 42V 48V TA482 ZB 64V TA727
    Y 48V TA414 ZG 72V TA728
    KY 48V TA860 ZE 80V TA729
    KP 100V 100 - 110V 100V TA861 ZD 110V TA733
    D 110V 120V TA473 ZP 115V TA734
    KD 110V TA856 ZS 125V TA737
    P 120V TA425 ZA 220V TA747
    S 127V TA428 ZF 230V TA749
    KG 200V 200 - 220V 200V TA862 ZT 250V TA751
    H 208V TA049
    L 200 - 220V 208 - 240V TA296
    KL 200 - 230V TA864
    A 220V 240V TA474
    F 220 - 230V 260V TA441
    KF 230V TA851
    VA 230 - 240V TA440
    T 240V 277V TA480
    KA 240V TA858
    I 347V TA065
    E 380V TA067
    N 380 - 400V 440V TA071
    KN 400V TA863
    G 400-415V TA457
    B 440V 480V TA475
    KB 440V TA859
    M 500V TA479
    C 550V 600V TA476
      

    Specifications

    General

      Main Relay
    Cat. Nos.
    700-CF, 700S-CF
    Front Mounted Standard Auxiliary Contacts Main Relay
    Cat. No.
    700-CFB, 700S-CFB
    Master Relay
    Cat. No.
    700-CFM
    Front Mounted Bifurcated Auxiliary Contacts Side-mounted Auxiliary Contacts
    Contact Ratings — NEMA A600, P600 A600, Q600 A600, Q600 2 x A600, P600 A600, Q600 A600, Q600
    Min. Contact Rating 17V, 10 mA 17V, 5 mA 8V, 5 mA 5V, 3 mA 17V, 10 mA
    Contact Ratings — IEC AC-15 (solenoids, contactors) at rated voltage
    IEC 60947-5-1
    24V 10 A 6 A 3 A 15 A 3 A 6 A
    48V 10 A 6 A 3 A 15 A 3 A 6 A
    120V 10 A 6 A 3 A 15 A 3 A 6 A
    240V 10 A 5 A 3 A 15 A 3 A 5 A
    400V 6 A 3 A 2 A 7.5 A 2 A 3 A
    480V/500V 2.5 A 1.6 A 1.2 A 5 A 1.2 A 1.6 A
    600V 1 A 1 A 0.7 A 2 A 0.7 A 1 A
    690V 1 A 1 A 0.7 A 2 A 0.7 A 1 A
    AC-12 (Control of resistive loads)
    IEC 60947-5-1
    40 °C Ith 20 A 10 A 10 A 20 A 10 A 10 A
    230V 8 kW
    400V 14 kW
    690V 24 kW
    60 °C Ith 20 A 6 A 6 A 20 A 6 A 6 A
    230V 8 kW
    400V 14 kW
    690V 24 kW
    DC-12 Switching DC Loads
    L/R < 1ms, Resistive Loads
    IEC 60947-5-1
    24V 15 A 10 A 6 A 20 A 6 A 6 A
    48V 10 A 9 A 3.2 A 20 A 3.2 A 3.2 A
    110V 6 A 3.5 A 1 A 8 A 1 A 1 A
    220V 1 A 0.7 A 0.5 A 1.5 A 0.5 A 0.5 A
    440V 0.4 A 0.2 A 0.2 A 0.4 A 0.2 A 0.2 A
    DC-13 IEC 60947-5-1, Solenoids and contactors 24V 5 A 5 A 2.5 A 5 A 2.5 A 5 A
    48V 3 A 3 A 1.5 A 3 A 1.5 A 2.5 A
    110V 1.2 A 1.2 A 0.6 A 1.2 A 0.6 A 0.68 A
    220V 0.6 A 0.6 A 0.3 A 0.6 A 0.3 A 0.32 A
    440V 0.3 A 0.15 A 0.15 A 0.3 A 0.15 A 0.15 A
      

    Click to enlarge - 700CF-193-1 Location of welded N.O. contacts State of N.C. Contacts if N.O. contact welds
    Main Front aux. Side aux.
    Main Open Open Open⋆ 
    Mechanically Linked Contacts‡  Front aux. Open Open
      
    ⋆ Side mounted auxiliary contacts provide “mirror contact” performance with main poles only.
    ‡ Defined in IEC 60947-5-1 annex L. Mechanically linked is a relationship between contacts of opposite types (i.e., N.O. and N.C.).

      Cat. No. 700-CF Aux./Pneumatic Timer Contact (Front-mounted)
    Mechanical Life [Mil] 15 5
    Electrical Life AC-15
    (240V, 3 A)
    [Mil] 1.5 1.5
    Weight AC Coil [g] 390
    Terminal Cross-Sections
    Terminal Type Click to enlarge - 700CF-193-3 Click to enlarge - 700CF-193-3
    Terminal Size per IEC60 947-1 2 x A4 2 x A4
    Click to enlarge - 700CF-193-2 Solid/ Stranded 1 Conductor [mm2] 1.5…6 0.5…2.5
    ♣  2 Conductor [mm2] 1.5…6 0.75…2.5
    Max. Wire Size per UL/CSA [AWG] 16…10 18…14
    Tightening Torque [lb·in] 13.3…17.7 8.9…13.3
    Tightening Torque [N·m] 1.5…2.0 1…1.5
      
    ♣ For 16 or more strands, end ferrule is required.

    DC Switching Ratings for 700-CF Main Poles in Series (Resistive Load at 60 °C)
      1 pole 2 poles 3 poles
    24/48V 25/20 A 25 A 25 A
    125V 6 A 25 A 25 A
    220V 1.5 A 8 A 25 A
    440V 0.4 A 1 A 3 A
      

    Control Circuit

      Cat. No. 700-CF
    Operating Voltage
    AC 50/60 Hz Pickup [x Us] 0.85…1.1
    Dropout [x Us] 0.3…0.6
    DC⋆  Pickup [x Us] 0.8…1.1
    Dropout [x Us] 0.1…0.6
    Coil Consumption
    AC 50/60 Hz Inrush [VA/W] 70/50
    Seal [VA/W] 8/2.6
    DC (conventional) Inrush/Seal [W] 6.5
    DC (electronic) Inrush (avg./ peak) [W] 10/17
    Seal [W] 1.7
    Operating Times
    AC 50/60 Hz Pickup Time [ms] 15…30
    Dropout Time [ms] 10…60
    DC (conventional) Pickup Time [ms] 40…70
    Dropout Time [ms] 7…15
    DC (electronic) Pickup Time [ms] 25…50
    Dropout Time [ms] 25…50
    Min OFF time [ms] 200
    Max. ripple ± 15%
    Latch Attachment Release, 100-FL
    Coil Consumption AC [VA/W] 45/40
    DC [W] 25
    Contact Signal Duration [min./max] 0.03…15 s
    Timing Attachment
    Reset Time, 100-ETA, 100-ETB at min. time setting [ms] 10
    at max. time setting [ms] 70
    Repeat Accuracy ± 10%
      
    ⋆ For 9V DC, code ZR, use operating voltage 0.65…1.3 x Us.
    For 24V DC, code ZJ, DJ, or EJ use operating voltage 0.7…1.25 x Us.
    For 110V DC, code ED use operating voltage 0.7…1.25 x Us.

    General

      Cat. No. 700-CF
    Rated Insulation Voltage Ui
    IEC 690V
    UL; CSA 600V
    Rated Impulse StrengthUimp 6 kV
    High Test Voltage
    1 minute (per IEC 60947-4)
    2500V
    Rated Voltage Ue
    AC 115, 230, 400, 500, 690V
    DC 24, 48, 110, 220, 440V
    Short-Circuit Protection gG Fuse 10 A
    Rated Frequency 50/60 Hz, DC
    Ambient Temperature
    Storage –55…+80 °C (–67…176 °F)
    Operation at nominal current –25…+60 °C (–13…140 °F)
    15% current reduction
    for AC-12 at > 60 °C
    –25…+70 °C (–13…158 °F)
    Corrosion Resistance humid-alternating climate, cyclic,
    per IEC 60068-2-30 and
    DIN 50 016, 56 cycles
    Altitude 2000 m above mean sea level, per
    IEC60 947-4
    Type of Protection
    IP2X (IEC 60529 and DIN 40050) in connected state
    Shock Resistance IEC 60068-2: Half sinusoidal shock
    11 ms, 30 G (in 3 directions)
    Vibration Resistance IEC 60068-2: Static >2 G, in normal
    position no malfunction <5 G
      

    Utilization Category Table from EN 60947-5-1

    Verification of Making and Breaking Capacities of Switching Elements Under Normal Conditions
    Corresponding to the Utilization Categories‡ 
    Utilization
    Category
    Normal Condition of Use
    Make§  Break§  Number and Rate of Making and Breaking operations
    I/Ie U/Ue cos y I/Ie U/Ue cos y No. operating
    cycles♣ 
    Operating cycles per
    minute
    ON time [s]♦ 
    AC-12♠  1 1 0.9 1 1 0.9 6050 6 0.05
    AC-13♠  2 1 0.65 1 1 0.65 6050 6 0.05
    AC-14♠  6 1 0.3 1 1 0.3 6050 6 0.05
    AC-15♠  10 1 0.3 1 1 0.3 6050 6 0.05
    DC T0.95 T0.95
    DC-12 1 1 1 ms 1 1 1 ms 6050 6 0.05♦ 
    DC-13 1 1 6 x P∆  1 1 6 x P∆  6050 6 0.05♦ 
    DC-14♠  10 1 15 ms 1 1 15 ms 6050 0.05♦ 
      
    Ie Rated operational current, I Current to be made or broken
    Ue Rated operational voltage, U Voltage before make
    PUeIe Steady-state power consumption (W)
    T0.95 Time to reach 95% of the steady-state current (ms)
    ‡ See sub-clause 8.3.3.5.2.
    § For tolerances on test quantities, see sub-clause 8.3.2.2.
    ♣ The first 50 operating cycles shall be run at U/Ue=1.1 with the loads set at Ue.
    ∆ The value “6 x P” results from an empirical relationship which is found to represent most DC magnetic loads to an upper limit of P = 50 W, e.g., 6 x P= 300 W.
    ♦ The ON time shall be at least equal to T0.95.
    ♠ Where the break current differs from the make current value, the ON time refers to the make current value after which the current is reduced to the break current value for a suitable period e.g., 0.05 s.

    Contact Rating Table from EN 60947-5-1

    Examples of Contact Rating Designation Based on Utilization Categories
    NEMA
    Designation ⋆ 
    IEC
    Utilization Category
    Conventional Thermal
    Current Ithe (A)
    Rated Operational Current Ie (A) at Rated
    Operational Voltage Ue
    VA Rating
    AC 120V 240V 380V 480V 500V 600V Make Break
    A150 AC-15 10 6 7200 720
    A300 AC-15 10 6 3 7200 720
    A600 AC-15 10 6 3 1.9 1.5 1.4 1.2 7200 720
    B150 AC-15 5 3 3600 360
    B300 AC-15 5 3 1.5 3600 360
    B600 AC-15 5 3 1.5 0.95 0.75 0.72 0.6 3600 360
    C150 AC-15 2.5 1.5 1800 180
    C300 AC-15 2.5 1.5 0.75 1800 180
    C600 AC-15 2.5 1.5 0.75 0.47 0.375 0.35 0.3 1800 180
    D150 AC-14 1.0 0.6 432 72
    D300 AC-14 1.0 0.6 0.3 432 72
    E150 AC-14 0.5 0.3 216 36
    DC 125V 250V 440V 500V 600V
    N150 DC-13 10 2.2 275 275
    N300 DC-13 10 2.2 1.1 275 275
    N600 DC-13 10 2.2 1.1 0.63 0.55 0.4 275 275
    P150 DC-13 5 1.1 138 138
    P300 DC-13 5 1.1 0.55 138 138
    P600 DC-13 5 1.1 0.55 0.31 0.27 0.2 138 138
    Q150 DC-13 2.5 0.55 69 69
    Q300 DC-13 2.5 0.55 0.27 69 69
    Q600 DC-13 2.5 0.55 0.27 0.15 0.13 0.1 69 69
    R150 DC-13 1.0 0.22 28 28
    R300 DC-13 1.0 0.22 0.1 28 28
      
    ⋆ This letter stands for the conventional thermal current and identifies AC or DC: e.g., B = 5 A AC. The number that follows is the rated insulation voltage.

    Approximate Dimensions

    Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended for manufacturing purposes.

    Mounting Position

    Click to enlarge - 700CF-196-1
    ⋆ May be mounted to 35 mm EN 50 022 DIN Rail.


    Click to enlarge - 700CF-196-2


    Click to enlarge - 700CF-196-3


    AC and DC Control Relays with 12V or 24V DC Electronic Coil

    Type a b c c1 c2 Æd d1 d2
    700-CF, -CFB,
    -CFM
    45
    (1-25/32)
    81
    (3-3/16)
    80.5
    (3-11/64)
    75.5
    (3-3/32)
    6
    (1/4)
    2 screws
    4.5
    (3/16)
    60
    (2-23/64)
    35
    (1-25/64)
      

    DC Control Relays with 110V or 220V DC Electronic Coil

    Type a b c c1 c2 Æd d1 d2
    700-CF, -CFB,
    -CFM
    45
    (1-25/32)
    105
    (4-1/8)
    80.5
    (3-11/64)
    75.5
    (3-3/32)
    6
    (1/4)
    2 screws
    4.5
    (3/16)
    60
    (2-23/64)
    35
    (1-25/64)
      

    DC Control Relays

    Type a b c c1 c2 Æd d1 d2
    700-CF, -CFB,
    -CFM
    45
    (1-25/32)
    81
    (3-3/16)
    106.5
    (4-3/16)
    101.5
    (4)
    6
    (1/4)
    2 screws
    4.5
    (3/16)
    60
    (2-23/64)
    35
    (1-25/64)
      

    Accessories

    Relay with AC Control Relay DC Control Relay
    mm (inches) mm (inches)
    Auxiliary Contact for Front Mounting 2- or 4-pole c/c1 + 39 (c/c1 + 1 – 37/64) c/c1 + 39 c/c1 + 1 – 37/64)
    Auxiliary Contact for Side Mounting 1- or 2-pole a + 9 (a + 23/64) a + 9 (a + 23/64)
    Pneumatic Timing Module c/c1 + 58 (c/c1 + 2 – 23/64)
    Solid-state Timing Module on coil terminal side b + 24 (b + 15/16) b + 24 (b + 15/16)
    Mechanical Latching c/c1 + 61 (c/c1 + 2 – 31/64)
    DC Interface on coil terminal side b + 9 (b + 23/64)
    Surge Suppressor on coil terminal side b + 3 (b + 1/8) b + 3 (b + 1/8)
    Labelling with: label sheet +0 (+0) +0 (+0)
    marking tag with cover +0 (+0) +0 (+0)
    marking tag carrier for System V4/V5 +5.5 (+7/32) +5.5 (+7/32)
    marking tag carrier for System Bull. 1492W +5.5 (+7/32) +5.5 (+7/32)