Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > Industrial Relays and Timers > IEC Industrial Relays > Bulletin 700-CF Control Relay
Bulletin 700-CF Control Relay
| Introduction | Standards Compliance | Product Selection | Assignment of Contacts | Accessories | Specifications | Approximate Dimensions |
General
| Main Relay Cat. Nos. 700-CF, 700S-CF |
Front Mounted Standard Auxiliary Contacts | Main Relay Cat. No. 700-CFB, 700S-CFB |
Master Relay Cat. No. 700-CFM |
Front Mounted Bifurcated Auxiliary Contacts | Side-mounted Auxiliary Contacts | |||
| Contact Ratings — NEMA | A600, P600 | A600, Q600 | A600, Q600 | 2 x A600, P600 | A600, Q600 | A600, Q600 | ||
| Min. Contact Rating | 17V, 10 mA | 17V, 5 mA | 8V, 5 mA | — | 5V, 3 mA | 17V, 10 mA | ||
| Contact Ratings — IEC AC-15 (solenoids, contactors) at rated voltage IEC 60947-5-1 |
24V | 10 A | 6 A | 3 A | 15 A | 3 A | 6 A | |
| 48V | 10 A | 6 A | 3 A | 15 A | 3 A | 6 A | ||
| 120V | 10 A | 6 A | 3 A | 15 A | 3 A | 6 A | ||
| 240V | 10 A | 5 A | 3 A | 15 A | 3 A | 5 A | ||
| 400V | 6 A | 3 A | 2 A | 7.5 A | 2 A | 3 A | ||
| 480V/500V | 2.5 A | 1.6 A | 1.2 A | 5 A | 1.2 A | 1.6 A | ||
| 600V | 1 A | 1 A | 0.7 A | 2 A | 0.7 A | 1 A | ||
| 690V | 1 A | 1 A | 0.7 A | 2 A | 0.7 A | 1 A | ||
| AC-12 (Control of resistive loads) IEC 60947-5-1 |
40 °C | Ith | 20 A | 10 A | 10 A | 20 A | 10 A | 10 A |
| 230V | 8 kW | |||||||
| 400V | 14 kW | |||||||
| 690V | 24 kW | |||||||
| 60 °C | Ith | 20 A | 6 A | 6 A | 20 A | 6 A | 6 A | |
| 230V | 8 kW | |||||||
| 400V | 14 kW | |||||||
| 690V | 24 kW | |||||||
| DC-12 Switching DC Loads L/R < 1ms, Resistive Loads IEC 60947-5-1 |
24V | 15 A | 10 A | 6 A | 20 A | 6 A | 6 A | |
| 48V | 10 A | 9 A | 3.2 A | 20 A | 3.2 A | 3.2 A | ||
| 110V | 6 A | 3.5 A | 1 A | 8 A | 1 A | 1 A | ||
| 220V | 1 A | 0.7 A | 0.5 A | 1.5 A | 0.5 A | 0.5 A | ||
| 440V | 0.4 A | 0.2 A | 0.2 A | 0.4 A | 0.2 A | 0.2 A | ||
| DC-13 IEC 60947-5-1, Solenoids and contactors | 24V | 5 A | 5 A | 2.5 A | 5 A | 2.5 A | 5 A | |
| 48V | 3 A | 3 A | 1.5 A | 3 A | 1.5 A | 2.5 A | ||
| 110V | 1.2 A | 1.2 A | 0.6 A | 1.2 A | 0.6 A | 0.68 A | ||
| 220V | 0.6 A | 0.6 A | 0.3 A | 0.6 A | 0.3 A | 0.32 A | ||
| 440V | 0.3 A | 0.15 A | 0.15 A | 0.3 A | 0.15 A | 0.15 A | ||
| DC Switching Ratings for 700-CF Main Poles in Series (Resistive Load at 60 °C) | |||
| 1 pole | 2 poles | 3 poles | |
| 24/48V | 25/20 A | 25 A | 25 A |
| 125V | 6 A | 25 A | 25 A |
| 220V | 1.5 A | 8 A | 25 A |
| 440V | 0.4 A | 1 A | 3 A |
Control Circuit
| Cat. No. 700-CF | |||
| Operating Voltage | |||
| AC 50/60 Hz | Pickup | [x Us] | 0.85…1.1 |
| Dropout | [x Us] | 0.3…0.6 | |
| DC⋆ | Pickup | [x Us] | 0.8…1.1 |
| Dropout | [x Us] | 0.1…0.6 | |
| Coil Consumption | |||
| AC 50/60 Hz | Inrush | [VA/W] | 70/50 |
| Seal | [VA/W] | 8/2.6 | |
| DC (conventional) | Inrush/Seal | [W] | 6.5 |
| DC (electronic) | Inrush (avg./ peak) | [W] | 10/17 |
| Seal | [W] | 1.7 | |
| Operating Times | |||
| AC 50/60 Hz | Pickup Time | [ms] | 15…30 |
| Dropout Time | [ms] | 10…60 | |
| DC (conventional) | Pickup Time | [ms] | 40…70 |
| Dropout Time | [ms] | 7…15 | |
| DC (electronic) | Pickup Time | [ms] | 25…50 |
| Dropout Time | [ms] | 25…50 | |
| Min OFF time | [ms] | 200 | |
| Max. ripple | ± 15% | ||
| Latch Attachment Release, 100-FL | |||
| Coil Consumption | AC | [VA/W] | 45/40 |
| DC | [W] | 25 | |
| Contact Signal Duration | [min./max] | 0.03…15 s | |
| Timing Attachment | |||
| Reset Time, 100-ETA, 100-ETB | at min. time setting | [ms] | 10 |
| at max. time setting | [ms] | 70 | |
| Repeat Accuracy | ± 10% | ||
| ⋆ For 9V DC, code ZR, use operating voltage 0.65…1.3 x Us. For 24V DC, code ZJ, DJ, or EJ use operating voltage 0.7…1.25 x Us. For 110V DC, code ED use operating voltage 0.7…1.25 x Us. |
|||
General
| Cat. No. 700-CF | |
| Rated Insulation Voltage Ui | |
| IEC | 690V |
| UL; CSA | 600V |
| Rated Impulse StrengthUimp | 6 kV |
| High Test Voltage 1 minute (per IEC 60947-4) |
2500V |
| Rated Voltage Ue | |
| AC | 115, 230, 400, 500, 690V |
| DC | 24, 48, 110, 220, 440V |
| Short-Circuit Protection gG Fuse 10 A | |
| Rated Frequency | 50/60 Hz, DC |
| Ambient Temperature | |
| Storage | 55…+80 °C (67…176 °F) |
| Operation at nominal current | 25…+60 °C (13…140 °F) |
| 15% current reduction for AC-12 at > 60 °C |
25…+70 °C (13…158 °F) |
| Corrosion Resistance | humid-alternating climate, cyclic, per IEC 60068-2-30 and DIN 50 016, 56 cycles |
| Altitude | 2000 m above mean sea level, per IEC60 947-4 |
| Type of Protection | |
| IP2X (IEC 60529 and DIN 40050) | in connected state |
| Shock Resistance | IEC 60068-2: Half sinusoidal shock 11 ms, 30 G (in 3 directions) |
| Vibration Resistance | IEC 60068-2: Static >2 G, in normal position no malfunction <5 G |
Utilization Category Table from EN 60947-5-1
| Verification of Making and Breaking Capacities of Switching Elements Under Normal Conditions Corresponding to the Utilization Categories |
|||||||||
| Utilization Category |
Normal Condition of Use | ||||||||
| Make§ | Break§ | Number and Rate of Making and Breaking operations | |||||||
| I/Ie | U/Ue | cos y | I/Ie | U/Ue | cos y | No. operating cycles♣ |
Operating cycles per minute |
ON time [s]♦ | |
| AC-12♠ | 1 | 1 | 0.9 | 1 | 1 | 0.9 | 6050 | 6 | 0.05 |
| AC-13♠ | 2 | 1 | 0.65 | 1 | 1 | 0.65 | 6050 | 6 | 0.05 |
| AC-14♠ | 6 | 1 | 0.3 | 1 | 1 | 0.3 | 6050 | 6 | 0.05 |
| AC-15♠ | 10 | 1 | 0.3 | 1 | 1 | 0.3 | 6050 | 6 | 0.05 |
| DC | — | — | T0.95 | — | — | T0.95 | — | — | — |
| DC-12 | 1 | 1 | 1 ms | 1 | 1 | 1 ms | 6050 | 6 | 0.05♦ |
| DC-13 | 1 | 1 | 6 x P∆ | 1 | 1 | 6 x P∆ | 6050 | 6 | 0.05♦ |
| DC-14♠ | 10 | 1 | 15 ms | 1 | 1 | 15 ms | 6050 | — | 0.05♦ |
| Ie Rated operational current, I Current to be made or broken | |||||||||
| Ue Rated operational voltage, U Voltage before make | |||||||||
| PUeIe Steady-state power consumption (W) | |||||||||
| T0.95 Time to reach 95% of the steady-state current (ms) | |||||||||
| See sub-clause 8.3.3.5.2. | |||||||||
| § For tolerances on test quantities, see sub-clause 8.3.2.2. | |||||||||
| ♣ The first 50 operating cycles shall be run at U/Ue=1.1 with the loads set at Ue. | |||||||||
| ∆ The value 6 x P results from an empirical relationship which is found to represent most DC magnetic loads to an upper limit of P = 50 W, e.g., 6 x P= 300 W. | |||||||||
| ♦ The ON time shall be at least equal to T0.95. | |||||||||
| ♠ Where the break current differs from the make current value, the ON time refers to the make current value after which the current is reduced to the break current value for a suitable period e.g., 0.05 s. | |||||||||
Contact Rating Table from EN 60947-5-1
| Examples of Contact Rating Designation Based on Utilization Categories | ||||||||||
| NEMA Designation ⋆ |
IEC Utilization Category |
Conventional Thermal Current Ithe (A) |
Rated Operational Current Ie (A) at Rated Operational Voltage Ue |
VA Rating | ||||||
| AC | 120V | 240V | 380V | 480V | 500V | 600V | Make | Break | ||
| A150 | AC-15 | 10 | 6 | — | — | — | — | — | 7200 | 720 |
| A300 | AC-15 | 10 | 6 | 3 | — | — | — | — | 7200 | 720 |
| A600 | AC-15 | 10 | 6 | 3 | 1.9 | 1.5 | 1.4 | 1.2 | 7200 | 720 |
| B150 | AC-15 | 5 | 3 | — | — | — | — | — | 3600 | 360 |
| B300 | AC-15 | 5 | 3 | 1.5 | — | — | — | — | 3600 | 360 |
| B600 | AC-15 | 5 | 3 | 1.5 | 0.95 | 0.75 | 0.72 | 0.6 | 3600 | 360 |
| C150 | AC-15 | 2.5 | 1.5 | — | — | — | — | — | 1800 | 180 |
| C300 | AC-15 | 2.5 | 1.5 | 0.75 | — | — | — | — | 1800 | 180 |
| C600 | AC-15 | 2.5 | 1.5 | 0.75 | 0.47 | 0.375 | 0.35 | 0.3 | 1800 | 180 |
| D150 | AC-14 | 1.0 | 0.6 | — | — | — | — | — | 432 | 72 |
| D300 | AC-14 | 1.0 | 0.6 | 0.3 | — | — | — | — | 432 | 72 |
| E150 | AC-14 | 0.5 | 0.3 | — | — | — | — | — | 216 | 36 |
| DC | 125V | 250V | 440V | 500V | 600V | — | — | — | ||
| N150 | DC-13 | 10 | 2.2 | — | — | — | — | — | 275 | 275 |
| N300 | DC-13 | 10 | 2.2 | 1.1 | — | — | — | — | 275 | 275 |
| N600 | DC-13 | 10 | 2.2 | 1.1 | 0.63 | 0.55 | 0.4 | — | 275 | 275 |
| P150 | DC-13 | 5 | 1.1 | — | — | — | — | — | 138 | 138 |
| P300 | DC-13 | 5 | 1.1 | 0.55 | — | — | — | — | 138 | 138 |
| P600 | DC-13 | 5 | 1.1 | 0.55 | 0.31 | 0.27 | 0.2 | — | 138 | 138 |
| Q150 | DC-13 | 2.5 | 0.55 | — | — | — | — | — | 69 | 69 |
| Q300 | DC-13 | 2.5 | 0.55 | 0.27 | — | — | — | — | 69 | 69 |
| Q600 | DC-13 | 2.5 | 0.55 | 0.27 | 0.15 | 0.13 | 0.1 | — | 69 | 69 |
| R150 | DC-13 | 1.0 | 0.22 | — | — | — | — | — | 28 | 28 |
| R300 | DC-13 | 1.0 | 0.22 | 0.1 | — | — | — | — | 28 | 28 |
| ⋆ This letter stands for the conventional thermal current and identifies AC or DC: e.g., B = 5 A AC. The number that follows is the rated insulation voltage. | ||||||||||