Bulletin 700S-CF Safety Control Relay

Product Overview


Click to enlarge - TOC-5-4


Bulletin 700S-CF — Safety Control Relay

The Bulletin 700S-CF Safety Control Relay provides mechanically or mirror contact performance, which are required in feedback circuits for safety applications. Bifurcated contacts are ideal for low energy feedback safety dircuits where high contact reliability is required.

Features


Standards Compliance


Certifications


Product Selection

Build a Catalog Number


Type CF and CFB Safety Control Relays — 8-Pole AC Coil Voltage (Ratings for 700S-CF Only)

AC-12 AC-15 Connection Diagrams Contacts Standard Contacts (Main)
Gold-Plated Bifurcated (Front)
Cat. No.
Gold-Plated Bifurcated, All Contacts
Cat. No.‡ 
Ith [A] Ie [A] Click to enlarge - 700CF-193-1
Main
Contacts
Auxiliary
Contacts
Click to enlarge - 700CF-186-2 Click to enlarge - 700SCF-197-6
  40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V N.O. N.C.
Main
Contacts
20 20 10 10 10 6 2.5 1 1 Click to enlarge - 700SCF-197-3 Click to enlarge - 700SCF-197-4 4 4 700S-CF440ÄBC 700S-CFB440ÄC
Click to enlarge - 700SCF-197-3 Click to enlarge - 700SCF-197-8 5 3 700S-CF530ÄBC 700S-CFB530ÄC
Adder
Deck
Contacts
10 6 6 6 5 3 1.6 1 1 Click to enlarge - 700SCF-197-3 Click to enlarge - 700SCF-197-10 6 2 700S-CF620ÄBC 700S-CFB620ÄC
  
‡ Ratings for Bulletin 700S-CFB are on Specifications

Ä AC Coil Voltage Code

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700S-CF440ÄBC becomes Cat. No. 700S-CF440DBC for 120V, 60 Hz.

[V] 12 24 32 36 42 48 100 100...
110
110 120 127 200 200...
220
208 208...
240
220...
230
50 Hz R K V W X Y KP D P S KG L F
60 Hz Q J V X KP D KG H L
50/60 Hz KJ KY KP KD KG KL KL
  

[V] 230 230...
240
240 277 347 380 380...
400
400 400...
415
440 480 500 550 600
50 Hz VA T N G B M C
60 Hz A T I E N B C
50/60 Hz KF KA KN KB
  

Product Selection, Continued

Type CF and CFB Safety Control Relays — 8-Pole DC Coil Voltage (Ratings for 700S-CF Only)

AC-12 AC-15 Connection Diagrams Contacts Standard Contacts (Main)
Gold-Plated Bifurcated (Front)
Cat. No.
Gold Plated Bifurcated, All Contacts
Cat. No.⋆ 
Ith [A] Ie [A] Click to enlarge - 700CF-193-1
Main
Contacts
Auxiliary
Contacts
Click to enlarge - 700CF-186-2 Click to enlarge - 700SCF-197-6
  40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V No. of N.O. Contacts No. of N.C. Contacts
Main Contacts 20 20 10 10 10 6 2.5 1 1 Click to enlarge - 700SCF-197-3 Click to enlarge - 700SCF-197-4 4 4 700S-CF440ÄBC 700S-CFB440ÄC
Click to enlarge - 700SCF_197_7 Click to enlarge - 700SCF-197-8 5 3 700S-CF530ÄBC 700S-CFB530ÄC
Adder Deck Contacts 10 6 6 6 5 3 1.6 1 1 Click to enlarge - 700SCF_197_9 Click to enlarge - 700SCF-197-10 6 2 700S-CF620ÄBC 700S-CFB620ÄC
  
⋆ Ratings for Bulletin 700S-CFB are on Specifications

Ä DC Coil Voltage Code

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: 700S-CFB440ÄC becomes Cat. No. 700S-CFB440ZJC for 24V DC.

[V] 9 12 24 36 48 48...72 60 64 72 80 110 110...125 115 125 220 220...250 230 250
Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT
Standard with diode DJ
Electronic with diode EQ EJ EY ED EA
  

Assignment of Contacts

Safety Control Relays with Front-mount Auxiliary Contacts, 8-Pole AC or DC Coil Voltage

Click to enlarge - 700S-CF_8-Pole_Dia

Specifications

General

  Main Relay
Cat. Nos.
700-CF, 700S-CF
Front Mounted Standard Auxiliary Contacts Main Relay
Cat. No.
700-CFB, 700S-CFB
Master Relay
Cat. No.
700-CFM
Front Mounted Bifurcated Auxiliary Contacts Side-mounted Auxiliary Contacts
Contact Ratings — NEMA A600, P600 A600, Q600 A600, Q600 2 x A600, P600 A600, Q600 A600, Q600
Min. Contact Rating 17V, 10 mA 17V, 5 mA 8V, 5 mA 5V, 3 mA 17V, 10 mA
Contact Ratings — IEC AC-15 (solenoids, contactors) at rated voltage
IEC 60947-5-1
24V 10 A 6 A 3 A 15 A 3 A 6 A
48V 10 A 6 A 3 A 15 A 3 A 6 A
120V 10 A 6 A 3 A 15 A 3 A 6 A
240V 10 A 5 A 3 A 15 A 3 A 5 A
400V 6 A 3 A 2 A 7.5 A 2 A 3 A
480V/500V 2.5 A 1.6 A 1.2 A 5 A 1.2 A 1.6 A
600V 1 A 1 A 0.7 A 2 A 0.7 A 1 A
690V 1 A 1 A 0.7 A 2 A 0.7 A 1 A
AC-12 (Control of resistive loads)
IEC 60947-5-1
40 °C Ith 20 A 10 A 10 A 20 A 10 A 10 A
230 V 8 kW
400 V 14 kW
690 V 24 kW
60 °C Ith 20 A 6 A 6 A 20 A 6 A 6 A
230V 8 kW
400V 14 kW
690V 24 kW
DC-12 Switching DC Loads
L/R < 1ms, Resistive Loads
IEC 60947-5-1
24V 15 A 10 A 6 A 20 A 6 A 6 A
48V 10 A 9 A 3.2 A 20 A 3.2 A 3.2 A
110V 6 A 3.5 A 1 A 8 A 1 A 1 A
220V 1 A 0.7 A 0.5 A 1.5 A 0.5 A 0.5 A
440V 0.4 A 0.2 A 0.2 A 0.4 A 0.2 A 0.2 A
DC-13 IEC 60947-5-1, Solenoids and contactors 24V 5 A 5 A 2.5 A 5 A 2.5 A 5 A
48V 3 A 3 A 1.5 A 3 A 1.5 A 3 A
110V 1.2 A 1.2 A 0.6 A 1.2 A 0.6 A 1.2 A
220V 0.6 A 0.6 A 0.3 A 0.6 A 0.3 A 0.6 A
440V 0.3 A 0.15 A 0.15 A 0.3 A 0.15 A 0.15 A
  
⋆ Side mounted auxiliary contacts provide “mirror contact” performance with main poles only.

Click to enlarge - 700CF-193-1 Location of welded N.O. contacts State of N.C. Contacts if N.O. contact welds
Main Front aux. Side aux.
Main Open Open Open⋆ 
Mechanically Linked Contacts‡  Front aux. Open Open
  
‡ Defined in IEC 60947-5-1 annex L. Mechanically linked is a relationship between contacts of opposite types (i.e., N.O. and N.C.).

Specifications, Continued

  Cat. No. 700S-CF Aux. Contact (Front-mounted)
Mechanical Life   [Mil] 15 15
Electrical Life AC-15
(240V, 3 A)
[Mil] 1.5 1.5
Weight AC Coil [g] 390
Terminal Cross-Sections Click to enlarge - 700CF-193-3 Click to enlarge - 700CF-193-3
Terminal Type
Terminal Size per IEC 947-1 2 x A4 2 x A4
Click to enlarge - 700CF-193-2 Solid/
Stranded§ 
1 Conductor [mm2] 1.5…6 0.5…2.5
2 Conductor [mm2] 1.5…6 0.75…2.5
Max. Wire Size per UL/CSA [AWG] 16…10 18…14
Tightening Torque [lb•in] 13.3…22 8.9…13.3
Tightening Torque [N•m] 1.5…2.5 1…1.5
  
§ For 16 or more strands, end ferrule is required

DC Switching Ratings for 700S-CF Main Poles in Series
(Resistive Load at 60 °C)
  1 pole 2 poles 3 poles
24/48V 25/20 A 25 A 25 A
125V 6 A 25 A 25 A
220V 1.5 A 8 A 25 A
440V 0.4 A 1 A 3 A
  

Approximate Dimensions

Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended for manufacturing purposes.

Click to enlarge - 700SCF-200-1


AC and DC Safety Control Relays with 12V or 24V DC Electronic Coil

Cat. No. a b c c1 c2 Æd d1 d2
700S-CF 45 81 119.5 114.5 6 2 - 4.5 60 35
(1-25/32) (3-3/16) (4-3/4) (4-43/64) (1/4) (2 - 3/16) (2-23/64) (1-25/64)
  

DC Safety Control Relays with 110V or 220V DC Electronic Coil

Cat. No. a b c c1 c2 Æd d1 d2
700S-CF 45 105 119.5 114.5 6 2 - 4.5 60 35
(1-25/32) (4-1/8) (4-3/4) (4-43/64) (1/4) (2 - 3/16) (2-23/64) (1-25/64)
  

DC Safety Control Relays

Cat. No. a b c c1 c2 Æd d1 d2
700S-CF 45 81 145.5 140.5 6 2 - 4.5 60 35
(1-25/32) (3-3/16) (5-49/64) (5-37/64) (1/4) (2 - 3/16) (2-23/64) (1-25/64)
  

Accessories

Safety Control Relays with mm [in.]
Auxiliary contact block for side mounting 1- or 2-pole a + 9 (a + 23/64)
Electronic Timing Module on coil terminal side b + 24 (b + 15/16)
Interface Module on coil terminal side b + 9 (b + 23/64)
Surge Suppressor on coil terminal side b + 3 (b + 1/8)
Labeling with label sheet + 0 (+ 0)
Marking tag sheet with clear cover + 0 (+ 0)
Marking tag adapter for System Bul. 1492W + 5.5 (+ 7/32)
  

Mounting Position

Click to enlarge - 100C_104C-123-2


Safety Relay Circuit With 5 Safety Outputs


  • Use (3) 700S-CF relays and this diagram to construct the circuit


  • Basic Circuit
    (1) Output Circuit (3 Relays, 9 Terminal Blocks)


    Click to enlarge - 700SCF-201-1


    ⋆ Numbers shown are the line numbers where the contacts for this relay appear.


    Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.