Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > Industrial Relays and Timers > IEC Industrial Relays > Bulletin 700S-CF Safety Control Relay

Bulletin 700S-CF Safety Control Relay

Introduction Standards Compliance and Certifications Product Selection Assignment of Contacts Specifications Approximate Dimensions
General

  Main Relay
Cat. Nos.
700-CF, 700S-CF
Front Mounted Standard Auxiliary Contacts Main Relay
Cat. No.
700-CFB, 700S-CFB
Master Relay
Cat. No.
700-CFM
Front Mounted Bifurcated Auxiliary Contacts Side-mounted Auxiliary Contacts
Contact Ratings — NEMA A600, P600 A600, Q600 A600, Q600 2 x A600, P600 A600, Q600 A600, Q600
Min. Contact Rating 17V, 10 mA 17V, 5 mA 8V, 5 mA 5V, 3 mA 17V, 10 mA
Contact Ratings — IEC AC-15 (solenoids, contactors) at rated voltage
IEC 60947-5-1
24V 10 A 6 A 3 A 15 A 3 A 6 A
48V 10 A 6 A 3 A 15 A 3 A 6 A
120V 10 A 6 A 3 A 15 A 3 A 6 A
240V 10 A 5 A 3 A 15 A 3 A 5 A
400V 6 A 3 A 2 A 7.5 A 2 A 3 A
480V/500V 2.5 A 1.6 A 1.2 A 5 A 1.2 A 1.6 A
600V 1 A 1 A 0.7 A 2 A 0.7 A 1 A
690V 1 A 1 A 0.7 A 2 A 0.7 A 1 A
AC-12 (Control of resistive loads)
IEC 60947-5-1
40 °C Ith 20 A 10 A 10 A 20 A 10 A 10 A
230 V 8 kW
400 V 14 kW
690 V 24 kW
60 °C Ith 20 A 6 A 6 A 20 A 6 A 6 A
230V 8 kW
400V 14 kW
690V 24 kW
DC-12 Switching DC Loads
L/R < 1ms, Resistive Loads
IEC 60947-5-1
24V 15 A 10 A 6 A 20 A 6 A 6 A
48V 10 A 9 A 3.2 A 20 A 3.2 A 3.2 A
110V 6 A 3.5 A 1 A 8 A 1 A 1 A
220V 1 A 0.7 A 0.5 A 1.5 A 0.5 A 0.5 A
440V 0.4 A 0.2 A 0.2 A 0.4 A 0.2 A 0.2 A
DC-13 IEC 60947-5-1, Solenoids and contactors 24V 5 A 5 A 2.5 A 5 A 2.5 A 5 A
48V 3 A 3 A 1.5 A 3 A 1.5 A 3 A
110V 1.2 A 1.2 A 0.6 A 1.2 A 0.6 A 1.2 A
220V 0.6 A 0.6 A 0.3 A 0.6 A 0.3 A 0.6 A
440V 0.3 A 0.15 A 0.15 A 0.3 A 0.15 A 0.15 A
  
⋆ Side mounted auxiliary contacts provide “mirror contact” performance with main poles only.

Click to enlarge - 700CF-193-1 Location of welded N.O. contacts State of N.C. Contacts if N.O. contact welds
Main Front aux. Side aux.
Main Open Open Open⋆ 
Mechanically Linked Contacts‡  Front aux. Open Open
  
‡ Defined in IEC 60947-5-1 annex L. Mechanically linked is a relationship between contacts of opposite types (i.e., N.O. and N.C.).

Specifications, Continued

  Cat. No. 700S-CF Aux. Contact (Front-mounted)
Mechanical Life   [Mil] 15 15
Electrical Life AC-15
(240V, 3 A)
[Mil] 1.5 1.5
Weight AC Coil [g] 390
Terminal Cross-Sections Click to enlarge - 700CF-193-3 Click to enlarge - 700CF-193-3
Terminal Type
Terminal Size per IEC 947-1 2 x A4 2 x A4
Click to enlarge - 700CF-193-2 Solid/
Stranded§ 
1 Conductor [mm2] 1.5…6 0.5…2.5
2 Conductor [mm2] 1.5…6 0.75…2.5
Max. Wire Size per UL/CSA [AWG] 16…10 18…14
Tightening Torque [lb•in] 13.3…22 8.9…13.3
Tightening Torque [N•m] 1.5…2.5 1…1.5
  
§ For 16 or more strands, end ferrule is required

DC Switching Ratings for 700S-CF Main Poles in Series
(Resistive Load at 60 °C)
  1 pole 2 poles 3 poles
24/48V 15/10 A 25 A 25 A
125V 6 A 25 A 25 A
220V 1.5 A 8 A 25 A
440V 0.4 A 1 A 3 A