Bulletin 700-K Control Relays
|
Bulletin 700-K Miniature Control Relays
- IEC compact industrial relay
- IP2X Finger Protection
- Bifurcated contacts for low-level signals
- Optional integrated coil protection diode
Standards Compliance
UL 508
CSA C22.2 No. 14
EN/IEC 60947-1, -5-1
Certifications
cULus Listed (File No. E33916, Guide NKCR/NKCR7)
CE Marked
Approvals
CE marked
cULus listed (File No. E33916, Guide No. NKCR and NKCR7)
4-Pole AC or DC Coil Voltage
Ä Coil Voltage Codes
The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: 230V, 50/60 Hz: Cat. No. 700-K40E-Ä becomes Cat. No. 700-K40E-KF. For other voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
| [V] | 12 | 24 | 110 | 120 | 125 | 220 | 230 | 240 | 250 | 400 | 440 | 480 | 525 | 600 | ||
| AC, 50 Hz | — | — | D | — | — | — | — | — | — | — | B | — | VC | — | ||
| AC, 60 Hz | — | — | — | D | — | — | — | — | — | — | — | B | — | VC | ||
| AC, 50/60 Hz | — | KJ | — | — | — | — | KF | KA | — | KN | — | — | — | — | ||
| Standard | DC | ZQ | ZJ | ZD | — | ZS | ZA | — | — | ZT | — | — | — | — | — | |
| Standard Diode | — | DJ | — | — | — | — | — | — | — | — | — | — | — | — | ||
Assignment of Contacts
Device Combinations in Accordance with IEC 60947-1 / -4-1
Table valid for : AC / DC = 0.85…1.1 x Us, Tamb. = -25 °C…+60 °C, normal position (horizontal rail mounting) ¬
Auxiliary Contact Blocks
Control Modules
Marking Systems
| Description | Pkg. Qty. | Cat. No. | |
|
|
Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm |
10 | 100-FMS |
|
Snap-In Marker Card | 5 | 1492-M6X12 |
IEC Specifications
| 700-K | |||
| AC-12 Rated Thermal Current Ambient temperature 40°C |
|||
| Ith | 24…240V | [A] | 10 |
| 230…500V | [A] | 10 | |
| 230…690V | [A] | 10 | |
| Ambient temperature 60°C | |||
| Ith | 24…240V | [A] | 6 |
| 230…500V | [A] | 6 | |
| 230…690V | [A] | 6 | |
| AC-15/B600 Switching of Solenoids and contactors |
|||
| 24V | [A] | 3 | |
| 48V | [A] | 3 | |
| 120V | [A] | 3 | |
| 230V | [A] | 2 | |
| 240V | [A] | 2 | |
| 400V | [A] | 1.2 | |
| 480V | [A] | 1 | |
| 500V | [A] | 1 | |
| 600V | [A] | 0.6 | |
| 690V | [A] | 0.6 | |
| Short-circuit Protection "gG" Fuse acc. to IEC 60947-5-1, no welding of contacts |
|||
| Fuse gG | [A] | 10 | |
| Min. Switching Capacity 15V For bifurcated contacts (control relays and auxiliary contact blocks) |
|||
| [mA] | 2 | ||
| Resistance and Power Dissipation | |||
| Main current circuit resistance, 1 pole | [mW] | 6.5 | |
| Power dissipation Ith, 4 poles | [W] | 2.6 | |
| Total power dissipation | |||
| Ith | AC control, warm | [W] | 4.4 |
| DC control, warm | [W] | 5.2 | |
| Lifespan | |||
| Mechanical | [Mio. op.] | 15 | |
| Electrical AC-15 (240V / 2 A) | [Mio. op.] | 0.7 | |
| Weight | |||
| AC control | kg (lbs.) | 0.16 (0.35) | |
| DC control | kg (lbs.) | 0.2 (0.44) | |
| Load Carrying Capacity per UL/CSA | |||
| Rated voltage | AC | [V] | max. 600 |
| Continuous rating | 40 °C | [A] | 10 |
| Switching capacity | AC | [A] | B 600 |
| Rated voltage | DC | [V] | max. 600 |
| Switching capacity | DC | [A] | Q 600 |
| 700-K | |||
| Continuous Current | |||
| (General Purpose) | 300V AC | [A] | 5 |
| 600V AC | [A] | 10 | |
| DC-13/Q600 | |||
| 1 pole | 24V | [A] | 2.3 |
| 48V | [A] | 1 | |
| 110V | [A] | 0.55 | |
| 125V | [A] | 0.55 | |
| 220V | [A] | 0.27 | |
| 250V | [A] | 0.27 | |
| 400V | [A] | 0.15 | |
| 440V | [A] | 0.15 | |
| 600V | [A] | 0.1 | |
Cross Sections
Coil Data
| 700-K | |||
| Operating Limits | |||
| AC control 50 Hz, 60 Hz, 50/60 Hz |
pick-up | [x Us] | 0.85…1.1 |
| dropout | [x Us] | 0.2…0.75 | |
| DC control | pick-up | [x Us] | 0.8…1.1 9, 12, 24, 110V DC: 0.7…1.25 |
| dropout | [x Us] | 0.1…0.75 | |
| Coil Consumption | |||
| AC control 50 Hz, 60 Hz, 50/60 Hz |
pick-up | [VA/W] | 35/32 |
| hold-in | [VA/W] | 5/1.8 | |
| DC control | pick-up | [W] | cold 3.0, warm 2.6 |
| hold-in | [W] | cold 3.0, warm 2.6 | |
| Operating Times | |||
| AC | closing delay | [ms] | 15…40 |
| opening delay | [ms] | 15…33 | |
| With RC module | opening delay | [ms] | 15…28 |
| DC | closing delay | [ms] | 18…40 |
| opening delay | [ms] | 6…12 | |
| With integrated diode | opening delay | [ms] | 8…12 |
| With external diode | opening delay | [ms] | 35…50 |
General Data
| 700-K | ||
| Rated Isolation Voltage Ui | ||
| IEC | [V] | 690 |
| UL, CSA | [V] | 600 |
| 1 minute acc. to IEC 60947-5-1 | [V] | — |
| Rated Impulse Voltage Withstand Uimp | [kV] | 6 |
| Rated Operating Voltage Ue | ||
| AC 50/60 Hz | [V] | 24, 48, 120, 230, 400, 500, 600, 690 |
| DC | [V] | 24, 48, 110, 220, 440 |
| Rated Coil Frequency | AC 50/60 Hz, DC | |
| Ambient Temperature | ||
| Storage | [°C] | -55…+80 |
| Operation at rated voltage | [°C] | -25…+60 |
| at 70°C | 15% current reduction against 60°C values | |
| Climatic Withstand | — | |
| Max. Altitude of Installation Site | [m] | 2000 NN |
| Protection Class | IP2X | |
| Auxiliary contact | — | |
| Standards | IEC/EN 60947-1, -5-1, -5-4, UL 508, CSA 22.2. No. 14 |
|
| Approvals | CE, cULus | |