Bulletin 700-K Control Relays

Click to enlarge - 700-K22Z_4c


Bulletin 700-K Miniature Control Relays


Standards Compliance

UL 508
CSA C22.2 No. 14
EN/IEC 60947-1, -5-1


Certifications

cULus Listed (File No. E33916, Guide NKCR/NKCR7)
CE Marked


Approvals

CE marked
cULus listed (File No. E33916, Guide No. NKCR and NKCR7)


4-Pole AC or DC Coil Voltage

AC-12 AC-15 (B600) Connection
Diagrams
Contacts Pkg. Qty. ¬   
Ie [A] Ie [A] Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V N.O. N.C. Cat. No.
10 6 3 3 2 1.2 1 0.6 0.6 Click to enlarge - 700-K40E_Dia 4 0 1 700-K40E-Ä
Click to enlarge - 700-K31Z_Dia 3 1 1 700-K31Z-Ä
Click to enlarge - 700-K22Z_Dia 2 2 1 700-K22Z-Ä
Click to enlarge - 700-KL22Z_Dia 1+1LT  1+1LT  1 700-KL22Z-Ä
  
¬ May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 700-K40E-ZJM.
T 1L = Late break N.C./early make N.O.

Ä Coil Voltage Codes

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: 230V, 50/60 Hz: Cat. No. 700-K40E-Ä becomes Cat. No. 700-K40E-KF. For other voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

  [V] 12 24 110 120 125 220 230 240 250 400 440 480 525 600
AC, 50 Hz D B VC
AC, 60 Hz D B VC
AC, 50/60 Hz KJ KF KA KN
Standard DC ZQ ZJ ZD ZS ZA ZT
Standard Diode DJ
  

Assignment of Contacts

Device Combinations in Accordance with IEC 60947-1 / -4-1

Table valid for : AC / DC = 0.85…1.1 x Us, Tamb. = -25 °C…+60 °C, normal position (horizontal rail mounting) ¬ 

Auxiliary Contact Blocks Control Relays 700-K (AC and DC Control)
  Circuit Diagram Control 700-K22Z-Ä 700-K31Z-Ä 700-K40E-Ä 700-KL22Z-Ä
Click to enlarge - 700-K22Z_Dia Click to enlarge - 700-K31Z_Dia Click to enlarge - 700-K40E_Dia Click to enlarge - 700-KL22Z_Dia
Front Mounting  
100-KFA02E Click to enlarge - 100-KFA02E_Dia AC/DC 31Z + 02E = 33Y T  40E + 02E = 42Y
100-KFA11E Click to enlarge - 100-KFA11E_Dia AC/DC 22Z + 11E = 33Y 31Z + 11E = 42Y 40E + 11E = 51Y L22Z + 11E = L33Y
100-KFA20E Click to enlarge - 100-KFA20E_Dia AC/DC 22Z + 20E = 42Y 31Z + 20E = 51Y 40E + 20E = 60Y L22Z + 20E = L42Y
100-KFA04E Click to enlarge - 100-KFA04E_Dia AC/DC 40E + 04E = 44Y T 
100-KFA13E Click to enlarge - 100-KFA13E_Dia AC/DC 31Z + 13E = 44Y T  40E + 13E = 53Y
100-KFA22Z Click to enlarge - 100-KFA22Z_Dia AC/DC 31Z + 22Z = 53Y T  40E + 22Z = 62Y
100-KFA31Z Click to enlarge - 100-KFA31Z_Dia AC/DC 40E + 31Z = 71Y ‡ 
100-KFA40E Click to enlarge - 100-KFA40E_Dia AC/DC 22Z + 40E = 62Y 31Z + 40E = 71Y 40E + 40E = 80Y L22Z + 40E = L62Y
  
¬ For other operating limits, please contact our technical consultant.
T Tamb. max. +40 °C
‡ Tamb. max. +40 °C and only allowed for coil voltage 24V DC or 230V AC

Auxiliary Contact Blocks

  Description Connection Diagrams Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a For Use With Pkg. Qty. ¬   
N.O. N.C. Cat. No.
Click to enlarge - 100-KF_2p_4c Front-mounted auxiliary contacts
Auxiliary Contact Blocks
2- and 4-pole versions
Choice of contact configurations
Snap on, no tools required
Electronic-compatible bifurcated contacts for signals down to 15V/2 mA
Click to enlarge - 100-KFA02E_Dia 0 2 100/104-K, 700-K 1 100-KFA02E
Click to enlarge - 100-KFA11E_Dia 1 1 100/104-K, 700-K 1 100-KFA11E
Click to enlarge - 100-KFA20E_Dia 2 0 100/104-K, 700-K 1 100-KFA20E
Click to enlarge - 100-KF_4p_4c Click to enlarge - 100-KFA04E_Dia 0 4 100/104-K, 700-K 1 100-KFA04E
Click to enlarge - 100-KFA13E_Dia 1 3 100/104-K, 700-K 1 100-KFA13E
Click to enlarge - 100-KFA22Z_Dia 2 2 100/104-K, 700-K 1 100-KFA22Z
Click to enlarge - 100-KFA31Z_Dia 3 1 100/104-K, 700-K 1 100-KFA31Z
Click to enlarge - 100-KFA40E_Dia 4 0 100/104-K, 700-K 1 100-KFA40E
  
¬ May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFA02EM.

Control Modules

  Description Connection
Diagrams
For Use With Pkg. Qty. Cat. No.
Click to enlarge - 100-KMCH_4c Mechanical Interlock
For interlocking of two adjacent contactors
No added width to contactor assembly
Front mount Plug-In type
Optional auxiliary contact blocks and suppressor modules mount onto the interlock
Click to enlarge - 100-KMHC_Dia 100-K, 700-K (AC & DC Control) 1 100-KMCH
Click to enlarge - 100-KFS_4c Surge Suppressor
Plug-in Type
Limits surge voltage on coil drop-off
RC Suppressor 24…48V AC Click to enlarge - 100-KFSC_Dia 100/104-K, 700-K 1 ¬  100-KFSC50
110…280V AC 1 ¬  100-KFSC280
380…480V AC 1 ¬  100-KFSC480
MOV Suppressor 12…55V AC, 12…77V DC Click to enlarge - 100-KFSV_Dia 100/104-K, 700-K 1 ¬  100-KFSV55
56…136V AC, 78…180V DC 1 ¬  100-KFSV136
137…277V AC, 181…250V DC 1 ¬  100-KFSV277
Diode Suppressor 12…250V DC Click to enlarge - 100-KFSD_Dia 100/104-K, 700-K 1 ¬  100-KFSD250
  
¬ May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.

Marking Systems

  Description Pkg. Qty. Cat. No.
Click to enlarge - 700CF-192-3 Label Sheet
105 self-adhesive paper labels each, 6 x 17 mm
10 100-FMS
Click to enlarge - 1492-M7X12a_bw Snap-In Marker Card 5 1492-M6X12
  

IEC Specifications

  700-K
AC-12 Rated Thermal Current
Ambient temperature 40°C
    Ith 24…240V [A] 10
  230…500V [A] 10
  230…690V [A] 10
Ambient temperature 60°C
        Ith 24…240V [A] 6
  230…500V [A] 6
  230…690V [A] 6
AC-15/B600
Switching of Solenoids and contactors
  24V [A] 3
  48V [A] 3
  120V [A] 3
  230V [A] 2
  240V [A] 2
  400V [A] 1.2
  480V [A] 1
  500V [A] 1
  600V [A] 0.6
  690V [A] 0.6
Short-circuit Protection
"gG" Fuse acc. to IEC 60947-5-1, no welding of contacts
  Fuse gG [A] 10
Min. Switching Capacity 15V
For bifurcated contacts (control relays and auxiliary contact blocks)
  [mA] 2
Resistance and Power Dissipation
Main current circuit resistance, 1 pole [mW] 6.5
Power dissipation Ith, 4 poles [W] 2.6
Total power dissipation
Ith AC control, warm [W] 4.4
  DC control, warm [W] 5.2
Lifespan
Mechanical [Mio. op.] 15
Electrical AC-15 (240V / 2 A) [Mio. op.] 0.7
Weight
  AC control kg (lbs.) 0.16 (0.35)
  DC control kg (lbs.) 0.2 (0.44)
Load Carrying Capacity per UL/CSA
Rated voltage AC [V] max. 600
Continuous rating 40 °C [A] 10
Switching capacity AC [A] B 600
Rated voltage DC [V] max. 600
Switching capacity DC [A] Q 600
  

  700-K
Continuous Current
(General Purpose) 300V AC [A] 5
  600V AC [A] 10
DC-13/Q600
1 pole 24V [A] 2.3
  48V [A] 1
  110V [A] 0.55
  125V [A] 0.55
  220V [A] 0.27
  250V [A] 0.27
  400V [A] 0.15
  440V [A] 0.15
  600V [A] 0.1
  

Cross Sections

Conductor Cross Sections
- Main Contacts and Auxiliary Contacts
700-K
Terminal type ¬ 
Click to enlarge - 140M-29-1
Click to enlarge - 140M-29-4 Fine stranded with ferrule (1) Conductor
(2) Conductors
[mm2]
[mm2]
0.75…2.5
0.75…2.5
Click to enlarge - 140M-29-6 Solid or coarse stranded (1) Conductor
(2) Conductors
[mm2]
[mm2]
1…4
1…2.5 + 1…4
Click to enlarge - 140M-29-5
Recommended torque [Nm] 1.2
Cross section per UL/CSA [AWG] 18…12 T 
Recommended torque [lb-in] 10.6
  
¬ Pozidriv No. 2 / Blade No. 3 screw
T Use same cross sections

Coil Data

  700-K
Operating Limits
AC control
50 Hz, 60 Hz, 50/60 Hz
pick-up [x Us] 0.85…1.1
dropout [x Us] 0.2…0.75
DC control pick-up [x Us] 0.8…1.1
9, 12, 24, 110V DC: 0.7…1.25
dropout [x Us] 0.1…0.75
Coil Consumption
AC control
50 Hz, 60 Hz, 50/60 Hz
pick-up [VA/W] 35/32
hold-in [VA/W] 5/1.8
DC control pick-up [W] cold 3.0, warm 2.6
hold-in [W] cold 3.0, warm 2.6
Operating Times
AC closing delay [ms] 15…40
opening delay [ms] 15…33
With RC module opening delay [ms] 15…28
DC closing delay [ms] 18…40
opening delay [ms] 6…12
With integrated diode opening delay [ms] 8…12
With external diode opening delay [ms] 35…50
  

General Data

  700-K
Rated Isolation Voltage Ui  
IEC [V] 690
UL, CSA [V] 600
1 minute acc. to IEC 60947-5-1 [V]
Rated Impulse Voltage Withstand Uimp [kV] 6
Rated Operating Voltage Ue    
AC 50/60 Hz [V] 24, 48, 120, 230, 400, 500, 600, 690
DC [V] 24, 48, 110, 220, 440
Rated Coil Frequency   AC 50/60 Hz, DC
Ambient Temperature    
Storage [°C] -55…+80
Operation at rated voltage [°C] -25…+60
at 70°C   15% current reduction against 60°C values
Climatic Withstand  
Max. Altitude of Installation Site [m] 2000 NN
Protection Class   IP2X
Auxiliary contact  
Standards   IEC/EN 60947-1, -5-1, -5-4,
UL 508, CSA 22.2. No. 14
Approvals   CE, cULus