Bulletin 700-K Control Relays

Product Overview


Click to enlarge - 700-K22Z_4c


Bulletin 700-K — Miniature Control Relays


Standards Compliance

UL 508
CSA C22.2 No. 14
EN/IEC 60947-1, -5-1
Meets the material restrictions for European Directive 2002/95/EC - EU-RoHS


Certifications

cULus Listed (File No. E33916, Guide NKCR/NKCR7)
CE Marked
CCC


4-Pole AC or DC Coil Voltage

AC-12 AC-15 (B600) Connection
Diagrams
Contacts Pkg. Qty. ⋆   
Ith [A] Ie [A] Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a
40 °C 60 °C 24/48V 120V 240V 400V 500V 600V 690V N.O. N.C. Cat. No.
10 6 3 3 2 1 1 0.6 0.6 Click to enlarge - 700-K40E_Dia 4 0 1 700-K40E-Ä
Click to enlarge - 700-K31Z_Dia 3 1 1 700-K31Z-Ä
Click to enlarge - 700-K22Z_Dia 2 2 1 700-K22Z-Ä
Click to enlarge - 700-KL22Z_Dia 1+1L‡  1+1L‡  1 700-KL22Z-Ä
  
⋆ May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 700-K40E-ZJM.
‡  1L = Late Break N.C. / Early Make N.O.

Ä Coil Voltage Codes

The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: 230V, 50/60 Hz: Cat. No. 700-K40E-Ä becomes Cat. No. 700-K40E-KF. For other voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.

For Screw Type Terminal Versions
  [V] 12 24 110 120 125 220 230 240 250 400 440 480 525 600
AC, 50 Hz D B VC
AC, 60 Hz D B VC
AC, 50/60 Hz KJ KF KA KN
Standard DC ZQ ZJ ZD ZS ZA ZT
Standard diode DJ
  
For Spring Clamp Type Terminal Versions
AC, 50 Hz D
AC, 60 Hz D
AC, 50/60 Hz KJ KF
Standard DC ZJ ZD
Standard diode DJ
  

Assignment of Contacts

Device Combinations in Accordance with IEC 60947-1 / -4-1

Table valid for : AC / DC = 0.85…1.1 x Us, Tamb. = -25 °C…+60 °C, normal position (horizontal rail mounting). Also valid for Bulletin 700-KR relays and Bulletin 100-KR auxiliary contacts. ⋆ 

Auxiliary Contact Blocks Control Relays 700-K (AC and DC Control)
  Circuit Diagram Control 700-K22Z-Ä 700-K31Z-Ä 700-K40E-Ä 700-KL22Z-Ä
Click to enlarge - 700-K22Z_Dia Click to enlarge - 700-K31Z_Dia Click to enlarge - 700-K40E_Dia Click to enlarge - 700-KL22Z_Dia
Front Mounting  
100-KFA02E Click to enlarge - 100-KFA02E_Dia AC/DC 31Z + 02E = 33Y ‡  40E + 02E = 42Y
100-KFA11E Click to enlarge - 100-KFA11E_Dia AC/DC 22Z + 11E = 33Y 31Z + 11E = 42Y 40E + 11E = 51Y L22Z + 11E = L33Y
100-KFA20E Click to enlarge - 100-KFA20E_Dia AC/DC 22Z + 20E = 42Y 31Z + 20E = 51Y 40E + 20E = 60Y L22Z + 20E = L42Y
100-KFA04E Click to enlarge - 100-KFA04E_Dia AC/DC 40E + 04E = 44Y ‡ 
100-KFA13E Click to enlarge - 100-KFA13E_Dia AC/DC 31Z + 13E = 44Y ‡  40E + 13E = 53Y
100-KFA22Z Click to enlarge - 100-KFA22Z_Dia AC/DC 31Z + 22Z = 53Y ‡  40E + 22Z = 62Y
100-KFA31Z Click to enlarge - 100-KFA31Z_Dia AC/DC 40E + 31Z = 71Y § 
100-KFA40E Click to enlarge - 100-KFA40E_Dia AC/DC 22Z + 40E = 62Y 31Z + 40E = 71Y 40E + 40E = 80Y L22Z + 40E = L62Y
  
⋆ For other operating limits, please contact our technical consultant.
‡ Tamb. max. +40 °C
§ Tamb. max. +40 °C and only allowed for coil voltage 24V DC or 230V AC

Auxiliary Contact Blocks

  Description Connection Diagrams Click to enlarge - 100M-66-3a Click to enlarge - 100M-66-4a For Use With Pkg. Qty. ⋆   
N.O. N.C. Cat. No.
Click to enlarge - 100-KF_2p_4c Front-mounted auxiliary contacts
  • Auxiliary Contact Blocks

  • 2- and 4-pole versions

  • Choice of contact configurations

  • Snap on, no tools required

  • Electronic-compatible bifurcated contacts for signals down to 15V/2 mA
  • Click to enlarge - 100-KFA02E_Dia 0 2 100/104-K, 700-K 1 100-KFA02E
    Click to enlarge - 100-KFA11E_Dia 1 1 100/104-K, 700-K 1 100-KFA11E
    Click to enlarge - 100-KFA20E_Dia 2 0 100/104-K, 700-K 1 100-KFA20E
    Click to enlarge - 100-KF_4p_4c Click to enlarge - 100-KFA04E_Dia 0 4 100/104-K, 700-K 1 100-KFA04E
    Click to enlarge - 100-KFA13E_Dia 1 3 100/104-K, 700-K 1 100-KFA13E
    Click to enlarge - 100-KFA22Z_Dia 2 2 100/104-K, 700-K 1 100-KFA22Z
    Click to enlarge - 100-KFA31Z_Dia 3 1 100/104-K, 700-K 1 100-KFA31Z
    Click to enlarge - 100-KFA40E_Dia 4 0 100/104-K, 700-K 1 100-KFA40E
      
    ⋆ May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFA02EM.

    Control Modules

      Description Connection
    Diagrams
    For Use With Pkg. Qty. Cat. No.
    Click to enlarge - 100-KMCH_4c Mechanical Interlock
  • For interlocking of two adjacent contactors

  • No added width to contactor assembly

  • Front mount plug-in type

  • Optional auxiliary contact blocks and suppressor modules mount onto the interlock
  • Click to enlarge - 100-KMHC_Dia 100/104-K/-KR, 700-K/-KR 1 100-KMCH
    Click to enlarge - 100-KFS_4c Surge Suppressor
  • Plug-in type

  • Limits surge voltage on coil drop-off
  • RC Suppressor 24…48V AC Click to enlarge - 100-KFSC_Dia 100/104-K/-KR, 700-K/-KR 1 ⋆  100-KFSC50
    110…280V AC 1 ⋆  100-KFSC280
    380…480V AC 1 ⋆  100-KFSC480
    MOV Suppressor 12…55V AC, 12…77V DC Click to enlarge - 100-KFSV_Dia 100/104-K/-KR, 700-K/-KR 1 ⋆  100-KFSV55
    56…136V AC, 78…180V DC 1 ⋆  100-KFSV136
    137…277V AC, 181…250V DC 1 ⋆  100-KFSV277
    Diode Suppressor 12…250V DC Click to enlarge - 100-KFSD_Dia 100/104-K/-KR, 700-K/-KR 1 ⋆  100-KFSD250
      
    ⋆ May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.

    Marking Systems

      Description Pkg. Qty. Cat. No.
    Click to enlarge - 700CF-192-3 Label Sheet
    105 self-adhesive paper labels each, 6 x 17 mm
    10 100-FMS
    Click to enlarge - 1492-M7X12a_bw Snap-In Marker Card 5 1492-M6X12
      

      700-K 700-KR
    AC-12 Rated Thermal Current
    Ambient temperature 40°C
    Ith 24…240V [A] 10
      230…500V [A] 10
      230…690V [A] 10
    Ambient temperature 60°C
    Ith 24…240V [A] 6
      230…500V [A] 6
      230…690V [A] 6
    AC-15/B600
    Switching of Solenoids and contactors
    Ie 24V [A] 3
      48V [A] 3
      120V [A] 3
      230V [A] 2
      240V [A] 2
      400V [A] 1.2
      480V [A] 1
      500V [A] 1
      600V [A] 0.6
      690V [A] 0.6
    Short-circuit Protection
    "gG" Fuse acc. to IEC 60947-5-1, no welding of contacts
      Fuse gG [A] 10
    Min. Switching Capacity 15V
    For bifurcated contacts (control relays and auxiliary contact blocks)
      [mA] 2
    Resistance and Power Dissipation
    Main current circuit resistance, 1 pole [mW] 6.5
    Power dissipation, 4 poles [W] 2.6
    Total power dissipation
      AC control, warm [W] 4.4
      DC control, warm [W] 5.2
    Lifespan
    Mechanical [Mio. op.] 15
    Electrical AC-15 (240V / 2 A) [Mio. op.] 0.7
    Weight
      AC control kg (lbs.) 0.16 (0.35)
      DC control kg (lbs.) 0.2 (0.44)
    Load Carrying Capacity per UL/CSA
    Rated voltage AC [V] max. 600
    Continuous rating 40 °C [A] 10 6
    Switching capacity AC [A] B 600
    Rated voltage DC [V] max. 600
    Switching capacity DC [A] Q 600
      

      700-K
    DC-13/Q600
    1 pole 24V [A] 2.3
      48V [A] 1
      110V [A] 0.55
      125V [A] 0.55
      220V [A] 0.27
      250V [A] 0.27
      400V [A] 0.15
      440V [A] 0.15
      600V [A] 0.1
      

    Cross Sections

    Conductor Cross Sections
    - Main Contacts, Auxiliary Contacts, and Coil Terminals
    700-K 700-KR
    Terminal type ⋆   
    Click to enlarge - 140M-29-1 Click to enlarge - 100-K_Push-In
    Click to enlarge - 140M-29-4 Fine stranded with ferrule (1) Conductor
    (2) Conductors
    [mm2]
    [mm2]
    0.75…2.5
    0.75…2.5
    0.50…2.5
    0.50…2.5
    Click to enlarge - 140M-29-6 Solid or coarse stranded (1) Conductor
    (2) Conductors
    [mm2]
    [mm2]
    1…4
    1…2.5 + 1…4
    0.75…2.5 ♣ 
    0.75…2.5 ♣ 
    Click to enlarge - 140M-29-5
    Recommended torque [Nm] 1.2
    Cross section per UL/CSA [AWG] 18…12 ‡  18…14 ♣ 
    Recommended torque [lb-in] 10.6
      
    ⋆ Pozidriv No. 2 / Blade No. 3 screw
    ‡ Use same cross sections
    ♣  Stranded wire only

    Coil Data

      700-K
    Operating Limits
    AC control
    50 Hz, 60 Hz, 50/60 Hz
    pick-up [x Us] 0.85…1.1
    dropout [x Us] 0.2…0.75
    DC control pick-up [x Us] 0.8…1.1
    9, 12, 24, 110V DC: 0.7…1.25
    dropout [x Us] 0.1…0.75
    Coil Consumption
    AC control
    50 Hz, 60 Hz, 50/60 Hz
    pick-up [VA/W] 35/32
    hold-in [VA/W] 5/1.8
    DC control pick-up [W] cold 3.0, warm 2.6
    hold-in [W] cold 3.0, warm 2.6
    Operating Times
    AC closing delay [ms] 15…40
    opening delay [ms] 15…33
    With RC module opening delay [ms] 15…28
    DC closing delay [ms] 18…40
    opening delay [ms] 6…12
    With integrated diode opening delay [ms] 8…12
    With external diode opening delay [ms] 35…50
      

    General Data

      700-K
    Rated Isolation Voltage Ui  
    IEC [V] 690
    UL, CSA [V] 600
    1 minute acc. to IEC 60947-5-1 [V]
    Rated Impulse Voltage Withstand Uimp [kV] 6
    Rated Operating Voltage Ue    
    AC 50/60 Hz [V] 24, 48, 120, 230, 400, 500, 600, 690
    DC [V] 24, 48, 110, 220, 440
    Rated Coil Frequency   AC 50/60 Hz, DC
    Ambient Temperature    
    Storage [°C] -55…+80
    Operation at rated voltage [°C] -25…+60
    at 70°C   15% current reduction against 60°C values
    Climatic Withstand  
    Max. Altitude of Installation Site [m] 2000 NN
    Protection Class   IP2X
    Auxiliary contact  
    Standards   IEC/EN 60947-1, -5-1, -5-4,
    UL 508, CSA 22.2. No. 14
    Approvals   CE, cULus
      

    Approximate Dimensions are shown in millimeters. Approximate Dimensions are not intended for manufacturing purposes.

    Click to enlarge - 700-K_Dims