Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > Industrial Relays and Timers > IEC Industrial Relays > Bulletin 700-K Control Relays
Bulletin 700-K Control Relays
| Introduction | Standards Compliance | Product Selection | Assignment of Contacts | Accessories | IEC Specifications | Approximate Dimensions |
| 700-K | 700-KR | |||
| AC-12 Rated Thermal Current Ambient temperature 40°C |
||||
| Ith | 24…240V | [A] | 10 | |
| 230…500V | [A] | 10 | ||
| 230…690V | [A] | 10 | ||
| Ambient temperature 60°C | ||||
| Ith | 24…240V | [A] | 6 | |
| 230…500V | [A] | 6 | ||
| 230…690V | [A] | 6 | ||
| AC-15/B600 Switching of Solenoids and contactors |
||||
| Ie | 24V | [A] | 3 | |
| 48V | [A] | 3 | ||
| 120V | [A] | 3 | ||
| 230V | [A] | 2 | ||
| 240V | [A] | 2 | ||
| 400V | [A] | 1.2 | ||
| 480V | [A] | 1 | ||
| 500V | [A] | 1 | ||
| 600V | [A] | 0.6 | ||
| 690V | [A] | 0.6 | ||
| Short-circuit Protection "gG" Fuse acc. to IEC 60947-5-1, no welding of contacts |
||||
| Fuse gG | [A] | 10 | ||
| Min. Switching Capacity 15V For bifurcated contacts (control relays and auxiliary contact blocks) |
||||
| [mA] | 2 | |||
| Resistance and Power Dissipation | ||||
| Main current circuit resistance, 1 pole | [mW] | 6.5 | ||
| Power dissipation, 4 poles | [W] | 2.6 | ||
| Total power dissipation | ||||
| AC control, warm | [W] | 4.4 | ||
| DC control, warm | [W] | 5.2 | ||
| Lifespan | ||||
| Mechanical | [Mio. op.] | 15 | ||
| Electrical AC-15 (240V / 2 A) | [Mio. op.] | 0.7 | ||
| Weight | ||||
| AC control | kg (lbs.) | 0.16 (0.35) | ||
| DC control | kg (lbs.) | 0.2 (0.44) | ||
| Load Carrying Capacity per UL/CSA | ||||
| Rated voltage | AC | [V] | max. 600 | |
| Continuous rating | 40 °C | [A] | 10 | 6 |
| Switching capacity | AC | [A] | B 600 | |
| Rated voltage | DC | [V] | max. 600 | |
| Switching capacity | DC | [A] | Q 600 | |
| 700-K | |||
| DC-13/Q600 | |||
| 1 pole | 24V | [A] | 2.3 |
| 48V | [A] | 1 | |
| 110V | [A] | 0.55 | |
| 125V | [A] | 0.55 | |
| 220V | [A] | 0.27 | |
| 250V | [A] | 0.27 | |
| 400V | [A] | 0.15 | |
| 440V | [A] | 0.15 | |
| 600V | [A] | 0.1 | |
Cross Sections
Coil Data
| 700-K | |||
| Operating Limits | |||
| AC control 50 Hz, 60 Hz, 50/60 Hz |
pick-up | [x Us] | 0.85…1.1 |
| dropout | [x Us] | 0.2…0.75 | |
| DC control | pick-up | [x Us] | 0.8…1.1 9, 12, 24, 110V DC: 0.7…1.25 |
| dropout | [x Us] | 0.1…0.75 | |
| Coil Consumption | |||
| AC control 50 Hz, 60 Hz, 50/60 Hz |
pick-up | [VA/W] | 35/32 |
| hold-in | [VA/W] | 5/1.8 | |
| DC control | pick-up | [W] | cold 3.0, warm 2.6 |
| hold-in | [W] | cold 3.0, warm 2.6 | |
| Operating Times | |||
| AC | closing delay | [ms] | 15…40 |
| opening delay | [ms] | 15…33 | |
| With RC module | opening delay | [ms] | 15…28 |
| DC | closing delay | [ms] | 18…40 |
| opening delay | [ms] | 6…12 | |
| With integrated diode | opening delay | [ms] | 8…12 |
| With external diode | opening delay | [ms] | 35…50 |
General Data
| 700-K | ||
| Rated Isolation Voltage Ui | ||
| IEC | [V] | 690 |
| UL, CSA | [V] | 600 |
| 1 minute acc. to IEC 60947-5-1 | [V] | — |
| Rated Impulse Voltage Withstand Uimp | [kV] | 6 |
| Rated Operating Voltage Ue | ||
| AC 50/60 Hz | [V] | 24, 48, 120, 230, 400, 500, 600, 690 |
| DC | [V] | 24, 48, 110, 220, 440 |
| Rated Coil Frequency | AC 50/60 Hz, DC | |
| Ambient Temperature | ||
| Storage | [°C] | -55…+80 |
| Operation at rated voltage | [°C] | -25…+60 |
| at 70°C | 15% current reduction against 60°C values | |
| Climatic Withstand | — | |
| Max. Altitude of Installation Site | [m] | 2000 NN |
| Protection Class | IP2X | |
| Auxiliary contact | — | |
| Standards | IEC/EN 60947-1, -5-1, -5-4, UL 508, CSA 22.2. No. 14 |
|
| Approvals | CE, cULus | |