IEC Industrial Relays

Catalogs > Industrial Controls Catalog > Relays, Timers, and Temperature Controllers > Industrial Relays and Timers > IEC Industrial Relays > Bulletin 700-K Control Relays

Bulletin 700-K Control Relays

Introduction Standards Compliance Product Selection Assignment of Contacts Accessories IEC Specifications Approximate Dimensions
IEC Specifications

  700-K 700-KR
AC-12 Rated Thermal Current
Ambient temperature 40°C
Ith 24…240V [A] 10
  230…500V [A] 10
  230…690V [A] 10
Ambient temperature 60°C
Ith 24…240V [A] 6
  230…500V [A] 6
  230…690V [A] 6
AC-15/B600
Switching of Solenoids and contactors
Ie 24V [A] 3
  48V [A] 3
  120V [A] 3
  230V [A] 2
  240V [A] 2
  400V [A] 1.2
  480V [A] 1
  500V [A] 1
  600V [A] 0.6
  690V [A] 0.6
Short-circuit Protection
"gG" Fuse acc. to IEC 60947-5-1, no welding of contacts
  Fuse gG [A] 10
Min. Switching Capacity 15V
For bifurcated contacts (control relays and auxiliary contact blocks)
  [mA] 2
Resistance and Power Dissipation
Main current circuit resistance, 1 pole [mW] 6.5
Power dissipation, 4 poles [W] 2.6
Total power dissipation
  AC control, warm [W] 4.4
  DC control, warm [W] 5.2
Lifespan
Mechanical [Mio. op.] 15
Electrical AC-15 (240V / 2 A) [Mio. op.] 0.7
Weight
  AC control kg (lbs.) 0.16 (0.35)
  DC control kg (lbs.) 0.2 (0.44)
Load Carrying Capacity per UL/CSA
Rated voltage AC [V] max. 600
Continuous rating 40 °C [A] 10 6
Switching capacity AC [A] B 600
Rated voltage DC [V] max. 600
Switching capacity DC [A] Q 600
  

  700-K
DC-13/Q600
1 pole 24V [A] 2.3
  48V [A] 1
  110V [A] 0.55
  125V [A] 0.55
  220V [A] 0.27
  250V [A] 0.27
  400V [A] 0.15
  440V [A] 0.15
  600V [A] 0.1
  

Cross Sections

Conductor Cross Sections
- Main Contacts, Auxiliary Contacts, and Coil Terminals
700-K 700-KR
Terminal type ⋆   
Click to enlarge - 140M-29-1 Click to enlarge - 100-K_Push-In
Click to enlarge - 140M-29-4 Fine stranded with ferrule (1) Conductor
(2) Conductors
[mm2]
[mm2]
0.75…2.5
0.75…2.5
0.50…2.5
0.50…2.5
Click to enlarge - 140M-29-6 Solid or coarse stranded (1) Conductor
(2) Conductors
[mm2]
[mm2]
1…4
1…2.5 + 1…4
0.75…2.5 ♣ 
0.75…2.5 ♣ 
Click to enlarge - 140M-29-5
Recommended torque [Nm] 1.2
Cross section per UL/CSA [AWG] 18…12 ‡  18…14 ♣ 
Recommended torque [lb-in] 10.6
  
⋆ Pozidriv No. 2 / Blade No. 3 screw
‡ Use same cross sections
♣  Stranded wire only

Coil Data

  700-K
Operating Limits
AC control
50 Hz, 60 Hz, 50/60 Hz
pick-up [x Us] 0.85…1.1
dropout [x Us] 0.2…0.75
DC control pick-up [x Us] 0.8…1.1
9, 12, 24, 110V DC: 0.7…1.25
dropout [x Us] 0.1…0.75
Coil Consumption
AC control
50 Hz, 60 Hz, 50/60 Hz
pick-up [VA/W] 35/32
hold-in [VA/W] 5/1.8
DC control pick-up [W] cold 3.0, warm 2.6
hold-in [W] cold 3.0, warm 2.6
Operating Times
AC closing delay [ms] 15…40
opening delay [ms] 15…33
With RC module opening delay [ms] 15…28
DC closing delay [ms] 18…40
opening delay [ms] 6…12
With integrated diode opening delay [ms] 8…12
With external diode opening delay [ms] 35…50
  

General Data

  700-K
Rated Isolation Voltage Ui  
IEC [V] 690
UL, CSA [V] 600
1 minute acc. to IEC 60947-5-1 [V]
Rated Impulse Voltage Withstand Uimp [kV] 6
Rated Operating Voltage Ue    
AC 50/60 Hz [V] 24, 48, 120, 230, 400, 500, 600, 690
DC [V] 24, 48, 110, 220, 440
Rated Coil Frequency   AC 50/60 Hz, DC
Ambient Temperature    
Storage [°C] -55…+80
Operation at rated voltage [°C] -25…+60
at 70°C   15% current reduction against 60°C values
Climatic Withstand  
Max. Altitude of Installation Site [m] 2000 NN
Protection Class   IP2X
Auxiliary contact  
Standards   IEC/EN 60947-1, -5-1, -5-4,
UL 508, CSA 22.2. No. 14
Approvals   CE, cULus