1492-L3P
|
1492-LDG3P
|
1492-LDAG3
|
Dimensions are not intended to be used for manufacturing purposes. Note: Height dimension is measured from top of rail to top of terminal block.
|
|
|
|
| Specifications
|
Single circuit plug-in component block for a variety of components
|
Terminal block with slot for plug-in component, feed-through circuit and 1 ground connection
|
Analog Loop Control Terminal Block with 2 Feed-Through Circuits and 1 Ground Connection
|
| Certifications
|
|
CSA
|
IEC
|
|
CSA
|
IEC
|
|
CSA
|
IEC
|
| Voltage Rating
|
600V AC/DC
|
500V AC/DC
|
300V AC/DC
|
250V AC/DC
|
300V AC/DC
|
250V AC/DC
|
| Maximum Current
|
20 A
|
24 A
|
10 A
|
20 A
|
10 A
|
24 A
|
| Wire Range (Rated Cross Section)
|
#30…12 AWG
|
4 mm2
|
#26…12 AWG
|
2.5 mm2
|
#26…12 AWG
|
2.5 mm2
|
| Wire Strip Length
|
0.39 in. (10 mm)
|
0.31 in. (8 mm)
|
0.31 in. (8 mm)
|
| Density
|
|
59 pcs/ft (196 pcs/m)
|
59 pcs/ft (196 pcs/m)
|
59 pcs/ft (196 pcs/m)
|
| Housing Temperature Range
|
-58…+248 °F (-50…+120 °C)
|
-58…+248 °F (-50…+120 °C)
|
-58…+248 °F (-50…+120 °C)
|
Terminal Blocks
|
Cat. No.
|
Pkg Qty.
|
Cat. No.
|
Pkg Qty.
|
Cat. No.
|
Pkg Qty.
|
| Color
|
Grey
|
1492-L3P
|
25
|
1492-LDG3P
|
25
|
1492-LDAG3
|
25
|
Accessories
|
Cat. No.
|
Pkg Qty.
|
Cat. No.
|
Pkg Qty.
|
Cat. No.
|
Pkg Qty.
|
Mounting Rails 1 m Symmetrical DIN (Steel)
|
199-DR1
|
10
|
199-DR1
|
10
|
199-DR1
|
10
|
| 1 m Symmetrical DIN (Aluminum)
|
1492-DR5
|
10
|
1492-DR5
|
10
|
1492-DR5
|
10
|
1 m Hi-Rise Symmetrical DIN (Aluminum)
|
1492-DR6
|
2
|
1492-DR6
|
2
|
1492-DR6
|
2
|
| 1 m Angled Hi-Rise Sym. DIN (Steel)
|
1492-DR7
|
2
|
1492-DR7
|
2
|
1492-DR7
|
2
|
| End Barrier
|
1492-EBL3
|
50
|
1492-EBLDAG3
|
20
|
1492-EBLDAG3
|
20
|
End Anchors and Retainers Screwless End Retainer
|
1492-ERL35
|
20
|
1492-ERL35
|
20
|
1492-ERL35
|
20
|
| DIN Rail — Normal Duty
|
1492-EAJ35
|
100
|
1492-EAJ35
|
100
|
1492-EAJ35
|
100
|
| DIN Rail — Heavy Duty
|
1492-EAHJ35
|
50
|
1492-EAHJ35
|
50
|
1492-EAHJ35
|
50
|
Jumpers Plug-In Center Jumper — 50-pole
|
1492-CJK5-50
|
10
|
1492-CJLJ5-50
|
10
|
1492-CJLJ5-50
|
10
|
| Plug-In Center Jumper — 10-pole
|
1492-CJK5-10
|
20
|
1492-CJLJ5-10
|
20
|
1492-CJLJ5-10
|
20
|
| Plug-In Center Jumper — 9-pole
|
1492-CJK5-9
|
20
|
1492-CJLJ5-9
|
20
|
1492-CJLJ5-9
|
20
|
| Plug-In Center Jumper — 8-pole
|
1492-CJK5-8
|
20
|
1492-CJLJ5-8
|
20
|
1492-CJLJ5-8
|
20
|
| Plug-In Center Jumper — 7-pole
|
1492-CJK5-7
|
20
|
1492-CJLJ5-7
|
20
|
1492-CJLJ5-7
|
20
|
| Plug-In Center Jumper — 6-pole
|
1492-CJK5-6
|
20
|
1492-CJLJ5-6
|
20
|
1492-CJLJ5-6
|
20
|
| Plug-In Center Jumper — 5-pole
|
1492-CJK5-5
|
20
|
1492-CJLJ5-5
|
20
|
1492-CJLJ5-5
|
20
|
| Plug-In Center Jumper — 4-pole
|
1492-CJK5-4
|
60
|
1492-CJLJ5-4
|
60
|
1492-CJLJ5-4
|
60
|
| Plug-In Center Jumper — 3-pole
|
1492-CJK5-3
|
60
|
1492-CJLJ5-3
|
60
|
1492-CJLJ5-3
|
60
|
| Plug-In Center Jumper — 2-pole
|
1492-CJK5-2
|
60
|
1492-CJLJ5-2
|
60
|
1492-CJLJ5-2
|
60
|
Other Accessories Disconnect Plug
|
1492-DPL
|
50
|
1492-DPL
|
50
|
—
|
—
|
| Component Plug
|
1492-CPL
|
50
|
1492-CPL
|
50
|
—
|
—
|
Fuse Plug Without Blown Fuse Indicator
|
1492-FPK2
|
20
|
1492-FPK2
|
20
|
—
|
—
|
| 10…36V Blown Fuse Indicator
|
1492-FPK224
|
20
|
⋆
|
1492-FPK224
|
20
|
—
|
—
|
| 35…70V Blown Fuse Indicator
|
1492-FPK248
|
20
|
⋆
|
1492-FPK248
|
20
|
—
|
—
|
| 60…150V Blown Fuse Indicator
|
1492-FPK2120
|
20
|
⋆
|
1492-FPK2120
|
20
|
—
|
—
|
| 140…250V Blown Fuse Indicator
|
1492-FPK2250
|
20
|
⋆
|
1492-FPK2250
|
20
|
—
|
—
|
Reducing Sleeves 28…24 AWG (0.13…0.2 mm2) White
|
1492-PSL3-2
|
100
|
—
|
—
|
—
|
—
|
Reducing Sleeves 22…20 AWG (0.25…0.5 mm2) Grey
|
1492-PSL3-5
|
100
|
—
|
—
|
—
|
—
|
Reducing Sleeves 18 AWG (0.75…1.0 mm2) Dark Grey
|
1492-PSL3-10
|
100
|
—
|
—
|
—
|
—
|
| Test Plug
|
1492-TPL5
|
25
|
1492-TP23
|
20
|
—
|
—
|
| Electrical Warning Plate
|
1492-EWPL5
|
20
|
—
|
—
|
—
|
—
|
Marking Systems Snap-In Marker Cards
|
1492-M5X10 (144/card)
|
5
|
1492-M5X10 (144/card)
|
5
|
1492-M5X10 (144/card)
|
5
|
| Snap-In Marker Cards
|
1492-M5X5 (200/card)
|
5
|
1492-M5X5 (200/card)
|
5
|
1492-M5X5 (200/card)
|
5
|
|
|
| ⋆ When using Cat. No. 1492-LDG3P with a fuse plug, a center jumper cannot be used on the top level. The only jumper option to use in combination with a fuse plug is a 2-pole side jumper: Cat. No. 1492-SJLM5-2.
|