Panel Mount Blocks
IntroductionAllen-Bradley Panel Mount Blocks are most often used when the installation requires only a few terminations. Designed to save on installation time, Allen-Bradley Panel Mount Blocks are ready to wire after mounting; no rail is needed. Available in four different styles and seven different types, the wide variety meets the needs of most applications.
Catalog Number 1492-HC6 blocks feature six poles in a two-inch long, finger-safe design. The Catalog Number 1492-HC6 has an interlocking feature which saves space in multi-block installations. Mounting screws are included.
Other Panel Mount Block Styles Include:
- Multiple Barrier Strip (Catalog Numbers 1492-HJ86, 1492-HJ812), for simple connection of solid or stranded wires, 6 or 12 poles.
- Pull-Apart Blocks (Catalog Numbers 1492-EC85, 1492-ED103), which allow the disconnection of multiple poles at once, are available in 3- or 5-pole versions and are used extensively in Motor Control Centers.
- High Temperature Dovetail Blocks (Catalog Numbers 1492-15T, 1492-25T), capable of handling up to 302 °F (150 °C). These blocks have a dovetail design, which allows multiple poles to be interlocked. They require only two fastening points every 12 blocks.
Note: Panel Mount terminal blocks come standard with a write-on marking surface for easy product identification. All Panel Mount Blocks are made of materials with a 94-V2 flammability rating except Catalog Numbers 1492-15T and 1492-25T, which are made of 94-V0 material.
Note: Most Panel Mount Blocks are UL Component Recognized and CSA Certified. Look for
|
or CSA in the product specifications.
- UL File Number E40735, Guide Number XCFR2
- CSA File Number LR67896, Class 622801
Panel Mount Blocks
| 1492-HC6 | 1492-HJ86 | 1492-HJ812 | ||||
| Dimensions are not intended to be used for manufacturing purposes. |
|
|
|
|||
| Specifications | High-density 6-pole panel mount terminal block. Can be interconnected to make 12- and 18-pole units. | Standard 6-pole panel mount block. Screw terminal with wire clamp. |
Standard 12-pole panel mount block. Screw terminal with wire clamp. |
|||
| Certifications |
|
|
|
|||
| Voltage Rating | 600V AC/DC | 600V AC/DC | 600V AC/DC | |||
| Maximum Current (per pole) | 25 A | 25 A | 25 A | |||
| Wire Range (Rated Cross Section) | #30…#12 AWG (0.05…4 mm2) | #16…#12 AWG (1.5…4 mm2) | #16…#12 AWG (1.5…4 mm2) | |||
| Wire Strip Length | 0.38 in. (9.7 mm) | 0.38 in. (9.7 mm) | 0.38 in. (9.7 mm) | |||
| Recommended Tightening Torque | 3…7 lbin (0.3…0.8 Nm) | 8…16 lbin (0.9…1.8 Nm) | 8…16 lbin (0.9…1.8 Nm) | |||
| Insulation Temperature Range | 40…+221 °F (40…+10 5°C) | 40…+221 °F (40…+105 °C) | 40…+221 °F (40…+105 °C) | |||
| Terminal Blocks | Cat. No. | Pkg Qty. | Cat. No. | Pkg Qty. | Cat. No. | Pkg Qty. |
| Terminal Block | 1492-HC6 | 1 | 1492-HJ86 | 1 | 1492-HJ812 | 1 |
| Accessories (Mounting Rails) | Cat. No. | Pkg Qty. | Cat. No. | Pkg Qty. | Cat. No. | Pkg Qty. |
| Jumpers: 2-Pole Uninsulated |
1492-N38 | 50 | 1492-N38 | 50 | 1492-N38 | 50 |
| 50-pole Uninsulated | 1492-N39 | 10 | — | — | — | — |
| Insulating Sleeve | 1492-SJS | 10 | — | — | — | — |
| Anchor Unit: (required every 12th block) |
Not Required | — | Not Required | — | Not Required | — |
| End Piece | Not Required | — | Not Required | — | Not Required | — |
| ¬ #8-32 screw. | ||||||
| T Measurement between mounting screw centers. | ||||||
| Mounting screws are offset 0.31 in. (7.9 mm) from centerline. | ||||||
| § Mounting screws are offset 0.19 in. (4.76 mm) from centerline. | ||||||
| 1492-15T | 1492-25T | |||
| Dimensions are not intended to be used for manufacturing purposes. |
|
|
||
| Specifications | High temperature 1-pole panel mount block, wire clamp. Gangable for multi-pole installation. |
High temperature 1-pole panel mount block, wire clamp. Gangable for multi-pole installation. |
||
| Voltage Rating | 600V AC/DC | 600V AC/DC | ||
| Maximum Current (per pole) | 35 A | 45 A | ||
| Wire Range (Rated Cross Section) | #16…12 AWG (1.5…4 mm2) | #16…10 AWG (1.5…6 mm2) | ||
| Wire Strip Length | 0.38 in. (9.7 mm) | 0.38 in. (9.7 mm) | ||
| Recommended Tightening Torque | 10…16 lbin (1.1…1.8 Nm) | 10…16 lbin (1.1…1.8 Nm) | ||
| Insulation Temperature Range | 40…+300 °F (40…+149 °C) | 40…+300 °F (40…+149 °C) | ||
| Terminal Blocks | Cat. No. | Pkg Qty. | Cat. No. | Pkg Qty. |
| Terminal Block | 1492-15T | 100 | 1492-25T | 100 |
| Accessories (Mounting Rails) | Cat. No. | Pkg Qty. | Cat. No. | Pkg Qty. |
| Anchor Unit: (required every 12th block) |
1492-25A | 10 | 1492-25A | 10 |
| End Piece | 1492-15E | 25 | 1492-25E | 25 |
| 1492-EC85 | 1492-ED103 | |||
| Dimensions are not intended to be used for manufacturing purposes. |
|
|
||
| Specifications | 5-pole terminal block. Pulls apart to disconnect all poles from the circuit. |
3-pole terminal block. Pulls apart to disconnect all poles from the circuit. |
||
| Certifications (See Allen-Bradley terminal blocks generally have been designed to meet the requirements of one or more regulatory bodies. Most products have also been tested per additional standards. The following is a listing of some of the regulatory bodies and standards which apply to Allen-Bradley terminal block products. See the particular product description for information on specific certifications and ratings.) |
|
|
||
| Voltage Rating | 600V AC/DC | 600V AC/DC | ||
| Maximum Current (per pole) | 25 A | 60 A | ||
| Wire Range (Rated Cross Section)T | #20…12 AWG (0.75…4 mm2) | #14…4 AWG (2.5…25 mm2) | ||
| Wire Strip Length | 0.38 in. (9.7 mm) | 0.38 in. (9.7 mm) | ||
| Recommended Tightening Torque | 6…16 lbin (0.7…1.8 Nm) | 10…30 lbin (1.1…3.4 Nm) | ||
| Insulation Temperature Range | 40…+22 °F (40…+105 °C) | 40…+221 °F (40…+105 °C) | ||
| Terminal Blocks | Cat. No. | Pkg Qty. | Cat. No. | Pkg Qty. |
| Terminal Block | 1492-EC85 | 1 | 1492-ED103 | 1 |
| Accessories (Mounting Rails) | Cat. No. | Pkg Qty. | Cat. No. | Pkg Qty. |
| Jumpers: 2-Pole Uninsulated |
1492-N38 | 50 | 1492-N38 | 50 |
| Anchor Unit: (required every 12th block) |
Not Required | — | Not Required | — |
| End Piece | Not Required | — | Not Required | — |
| ¬ #8-32 screw. | ||||
| T Both terminal blocks accept 1 wire per terminal. | ||||