Catalogs > Industrial Controls Catalog > Terminal Blocks and Wiring Systems > Wiring Systems
Wiring Systems
Bulletin 1756 ControlLogix IFM/XIM and Cable Selection Table
Digital 8-Point and 16-Point I/O Modulesv
| Description of 20-Terminal IFM | Cat. No. for Wiring System Module with Fixed Terminal Block | Cat. No. for Wiring System Module with Removable Terminal Block Socket Assembly (order plugs separately) | I/O Module Cat. No. 1756-… | ||||||||||||||
| I A 8 D |
I A 1 6 |
I B 1 6 |
I C 1 6 |
I N 1 6 |
I V 1 6 |
O A 8 |
O A 8 D |
O A 8 E |
O A 1 6 |
O B 8 |
O B 1 6 E |
O C 8 |
O N 8 |
O V 1 6 E |
|||
| Feed-through | |||||||||||||||||
| Standard 264V AC/DC Max. | 1492-IFM20F | 1492-RIFM20FØ | U | X | X | X | X | X | U | U | U | X | U | X | U | U | X |
| Narrow standard 132V AC/DC Max. | 1492-IFM20FN | 1492-RIFM20FNz | U | X | X | X | X | X | U | U | U | X | U | X | U | U | X |
| Extra terminals (2 per I/O) 264V AC/DC Max. | 1492-IFM20F-2 | 1492-RIFM20F-2Ø | U | X | X | X | X | X | U | U | U | X | U | X | U | U | X |
| 3-wire sensor type input devices 132V AC/DC Max. | 1492-IFM20F-3 | — | — | X | X | X | X | X | — | — | — | — | — | — | — | — | — |
| LED Indicating | |||||||||||||||||
| Standard with 24V AC/DC LEDs | 1492-IFM20D24 | — | — | — | X | — | X | X | — | — | — | — | — | X | — | — | X |
| Narrow standard with 24V AC/DC LEDs | 1492-IFM20D24N | — | — | — | X | — | X | X | — | — | — | — | — | X | — | — | — |
| Standard with 120V AC/DC LEDs | 1492-IFM20D120 | — | U | X | — | — | — | — | — | — | — | — | — | — | — | — | — |
| Narrow standard with 120V AC LEDs | 1492-IFM20D120N | — | U | X | — | — | — | — | — | — | — | X | — | — | — | — | — |
| 24V AC/DC LEDs and extra terminals for outputs | 1492-IFM20D24-2 | — | — | — | — | — | — | — | — | — | — | — | — | X | — | — | X |
| 24V AC/DC LEDs and extra terminals for inputs | 1492-IFM20D24A-2 | — | — | — | X | — | X | X | — | — | — | — | — | — | — | — | — |
| 120V AC LEDs and extra terminals for outputs | 1492-IFM20D120-2 | — | — | — | — | — | — | — | — | — | — | X | — | — | — | — | — |
| 120V AC LEDs and extra terminals for inputs | 1492-IFM20D120A-2 | — | U | X | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 3-wire sensor with 24V AC/DC LEDs | 1492-IFM20D24-3 | — | — | — | X | — | X | X | — | — | — | — | — | — | — | — | — |
| 8 Individually isolated with 24/48V AC/DC LEDs and 4 terminals/output | 1492-IFM20DS24-4 | — | — | — | — | — | — | — | — | — | — | — | W | — | W | W | — |
| 8 Individually isolated with 120V AC LEDs and 4 terminals/output | 1492-IFM20DS120-4 | — | — | — | — | — | — | — | W | V | V | — | — | — | — | — | — |
| 240V AC LEDs and extra terminals for outputs | 1492-IFM20D240-2 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 240V AC LEDs and extra terminals for inputs | 1492-IFM20D240A-2 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| Fusible | |||||||||||||||||
| 120V AC/DC with extra terminals for outputs | 1492-IFM20F-F-2 | 1492-RIFM20F-F-2Ø | — | — | — | — | — | — | — | — | — | X | — | X | — | — | X |
| Extra terminals with 24V AC/DC blown fuse LED indicators | 1492-IFM20F-F24-2 | 1492-RIFM20F-F24-2Ø | — | — | — | — | — | — | — | — | — | — | — | X | — | — | X |
| Extra terminals with 120V AC/DC blown fuse LED indicators | 1492-IFM20F-F120-2 | 1492-RIFM20F-F120-2Ø | — | — | — | — | — | — | — | — | — | X | — | — | — | — | — |
| Extra terminals with 240V AC/DC blown fuse LED indicators | 1492-IFM20F-F240-2 | — | — | — | — | — | — | — | — | — | — | X | — | — | — | — | — |
| Extra terminals with 24V AC/DC blown fuse LED indicators for inputs | 1492-IFM20F-F24A-2 | 1492-RIFM20F-F24A-2Ø | — | — | X | — | X | — | — | — | — | — | — | — | — | — | — |
| Extra terminals with 120V AC/DC blown fuse LED indicators for inputs | 1492-IFM20F-F120A-2 | 1492-RIFM20F-F120A-2Ø | — | X | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 8 Individually isolated 120V AC/DC with extra terminals for outputs | 1492-IFM20F-FS-2 | — | — | — | — | — | — | — | W | V | V | — | W | — | W | W | — |
| 8 Individually isolated with extra terminals and 24V AC/DC blown fuse LED indicators | 1492-IFM20F-FS24-2 | — | — | — | — | — | — | — | — | — | — | — | W | — | W | W | — |
| Two 4-point isolated groups with four terminals/input and 24V AC/DC blown fuse LED indicators | 1492-IFM20F-FS24A-4 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 8 Individually isolated with extra terminals/output and 120V AC/DC blown fuse LED indicators | 1492-IFM20F-FS120-2 | — | — | — | — | — | — | — | W | V | V | — | — | — | — | — | — |
| 8 Individually isolated with 4 terminals/output and 120V AC/DC blown fuse LED indicators | 1492-IFM20F-FS120-4 | — | — | — | — | — | — | — | W | V | V | — | — | — | — | — | — |
| Two 4-point isolated groups with four terminals/input and 120V AC/DC blown fuse indicators | 1492-IFM20F-FS120A-4 | — | U | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 8 Individually isolated with 4 terminals/output and 240V AC/DC blown fuse LED indicators | 1492-IFM20F-FS240-4 | — | — | — | — | — | — | — | W | — | — | — | — | — | — | — | — |
| Relay Master (LED Indicating) § § | |||||||||||||||||
| 20-pin master with eight 24V DC relays | 1492-XIM2024-8R | — | — | — | — | — | — | — | — | — | — | — | — | X | — | — | — |
| 20-pin master with sixteen 24V DC relays | 1492-XIM2024-16R | — | — | — | — | — | — | — | — | — | — | — | — | X | — | — | — |
| 20-pin master with sixteen 24V DC relays with fusing | 1492-XIM2024-16RF | — | — | — | — | — | — | — | — | — | — | — | — | X | — | — | — |
| 20-pin master with eight 120V AC relays | 1492-XIM20120-8R | — | — | — | — | — | — | — | — | — | — | X | — | — | — | — | — |
| 20-pin master with sixteen 120V AC relays | 1492-XIM20120-16R | — | — | — | — | — | — | — | — | — | — | X | — | — | — | — | — |
| 20-pin master with sixteen 120V AC relays with fusing | 1492-XIM20120-16RF | — | — | — | — | — | — | — | — | — | — | X | — | — | — | — | — |
| Relay Expander (LED Indicating)§ § | |||||||||||||||||
| Expander with eight 24V DC relays | 1492-XIM24-8R | 1492-RXIM24-8Rv | — | — | — | — | — | — | — | — | — | — | — | ¬ | — | — | — |
| Expander with eight 120V AC relays | 1492-XIM120-8R | — | — | — | — | — | — | — | — | — | — | ¬ | — | — | — | — | — |
| Fusible Expander | |||||||||||||||||
| 8-channel expander with 24V DC blown fuse indicators | 1492-XIMF-F24-2 | — | — | — | — | — | — | — | — | — | — | — | — | ¬ | — | — | — |
| 8-channel expander with 120V AC blown fuse indicators | 1492-XIMF-F120-2 | — | — | — | — | — | — | — | — | — | — | ¬ | — | — | — | — | — |
| Feed-through Expander | |||||||||||||||||
| Expander with eight feed-through channels 132V AC/DC max | 1492-XIMF-2 | — | — | — | — | — | — | — | — | — | — | ¬ | — | ¬ | — | — | — |
| ¬ Can have up to one (1) expander module depending upon master used (total 16 outputs or less). An extender cable is provided. | |||||||||||||||||
| T Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the catalog number, e.g., 005 = 0.5 m (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CABLE050W is for a 5.0 m cable, and the letter W. | |||||||||||||||||
| This IFM is not recommended for use with PLC I/P modules that have an off-state leakage current exceeding 0.5 mA. Use a 1492-IFM20D120N or 1492-20D120A-2 for inputs. Use 1492-IFM20D120-2 for outputs. | |||||||||||||||||
| § The LED indicates the PLC output status. | |||||||||||||||||
| Ø Compatible RTB plug 1492-RTB20N (screw style terminal) or 1492-RTB20P (push-in style). Order plugs separately. 2 plugs per cat. no. | |||||||||||||||||
| z Compatible RTB plug 1492-RTB10N (screw style terminal) or 1492-RTB10P (push-in style). Order plugs separately. 2 plugs per cat. no. | |||||||||||||||||
| v Compatible RTB plug 1492-RTB12N (screw style terminal) or 1492-RTB12P (push-in style). Order plugs separately. 2 plugs per cat. no. | |||||||||||||||||
| § The voltage rating is relay contro/coil voltage. Refer to the Specifications tab. |
Note:Footnotes are on page 12-136.
Bulletin 1756 ControlLogix IFMs and Cables, Continued
Digital 16-Point Isolated and 32-Point I/O Modules ¬
| Description of 40-Terminal IFM | Cat. No. with Wiring System Module with Fixed Terminal Block | Cat. No. for Wiring System Module with Removable Terminal Block Socket Assembly (order plugs separately) | I/O Module Cat. No. 1756-… | |||||||||||||||||
| I A 1 6 I |
I B 1 6 D |
I B 1 6 I |
I A 3 2 |
I B 3 2 |
I V 3 2 |
I H 1 6 I |
I M 1 6 I |
O A 1 6 I |
O B 8 E I |
O B 1 6 D |
O B 1 6 I |
O B 1 6 I S |
O B 3 2 |
O V 3 2 E |
O H 8 I |
O W 1 6 I |
O X 8 I |
|||
| Feed-through | ||||||||||||||||||||
| Standard 132V AC/DC Max. | 1492-IFM40F | 1492-RIFM40Fª | Y | Y | Y | Z | Z | Z | Y | — | Y | Y | Y | Y | Y | Z | Z | Y | Y | Y |
| Extra terminals (2 per I/O) 132V AC/DC Max. | 1492-IFM40F-2 | 1492-RIFM40F-2ª | — | Y | — | Z | Z | Z | — | — | — | — | Y | — | — | Z | Z | — | — | — |
| 3-wire sensor type input devices 60V AC/DC Max. | 1492-IFM40F-3 | — | — | — | — | — | Z | Z | — | — | — | — | — | — | — | — | — | — | — | — |
| LED Indicating | ||||||||||||||||||||
| Standard with 24V AC/DC LEDs | 1492-IFM40D24 | 1492-RIFM40D24ª | — | — | — | — | Z | Z | — | — | — | — | — | — | — | Z | Z | — | — | — |
| 24V AC/DC LEDs and extra terminals for outputs | 1492-IFM40D24-2 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | Z | Z | — | — | — |
| 24V AC/DC LEDs and extra terminals for inputs | 1492-IFM40D24A-2 | 1492-RIFM40D24A-2ª | — | — | — | — | Z | Z | — | — | — | — | — | — | — | — | — | — | — | — |
| 120V AC LEDs and extra terminals for outputs | 1492-IFM40D120-2 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 120V AC LEDs and extra terminals for inputs | 1492-IFM40D120A-2 | — | — | — | — | Z | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 3-wire sensor with 24V AC/DC LEDs | 1492-IFM40D24-3 | — | — | — | — | — | Z | Z | — | — | — | — | — | — | — | — | — | — | — | — |
| 16 individually isolated with 24/48V AC/DC LEDs and four terminals/output | 1492-IFM40DS24-4 | — | — | — | — | — | — | — | — | — | — | Y | Y13 | Y | Y | — | — | — | Y | Y |
| 16 individually isolated with 24V AC/DC LEDs and four terminals/input | 1492-IFM40DS24A-4 | — | — | Y | Y | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 16 individually isolated with 120V AC LEDs and four terminals/output | 1492-IFM40DS120-4 | — | — | — | — | — | — | — | — | — | Y | — | — | — | — | — | — | — | Y | Y |
| 16 individually isolated with 120V AC LEDs and four terminals/input | 1492-IFM40DS120A-4 | — | Y | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 16 individually isolated with 240V AC LEDs and four terminals/input | 1492-IFM40DS240A-4 | — | — | — | — | — | — | — | — | Y | — | — | — | — | — | — | — | — | — | — |
| Fusible | ||||||||||||||||||||
| 120V AC/DC with extra terminals for 32-point outputs | 1492-IFM40F-F-2 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | Z | Z | — | — | — |
| Extra terminals with 24V AC/DC blown fuse indicators for 32-point outputs | 1492-IFM40F-F24-2 | 1492-RIFM40F-F24-2ª | — | — | — | — | — | — | — | — | — | — | — | — | — | Z | Z | — | — | — |
| 16 individually fused with 24V DC blown fuse low leakage (0.05 mA) LED circuit, 2 isolated groups, 2 terminals/output | 1492-IFM40F-F24D-2 | — | — | — | — | — | — | — | — | — | — | — | Y | — | — | — | — | — | — | — |
| Individually fused with 24V DC blown fuse low leakage (0.05 mA) LED circuit, 4 isolated groups, 4 terminals/input | 1492-IFM40F-F24AD-4 | — | — | Y | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| Extra terminals with 120V AC/DC blown fuse indicators for outputs | 1492-IFM40F-F120-2 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 16 individually isolated with extra terminals for 120V AC/DC outputs | 1492-IFM40F-FS-2 | — | — | — | — | — | — | — | — | — | Y | Y | Y | Y12 | Y12 | — | — | Y | Y | Y |
| 16 individually isolated with extra terminals and 24V AC/DC blown fuse indicators | 1492-IFM40F-FS24-2 | — | — | — | — | — | — | — | — | — | — | Y | T | Y12 | Y12 | — | — | — | Y | Y |
| 16 individually isolated with 24V AC/DC blown fuse indicators and four terminals/output | 1492-IFM40F-FS24-4 | — | — | — | — | — | — | — | — | — | — | Y | T | Y12 | Y12 | — | — | — | Y | Y |
| 16 individually isolated 240V AC/DC with four terminals/output | 1492-IFM40F-FS-4 | — | — | — | — | — | — | — | — | — | Y | Y | Y | Y12 | Y12 | — | — | — | Y | Y |
| 16 individually isolated with extra terminals and 120V AC/DC blown fuse LED indicators | 1492-IFM40F-FS120-2 | 1492-RIFM40F-FS120-2ª | — | — | — | — | — | — | — | — | Y | — | — | — | — | — | — | Y | Y | Y |
| 16 individually isolated with 120V AC/DC blown fuse indicators and four terminals/output | 1492-IFM40F-FS120-4 | 1492-RIFM40F-FS120-4v | — | — | — | — | — | — | — | — | Y | — | — | — | — | — | — | — | Y | Y |
| 16 individually isolated with 240V AC/DC blown fuse indicators and four terminals/output | 1492-IFM40F-FS240-4 | — | — | — | — | — | — | — | — | — | Y | — | — | — | — | — | — | — | Y | Y |
| 16 individually isolated with 24V AC/DC blown fuse indicators and four terminals/input | 1492-IFM40F-FS24A-4 | — | — | | Y | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| 16 individually isolated with 120V AC/DC with four terminals/input | 1492-IFM40F-FSA-4 | — | Y | Y | Y | — | — | — | Y | — | — | — | — | — | — | — | — | — | — | — |
| 16 individually isolated with 120V AC/DC blown fuse indicators and four terminals/input | 1492-IFM40F-FS120A-4 | 1492-RIFM40F-FS120A-4v | Y | — | — | — | — | — | Y | — | — | — | — | — | — | — | — | — | — | — |
| 16 individually isolated with 240V AC/DC blown fuse indicators and four terminals/input | 1492-IFM40F-FS240A-4 | — | — | — | — | — | — | — | — | Y | — | — | — | — | — | — | — | — | — | — |
| Relay Master (LED Indicating)§ § | ||||||||||||||||||||
| 40-pin master with eight 24V DC relays | 1492-XIM4024-8R | — | — | — | — | — | — | — | — | — | — | — | — | — | — | Z | — | — | — | — |
| 40-pin master with sixteen 24V DC relays | 1492-XIM4024-16R | 1492-RXIM4024-16Rª | — | — | — | — | — | — | — | — | — | — | — | — | — | Z | — | — | — | — |
| 40-pin master with sixteen 24V DC relays with fusing | 1492-XIM4024-16RF | — | — | — | — | — | — | — | — | — | — | — | — | — | — | Z | — | — | — | — |
| Relay Expander (LED Indicating)§ § | ||||||||||||||||||||
| Expander with eight 24V DC relays | 1492-XIM24-8R | 1492-RXIM24-8R11 | — | — | — | — | — | — | — | — | — | — | — | — | — | Ø | — | — | — | — |
| Expander with eight 120V AC relays | 1492-XIM120-8R | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| Fusible Expander | ||||||||||||||||||||
| 8-channel expander with 24V DC blown fuse indicators | 1492-XIMF-F24-2 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | Ø | — | — | — | — |
| 8-channel expander with 120V AC blown fuse indicators | 1492-XIMF-F120-2 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — |
| Expander with sixteen 24V DC relays with fusing | 1492-XIM24-16RF | — | — | — | — | — | — | — | — | — | — | — | — | — | — | z | — | — | — | — |
| Feed-through Expander | ||||||||||||||||||||
| Expander with eight feed-through channels 132V AC/DC max | 1492-XIMF-2 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | Ø | — | — | — | — |
| ¬ Cables are available in standard lengths of 0.5, 1.0, 2.5, and 5.0 m. To order, insert the code for the desired cable length into the catalog number, e.g., 005 = 0.5 m (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m), and insert the letter in the box. Example: Catalog Number 1492-CABLE050W is for a 5.0 m cable, and the letter Y. | ||||||||||||||||||||
| T The 1492-IFM40F-FS24-2 and 1492-IFM40F-FS24-4 module and 1492-CABLET Y cable can be used with the 1756-OB16D module. However, due to the 1492-IFM40F-FS24-2 and 1492-IFM40F-Fs24-4 module's blown fuse leakage current ratings, the "no load" diagnostic function of the 1756-OB16D will not indicate a blown or removed fuse as a no load condition. If you require this diagnostic to function for a blown or removed fuse, you must use a 1492-IFM40F-F24D-2. | ||||||||||||||||||||
| The 1492-IFM40F-FS24A-4 module and 1492-CABLET Y cable can be used with the 1756-IB16D module. However, due to the 1492-IFM40F-FS24A-4 module's blown fuse leakage current rating, the "wire off" diagnostic function of the 1756-IB16D will not indicate a blown or removed fuse as a wire off condition. If you require this diagnostic to function for a blown or removed fuse, you must use a 1492-IFM40F-F24AD-4. | ||||||||||||||||||||
| § The LED indicates the PLC output status. | ||||||||||||||||||||
| Ø Can have up to 2 or 3 expander modules depending upon master used (total 32 outputs or less). An extender cable is provided. | ||||||||||||||||||||
| z One 1492-XIM24-16RF is to be used with one 1492-XIM4024-16R or 1492-XIM4024-16RF master (32 pt. only). | ||||||||||||||||||||
| ª Compatible RTB plug; 1492-RTB20N (screw style terminal) or 1492-RTB20P(push-in style terminal). ORDER PLUGS SEPARATELY. 2 plugs per cat. no. | ||||||||||||||||||||
| v Compatible RTB plug; 1492-RTB17N (screw style terminal) or 1492-RTB17P (push-in style terminal). ORDER PLUGS SEPARATELY. 2 plugs per cat. no. | ||||||||||||||||||||
| ª Compatible RTB plug; 1492-RTB14N (screw style terminal) or 1492-RTB14P(push-in style terminal). ORDER PLUGS SEPARATELY. 2 plugs per cat. no. | ||||||||||||||||||||
| 11 Compatible RTB plug; 1492-RTB12N (screw style terminal) or 1492-RTB12P(push-in style terminal). ORDER PLUGS SEPARATELY. 2 plugs per cat. no. | ||||||||||||||||||||
| 12 Do not use this module in output sinking mode with fused IFM moduls as the IFM module fuses will not properly protect the circuit. | ||||||||||||||||||||
| 13 IFMs LED provides PLC output ON/OFF indication. Due to the magnitude of current through the LED, the 1756-0B16D PLC module No Load diagnostic function will not work. If this function is required, use the Cat. No. 1492-IFM40F-2. | ||||||||||||||||||||
| § The voltage rating is relay contro/coil voltage. Refer to the Specifications tab. |
Note:Footnotes are on page 12-138.
Bulletin 1756 ControlLogix IFMs and Cables, Continued
These pre-wired cables have a pre-wired RTB on one end to connect to the front of a Bulletin 1756 digital I/O module and a connector on the other end to plug into a 20- or 40-terminal IFM/XIM. You must first select the IFM/XIM from one of the preceding selection tables.
Pre-Wired Cables for Bulletin 1756 Digital I/O Modules
| Cable Cat. No. | Standard Cable Lengths | Build-to-Order Available | No. of Conductors | Mating I/O Module Cat. No. |
| 1492-CABLE¬ U | 0.5, 1.0, 2.5, 5.0 m | Yes | 20 | 1756-IA8D, -OA8, -OA8D, -OA8E, -OB8, -OC8, -ON8 |
| 1492-CABLE¬ V | 0.5, 1.0, 2.5, 5.0 m | Yes | 20 | 1756-OA8D, -OA8E |
| 1492-CABLE¬ W | 0.5, 1.0, 2.5, 5.0 m | Yes | 20 | 1756-OA8, -OB8, -OC8, -ON8 |
| 1492-CABLE¬ X | 0.5, 1.0, 2.5, 5.0 m | Yes | 20 | 1756-IA16, -IB16, -IC16, -IN16, -IV16, -OA16, -OB16E, -OV16E |
| 1492-CABLE¬ Y | 0.5, 1.0, 2.5, 5.0 m | Yes | 40 | 1756-IA16I, -IB16D, -IB16I, -IH16, -IM16I, -OA16I, -OB8EI, -OB16D, -OB16I, -OB16IS, -OH8I, -OW16I, -OX8I |
| 1492-CABLE¬ Z | 0.5, 1.0, 2.5, 5.0 m | Yes | 40 | 1756-IB32, -IV32, -IA32, -OB32, -OV32E |
| ¬ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the cat. no. (005 = 0.5 m, 010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Cat. No. 1492-CABLE005Y is for a 0.5 m cable that could be used to connect a Cat. No. 1492-IFM40F IFM to a Cat. No. 1756-IA16I I/O module. | ||||
The I/O module-ready cables have a pre-wired RTB on one end to plug onto the front of a Bulletin 1756 I/O module and 20 or 40 individually colored #18 AWG conductors on the other end. These cables provide the convenience of pre-wired connections at the I/O module end, while still allowing the flexibility to fieldwire to standard terminal blocks of your choice.
I/O Module-Ready Cables for Bulletin 1756 Digital I/O Modules
| Cable Cat. No. | Standard Cable Lengths | Build-to-Order Available | No. of Conductors | Mating I/O Module Cat. No. |
| 1492-CABLET TBNH | 1.0, 2.5, 5.0 m | Yes | 20 | 1756-IA8D, -IA16, -IB16, -IC16, -IN16, -IV16, -OA8, -OA8D, -OA8E, -OA16, -OB8, -OB16E, -OC8, -ON8, -OV16E |
| 1492-CABLET TBCH | 1.0, 2.5, 5.0 m | Yes | 40 | 1756-IA16I, -IA32, -IB16D, -IB16I, -IB32, -IV32, -IH16I, -IM16I, -OA16I, -OB8EI, -OB16D, -OB16IS, -OB16I, -OB32, -OV32E, -OH8I, -OW16I, -OX8I |
| T Cables are available in standard lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the cat. no. (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Cat. No. 1492-CABLE050TBNH is for a 5.0 m cable with a pre-wired Cat. No. 1756-TBNH RTB on one end. | ||||
| Discrete I/O read cables should not be used with PLC analog I/O modules as cable shield and drain wires are not provided. | ||||