Panel Connection Systems
DescriptionConnecting inputs and outputs to an Allen-Bradley PLC is very convenient with Allen-Bradley PanelConnect™ Modules and cables. Unlike conventional methods of:
- wiring a number of inputs or outputs on machine devices (sensors and pneumatic valves) through a panel and maintaining the integrity of the enclosure then
- wiring the connector to a terminal block then
- wiring to the PLC I/O Module or
- facing the task of providing a seal on a number of cables entering an enclosure
Using a PanelConnect Module with associated Connection systems, allows connection of up to 32 inputs or outputs directly to a 32 point PLC Input or Output module with convenient pre-built cables and connectors.
Benefits
Simplifies Machine and System Commissioning
Often a machine or system is set up at the manufacturer and then disassembled for shipping to the job site. Many of the input and output connections need to be initially connected, then disconnected for shipment, and then reconnected for final assembly. When connecting through the enclosure, the time needed for the reconnection as well as making correct enclosure seals, and making the correct connection for final assembly can be greatly simplified and costs reduced using the PanelConnect module and Connection systems. Commissioning can be done in hours instead of taking weeks and months.
Enclosure Integrity
The PanelConnect module is a simple system that mounts on the enclosure and creates the correct seal for the entry of the input and output connections. There is no longer a need to spend the additional time to seal the opening where the sensor or output cables enter the enclosure or use custom connectors. This reduces the associated time and wiring errors as well.
Environmental Rating
PanelConnect Modules are rated for the harsh environments of IP65/NEMA Type 1, 4, 4X, and 12. These products bridge the IP20, In Panel environment to the IP65, On Machine environment.
Reduced Wiring Time and Cost
Wiring is completed in a fraction of the time when connecting the Plug and Play easy assembly system of PanelConnect modules, Pre-Wired I/O Cables, Distribution Box and Distribution Box Patch Cords when compared to traditional methods. Both standard and specific build-to-order length cables are available, providing the correct length for any panel in a neat, space-efficient wiring solution. Lower wiring costs are possible for OEMs and users because less skilled labor is needed to connect the Plug and Play system.
Minimal Repair and Replacement Time
Plug and Play PanelConnect and Connection systems are easily field replaceable using threaded secured connectors. These systems support the control system requirement for Minimal Time To Repair.
Simplified Design
Design engineers can simplify their panel drawings by calling out a PanelConnect Module and pre-wired cable instead of having to detail every individual wire and terminal block on their drawings. Simplified panel drawings aid not only the installer but also the end customer who receives the panel.
Reduced Wiring Errors
Wiring system cables are pre-tested to ensure 100% accurate connections and eliminate the need for point-to-point checking of wiring. This reduces the possibility of crossed wires and loose connections between the I/O module and the PanelConnect Module. Even one error in wiring 128 I/O points in a point-to-point system may require a complete check of the wiring. Wiring errors can take several minutes to track down and correct before the panel is ready for startup. When PanelConnect Modules and cables are snapped in place, they fit every time — no need to find the wrong or loose connection, resulting in a much higher rate of success at system startup.
Increased Volume and Productivity
PanelConnect systems can help OEMs and panel builders produce a higher volume of machines. Inter-connected wiring for a wiring system is 60 times faster to install than traditional point-to-point wiring, enabling OEMs and panel builders using PanelConnect System components to build panels faster and produce more machines. Machine segments also can be outsourced as machine segments can be connected via the Plug and Play products. Wiring is completed in a fraction of the time when connecting inputs and outputs with the Connection system and the PanelConnect Module as compared to the time required for traditional methods.
Design Flexibility
To develop a cost-effective system, the hardware components must meet the needs of the design engineer. Allen-Bradley products provide the broadest range of PanelConnect modules and cables, as well as flexibility with modularity and system expansion capabilities. Allen-Bradley Wiring Systems deliver a lower life-cycle cost.
Quality-Looking Panels
The pre-wired cables and PanelConnect modules organize the wiring in your panel providing a consistent look. Markers and pre-printed adhesive labels for the terminal wiring neatly identify field-wiring-side connections, which correspond to the I/O module. A large marking area is also available for identifying I/O information on the PanelConnect modules.
Smaller Panel Space
By mounting the PanelConnect modules on the side wall of the enclosure, DIN Rail space is eliminated in the panel when compared to traditional terminal blocks.
Reduced Wire Preparation and Routing
PanelConnect systems eliminate the time and costs associated with stripping and cutting wires. Pre-wired cables eliminate this step altogether. Routing wires is much easier with wiring systems since engineers only have to worry about routing one pre-wired cable versus 20 wires used in the traditional wiring method.
Easier Marking and Labeling
Three markers on the front of the PanelConnect are provided to mark both I/O module and input/output points and Patch Cord cables. Pre-printed, I/O-specific adhesive label strips for quick marking of power supply terminals save labor compared to point-to-point wiring that requires labor-intensive wire markers. No wire labels are required on a pre-wired cable. Voltage Marking rings are provided to note AC and DC PanelConnect modules.
Fewer Parts, Less Inventory, and Lower Carrying Cost
A wiring system involves the PanelConnect module and the cable, versus a terminal block, barrier, a jumper, markers, wires, and swing arms with traditional hardwired systems. Therefore, it requires fewer components and, in turn, less inventory and lower carrying costs.
Compatibility
PanelConnect systems works with other digital and analog Allen-Bradley 1492 Programmable Controller Wiring Systems. PanelConnect systems work with the Allen-Bradley Sensor Connection Systems as well as other leading connection systems manufacturers: Brad Harrison™ - Daniel Woodhead, Crouse Hinds, Lumberg and Turck. PanelConnect supports connector cables for both Mini-Plus and M23 style for Mini and Micro Sensor connectors.
PanelConnect System View
|
|
|
|
Typical Configuration
|
PanelConnect Input and Output Module Overview
¬ Field side connectors for two keyed (4 on 32 point) 10-pin or 12-pin Mini-Plus style connectors or M23 12-pin (not on 32 point) which mate to patchcords of the appropriate style.
T PanelConnect input/output module connector for 16-point input/output module cable.
Pre-wired or I/O ready PanelConnect Module cable.
§ Power supply Connector for Power source input.
Note:All of the digital PanelConnect for input and output products have the following features:
|
|
|
cULus Listed and CE Approved
PanelConnect 32-Point Combination (16 Input, 16 Output) Module Overview
¬ Field side connectors for four keyed 12-pin Mini-Plus style connectors which mate to 12-pin Mini-Plus style patchcords.
T PanelConnect input/output module connector for 16-point input/output module cables.
Pre-wired or I/O ready PanelConnect Module cable.
§ Power supply Connector for Power source input.
Note:All of the digital PanelConnect combination input and output products have the following features:
|
|
|
cULus Listed and CE Approved
PanelConnect Input Features
|
16-Point Input PanelConnect Module with two 10-pin Mini-Plus Connectors
These modules are used with sensor (input) distribution boxes with no LEDs. Each 10-pin Mini-Plus connector mates with a 10-conductor main patch cord that connects to the distribution box. On the field connector, various sensors (including photoelectric sensors and proximity sensors) connect with a variety of connector styles. AC and DC versions of the PanelConnect module are available to meet the input (sensor) voltage requirements. Up to 16 inputs (sensors) can be connected to each PanelConnect module. Each PanelConnect Module has an LED to indicate when the module is powered. On the internal panel side, the PanelConnect mates with a cable that connects to a PLC-input module. Cables are available to connect to the most popular Allen-Bradley PLC input modules. Modules are available in NEMA Type 4 or 4X versions.
|
16-Point Input PanelConnect Module with two 12-pin Mini-Plus Connectors
These modules are normally used with sensor (input) distribution boxes with LEDs. Each 12-pin Mini-Plus connector mates with a 12-conductor main patch cord that connects to the distribution box. On the field connector, various sensors (including photoelectric sensors and proximity sensors or other inputs) connect with a variety of connector styles. AC and DC versions of the PanelConnect module are available to meet the input (sensor) voltage requirements. Up to 16 inputs (sensors) can be connected to each PanelConnect module. Each PanelConnect Module has an LED to indicate when the module is powered. On the internal panel side, the PanelConnect mates with cables that connect to a PLC-input module. Cables are available to connect to the most popular Allen-Bradley PLC input modules. Modules are available in NEMA Type 4 or 4X versions.
|
16-Point Input PanelConnect Module with two 12-pin M23 Connectors
These modules are used with sensor (input) distribution boxes with or without LEDs. Each 12-pin M23 connector mates with a ten-, eleven-, or twelve-conductor main patch cord that connects to the distribution box. On the field connector side, various sensors (including photoelectric sensors and proximity sensors or other inputs) connect with a variety of connector styles. AC and DC versions of the PanelConnect module are available to meet the sensor voltage requirements. Up to 16 inputs (sensors) can be connected to each PanelConnect module. Each PanelConnect Module has an LED to indicate when the module is powered. On the internal panel side, the PanelConnect mates with a cable to connect to a PLC-input module. Cables are available to connect to the most popular Allen-Bradley PLC input modules. Modules are available in NEMA Type 4 or 4X versions.
|
32-Point Input PanelConnect Module with four 10-pin Mini-Plus Connectors
These modules are used with Connection systems without LEDs on the distribution box. Each 10-pin Mini-Plus connector mates with a ten-conductor main patch cord that connects to the distribution box. Additionally on the field connection side, various inputs (sensors) connect with a variety of connector styles. Up to 32 inputs can be connected to each PanelConnect module. Each PanelConnect Module has an LED to indicate when the module is powered. On the internal panel side, the PanelConnect mates with a cable to connect to a PLC-input module. Cables are available to connect to the most popular Allen-Bradley PLC input modules. Modules are available in NEMA Type 4 or 4X versions.
|
32-Point Input PanelConnect Module with four 12-pin Mini-Plus Connectors
These modules are used with Connection systems with LEDs on the distribution box. Each 12-pin Mini-Plus connector mates with a 12-conductor main patch cord that connects to the distribution box. Additionally on the field connection side, various inputs (sensors) connect with a variety of connector styles. Up to 32 inputs can be connected to each PanelConnect module. Each PanelConnect Module has an LED to indicate when the module is powered. On the internal panel side, the PanelConnect mates with a cable to connect to a PLC-input module. Cables are available to connect to the most popular Allen-Bradley PLC input modules. Modules are available in NEMA Type 4 or 4X versions.
|
Digital Pre-Wired Cables
Bulletin 1492 pre-wired cables are designed to minimize control wiring in a panel. Pre-wired cables, when used with a PanelConnect Module replace the point-to-point wiring between Allen-Bradley programmable controller I/O modules and individual terminal blocks. The pre-wired cables have a removable terminal block or wiring arm at the I/O end of the cable and a cable connector on the other end to connect to the PanelConnect Module. All of the pre-wired cables use #22 AWG wire and are 100% tested for continuity to make a perfect connection every time. The digital pre-wired cables are offered in four standard lengths of 0.5, 1.0, 2.5, and 5.0 m to fit a variety of applications. Other cable lengths are also available as build-to-order products. Pre-wired cables are available for many of the 1746 SLC I/O, 1756 ControlLogix, 1769 Compact for CompactLogix and MicroLogix 1500, and 1771 (PLC-5) Output Modules.
|
Ready-to-Wire Digital Cables
PanelConnect-ready cables have a cable connector that attaches to the PanelConnect Module, pre-wired to one end, and have free connectors ready to wire to other suppliers I/O modules or other components on the other end. PanelConnect ready cables use #22 AWG wire and have individual color-coded conductors for quick wire-to-terminal coordination. The digital PanelConnect-ready cables are offered in standard lengths of 1.0, 2.5, and 5.0 m to fit a variety of applications. Other cable lengths are also available as build-to-order products.
|
PanelConnect Fuse Module (optional)
The PanelConnect fuse module provides a convenient method of adding overcurrent protection to your PanelConnect inputs and outputs. This module has sixteen or thirty-two (16 or 32) 5x20 fuse holders to protect each individual input or output. The module has two 20-pin or 40-pin connectors with locking tabs. The right connector is used to connect to the back of the PanelConnect (in-panel connector). The left connector is used to connect to the Input or Output PLC module. The connection between the PanelConnect Module and the Fuse Module is done via the PanelConnect Option Module cable while connection to the PLC is done via PanelConnect pre-wired cables. This module is optional so OEMs can add fusing based on the needs of their customers.
|
Digital Option Module Cables
PanelConnect Option Module cable has two over molded cable connectors. The cables use #22 AWG wire and are 100% tested for continuity to make a perfect connection between the fuse module and PanelConnect module every time. These cables are offered in five standard lengths of 0.5, 1.0, 1.5, 2.5, and 5.5 meters to fit a variety of applications.
|
¬ PanelConnect 16- and 32-point Input...Digital Pre-Wired Cables
T PanelConnect 16- and 32-point Output…Table 1. AC Output Systems NEMA Type 4
Wiring Systems Cable
§ Main Patchcord (Mini-Plus)
§ Distribution Box
Ø Device Patchcords
z Sealing Caps
ª Inductive Proximity...See the Sensors Catalog
v Photoelectric Sensor…See the Sensors Catalog
ª Limit Switch…See the Sensors Catalog
|
Product Selection — Input Modules
Using Selection Tables to Make Valid Catalog Numbers
Configure the cable catalog number using 1492-CABLE¬ (for digital cables). See footnote ¬ on pages Table 1. AC Input Systems NEMA Type 4 and .
Table 1. AC Input Systems NEMA Type 4
| Catalog Number | ||||||||
| Allen-Bradley Distribution Box | 3-pin mini, no LED | 898N-38PS-N10 | — | — | — | |||
| 3-pin mini, LEDs | — | 898N-L38PS-N12 | — | — | ||||
| 3-pin AC micro, no LED | — | — | 898R-38PS-N10 | — | ||||
| 3-pin AC micro, LED | — | — | — | 898R-L38PS-N12 | ||||
| Allen-Bradley Device Patchcords | 889N-F3AFNU- F | 889R-F3AERM-§ | ||||||
| Allen-Bradley Main Patchcords | 10-pin Mini Plus | 12-pin Mini Plus | 10-pin Mini Plus | 12-pin Mini Plus | ||||
| 889N-F10ACNU-§ | 889N-F12ACNU-§ | 889N-F10ACNU-§ | 889N-F12ACNU-§ | |||||
| Allen-Bradley PanelConnect (16-input) | 1667-16IA1008 | 1667-16IA1207 | 1667-16IA1008 | 1667-16IA1207 | ||||
| System | ||||||||
| I/O System | Nominal System |
I/O Range | Frequency Module |
I/O Module | Cat. No. | Cat. No. | Cat. No. | Cat. No. |
| 1746 | 100/120V AC | 85…132V AC | 47…63 Hz | 1746-IA16 | 1492-CABLE¬ A | 1492-CABLE¬ A | 1492-CABLE¬ A | 1492-CABLE¬ A |
| 24V AC | 10…30V AC | 47…63 Hz | 1746-IN16 | 1492-CABLE¬ B | 1492-CABLE¬ B | 1492-CABLE¬ B | 1492-CABLE¬ B | |
| 1756 | 120V AC | 74…132V AC | 47…63 Hz | 1756-IA16 | 1492-CABLE¬ X | 1492-CABLE¬ X | 1492-CABLE¬ X | 1492-CABLE¬ X |
| 24V AC | 10…30V AC | 47…63 Hz | 1756-IN16 | 1492-CABLE¬ X | — | 1492-CABLE¬ X | — | |
| 1769 | 100/120V AC | 79…132V AC | 47…63 Hz | 1769-IA16 | 1492-CAB¬ A69 | 1492-CAB¬ A69 | 1492-CAB¬ A69 | 1492-CAB¬ A69 |
| 1771 | 120V AC | 70…138V AC | 50/60 Hz | 1771-IAD | 1492-CABLE¬ F | 1492-CABLE¬ F | 1492-CABLE¬ F | 1492-CABLE¬ F |
| 24V AC | 16…30V AC | 50/60 Hz | 1771-IND | 1492-CABLE¬ F | 1492-CABLE¬ F | 1492-CABLE¬ F | 1492-CABLE¬ F | |
| 1764 | 100/120V AC | 79…132V AC | 47…63 Hz | 1764-24AWA | 1492-CAB¬ A64 | 1492-CAB¬ A64 | 1492-CAB¬ A64 | 1492-CAB¬ A64 |
| 1794 | 100/120V AC | 85…132V AC | 47…63 Hz | 1794-IA16 | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P |
| Other AC PLC Input Modules | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | ||||
| ¬ PanelConnect to PLC I/O module cables are available in standard lengths of 0.5 m, 1.0 m, and 5.0 m. To order, insert the desired length code in the catalog number (005 = 0.5 m, 010 = 1.0 m, 0.25 = 2.5 m, and 050 = 5 m). Example: 1492-CABLE005B is for a 0.5 m cable for the 1746-IB16 I/O module. 1492-CABLE¬ P has minimum length of 1.0 m. | ||||||||
| Mini patchcords are available in standard lengths of 0.9 m, 1.8 m, 3.6 m, and 6 m (3 ft, 6 ft, 12 ft, and 20 ft). To order, insert the desired length in the catalog number. Example: 889NF3AFNU3F represents a mini 0.9 m (3 ft) patchcord. Note catalog number reflects straight male to straight female version with 16 AWG conductors, additional models are also available. |
||||||||
| § AC micro patchcords are available in standard lengths of 1 m, 2 m, 3 m, 5 m, and 10 m (3.3 ft, 6.5 ft, 9.8 ft, 16.4 ft and 32.8 ft). To order, insert the desired length in the catalog number. Example: 889RF3AERM3 represents an AC micro 3 m (9.8 ft) patchcord. Note catalog number reflects straight male to straight female version with 18 AWG conductors, additional models are also available. | ||||||||
| § Mini-Plus patchcords are available in standard lengths of 1 m, 2 m, 3 m, 5 m, and 10 m (3.3 ft, 6.5 ft, 9.8 ft, 16.4 ft and 32.8 ft). To order, insert the desired length in the catalog number. Example: 889NF12ACNU2 represents a 2 m (6.5 ft) patchcord. Note catalog number reflects straight male to straight female version with 18/22 AWG conductors, additional models are also available. | ||||||||
Table 2. DC Input Systems NEMA Type 4
| Catalog Number | ||||||||||
| Allen-Bradley Distribution Box | 5-pin DC micro, no LED | 898D-58PT-N12 | ||||||||
| 5-pin DC micro, PNP LED | — | — | 898D-P58PT-N12 | — | 898D-P58PT-N12 | — | ||||
| 5-pin DC micro, NPN LED | — | — | — | 898D-N58PT-N12 | — | — | ||||
| 4-pin mini, no LED | 898N-48PS-N10 | — | — | — | 898N-48PS-N10 | |||||
| Allen-Bradley Device Patchcords | 889B-F4AFNU- F | 889D-F4ACDM-§ | 889D-F4AFNU- F | |||||||
| Allen-Bradley Main Patchcords | 10-pin Mini Plus | 12-pin Mini Plus | 10-pin Mini Plus | |||||||
| 889N-F10ACNU-§ | 889N-F12ACNU-§ | 889N-F10ACNU-§ | ||||||||
| PanelConnect (16-input) | 1667-16ID1004 | 1667-16ID1001 | 1667-16ID1201 | 1667-16ID1212 | — | — | ||||
| PanelConnect (32-input) | — | — | — | — | 1667-32ID1201 | 1667-32ID1001 | ||||
| System | ||||||||||
| I/O System | Nominal System (DC) | I/O Range (DC) | Type Module | I/O Module | ||||||
| 1746 | 24V DC | 10…30V DC | Sink | 1746-IB16 | 1492-CABLE¬ B | — | 1492-CABLE¬ B | — | — | — |
| 48V DC | 30…60V DC | Sink | 1746-IC16 | 1492-CABLE¬ B | — | — | — | — | — | |
| 120V DC | 90…146V DC | Sink | 1746-IH16 | 1492-CABLE¬ B | — | — | — | — | — | |
| 24V DC | 10…30V DC | Sink | 1746-IN16 | 1492-CABLE¬ B | — | 1492-CABLE¬ B | — | — | — | |
| 24V DC | 10…30V DC | Sink | 1746-ITB16 | 1492-CABLE¬ B | — | 1492-CABLE¬ B | — | — | — | |
| 24V DC | 10…30V DC | Source | 1746-ITV16 | — | 1492-CABLE¬ B | — | 1492-CABLE¬ BT | — | — | |
| 24V DC | 10…30V DC | Source | 1746-IV16 | — | 1492-CABLE¬ B | — | 1492-CABLE¬ BT | — | — | |
| 24V DC | 30…60V DC | Sink | 1746-IB32 | — | — | — | — | 1492-CABLE¬ H | 1492-CABLE¬ H | |
| 1756 | 12/24V DC | 10…30V DC | Sink | 1756-IB16 | 1492-CABLE¬ X | — | 1492-CABLE¬ X | — | — | — |
| 48V DC | 30…60V DC | Sink | 1756-IC16 | 1492-CABLE¬ X | — | — | — | — | — | |
| 24V DC | 10…30V DC | Sink | 1756-IB32 | — | — | — | — | 1492-CABLE¬ Z | 1492-CABLE¬ Z | |
| 24V DC | 10…30V DC | Source | 1756-IV32 | — | — | — | — | — | — | |
| 1762 | 24V DC | 14…30V DC | Sink | 1762-L40BWA | — | — | — | — | 1492-CAB¬ A62 | 1492-CAB¬ A62 |
| 1762-L40BXB | — | — | — | — | ||||||
| 1764 | 24V DC | 14…30V DC | Sink | 1764-24BWA | 1492-CAB¬ A64 | 1492-CAB¬ A64 | 1492-CAB¬ A64 | — | — | — |
| 1764-28BXB | 1492-CAB¬ B64 | 1492-CAB¬ B64 | 1492-CAB¬ B64 | — | — | — | ||||
| 1769 | 24V DC | 10…30V DC | Sink | 1769-IQ16 | 1492-CAB¬ B69 | — | 1492-CAB¬ B69 | — | — | — |
| 1769-IQ16F | — | — | — | — | ||||||
| 24V DC | 10…30V DC | Source | 1769-IQ16 | — | 1492-CAB¬ B69 | — | 1492-CAB¬ B69 | — | — | |
| 1769-IQ16F | — | — | — | — | ||||||
| 24V DC | 10…30V DC | Sink | 1769-IQ32 | — | — | — | — | 1492-CAB¬ J69 | 1492-CAB¬ J69 | |
| 1771 | 125V DC | 70…138V DC | Sink | 1771-IAD | 1492-CABLE¬ F | — | — | — | — | — |
| 24V DC | 10…30V DC | Sink | 1771-IBD | 1492-CABLE¬ F | — | 1492-CABLE¬ F | — | — | — | |
| 48V DC | 20…60V DC | Sink | 1771-ICD | 1492-CABLE¬ F | — | 1492-CABLE¬ F | — | — | — | |
| 24V DC | 9…30V DC | Sink | 1771-IND | 1492-CABLE¬ F | — | 1492-CABLE¬ F | — | — | — | |
| 24V DC | 10…30V DC | Sink | 1771-IBN | — | — | — | — | 1492-CABLE¬ J | 1492-CABLE¬ J | |
| 1794 | 24V DC | 10…30V DC | Sink | 1794-IB16 | — | — | 1492-CABLE¬ Q | — | — | — |
| 48V DC | 20…60V DC | Sink | 1794-IC16 | — | — | 1492-CABLE¬ Q | — | — | — | |
| 24V DC | 10…30V AC | Sink | 1794-IB32 | — | — | — | — | 1492-CABLE¬ Q | 1492-CABLE¬ Q | |
| 24V DC | 10...30V DC | Source | 1794-IV32 | — | — | — | — | — | 1492-CABLE¬ Q | |
| Other DC PLC Input Modules | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ Q | 1492-CABLE¬ Q | ||||
| ¬ Cables are available in standard lengths of 0.5 m, 1.0 m, and 5.0 m (1.6 ft, 3.2 ft, 16.4 ft). To order, insert the desired length code in the catalog number (005 = 0.5 m, 010 = 1 m, 0.25 = 2.5 m 050 = 5 m). Example: 1492CABLE005B is a 0.5m cable. Note 1492CABLE¬ P has minimum length of 1 m. | ||||||||||
| Mini patchcords are available in standard lengths of 0.9 m, 1.8 m, 3.6 m, and 6 m (3 ft, 6 ft, 12 ft, and 20 ft). To order, insert the desired length in the catalog number. Example: 889NF4AFNU6F represents a mini 1.8 m (6 ft) patchcord. Note catalog number reflects straight male to straight female version with 16 AWG conductors, additional models are also available. |
||||||||||
| § DC micro patchcords are available in standard lengths of 1 m, 2 m, 3 m, 5 m, and 10 m (3.3 ft, 6.5 ft, 9.8 ft, 16.4 ft and 32.8 ft). To order, insert the desired length in the catalog number. Example: 889DF4ACDM3 represents an DC micro 3 m (9.8 ft) patchcord. Note catalog number reflects straight male to straight female version with 22 AWG conductors, additional models are also available.For use with outputs, 5-pin versions may be required for earth grounding on pin 5 depending on output field device. | ||||||||||
| § Mini-Plus patchcords are available in standard lengths of 1 m, 2 m, 3 m, 5 m, and 10 m (3.3 ft, 6.5 ft, 9.8 ft, 16.4 ft and 32.8 ft). To order, insert the desired length in the catalog number. Example: 889NF12ACNU2 represents a 2 m (6.5 ft) patchcord. Note catalog number reflects straight male to straight female version with 18/22 AWG conductors, additional models are also available. | ||||||||||
| Note: PNP type distribution boxes require sink type PLC inputs. NPN type require source inputs. | ||||||||||
Table 2. DC Input Systems NEMA Type 4, Continued
| Allen-Bradley Distribution Box LEDs | 5-pin DC micro, no LEDs | 889D-58PT-M12 | ||||
| 5-pin DC micro PNP, LEDs | 898D-P58PT-M12 | — | ||||
| Allen-Bradley Device Patchcord | 889D-F4ACDM-Ø | 889D-F4ACDM-Ø | ||||
| Allen-Bradley Main Patchcord | Metric 23 (12-pin) | |||||
| 889M-R11RMMU-Ø | ||||||
| PanelConnect (16-input) | 1667-16ID2206 | 1667-16ID2211 | ||||
| System | ||||||
| Input System | Nominal | Input Range | Type Module | Input Module | ||
| 1746 | 24V DC | 10…30V DC | Sink | 1746-IB16 | 1492-CABLE¬ B | — |
| 48V DC | 30…60V DC | Sink | 1746-IC16 | 1492-CABLE¬ B | — | |
| 120V DC | 90…146V DC | Sink | 1746-IH16 | — | — | |
| 24V DC | 10…30V DC | Sink | 1746-IN16 | 1492-CABLE¬ B | — | |
| 24V DC | 10…30V DC | Sink | 1746-ITB16 | 1492-CABLE¬ B | — | |
| 24V DC | 10…30V DC | Source | 1746-ITV16 | — | 1492-CABLE¬ B | |
| 24V DC | 10…30V DC | Source | 1746-IV16 | — | 1492-CABLE¬ B | |
| 24V DC | 10…30V DC | Source | 1746-IB32 | — | — | |
| 24V DC | 10…30V DC | Source | 1746-IBN | — | — | |
| 1756 | 12/24V DC | 10…30V DC | Sink | 1756-IB16 | 1492-CABLE¬ X | — |
| 48V DC | 30…60V DC | Sink | 1756-IC16 | 1492-CABLE¬ X | — | |
| 24V DC | 10…30V DC | Source | 1756-IB32 | — | — | |
| 1764 | 24V DC | 14…30V DC | Sink | 1764-24BWA | 1492-CAB¬ A64 | 1492-CAB¬ A64 |
| 1764-28BXB | 1492-CAB¬ B64 | 1492-CAB¬ B64 | ||||
| 1769 | 24V DC | 10…30V DC | Sink | 1769-IQ16 | 1492-CAB¬ B69 | — |
| 24V DC | 10…30V DC | Source | 1769-IQ16 | — | 1492-CAB¬ B69 | |
| 1771 | 125V DC | 70…138V DC | Sink | 1771-IAD | — | — |
| 24V DC | 10…30V DC | Sink | 1771-IBD | 1492-CABLE¬ F | — | |
| 48V DC | 20…60V DC | Sink | 1771-ICD | 1492-CABLE¬ F | — | |
| 24V DC | 9…30V DC | Sink | 1771-IND | 1492-CABLE¬ F | — | |
| Other DC PLC Intput Modules | 1492-CABLE¬ P | 1492-CABLE¬ P | ||||
| ¬ Panel Connect to PLC I/O module cables are available in standard lengths of 0.5 m, 1.0 m, and 5.0 m. To order, insert the desired length code in the catalog number (005 = 0.5 m, 010 = 1.0 m, 0.25 = 2.5 m, and 050 = 5 m). Example: 1492-CABLE005B is for a 0.5 m cable for the 1746-IB16 I/O module. 1492-CABLE¬ P has minimum length of 1.0 m. | ||||||
| Refer to the PLC module installation manual for details. | ||||||
| § DC micro patchcords are available in standard lengths of 1 m, 2 m, 3 m, 5 m, and 10 m (3.3 ft, 6.5 ft, 9.8 ft, 16.4 ft and 32.8 ft). To order, insert the desired length in the catalog number. Example: 889DF4ACDM3 represents an DC micro 3 m (9.8 ft) patchcord. Note catalog number reflects straight male to straight female version with 22 AWG conductors, additional models are also available.For use with outputs, 5-pin versions may be required for earth grounding on pin 5 depending on output field device. | ||||||
| Ø Replace with length of cable in meters (1 m, 2 m, 3 m, 5 m, or 10 m standard). | ||||||
| Note: PNP type distribution boxes require sink type PLC inputs. NPN type require source inputs. | ||||||
The same information for PanelConnect NEMA Type 4 applies to PanelConnect NEMA Type 4X products as shown in Tables 1 and 2 for Cables and Distribution Boxes.
Table 3. NEMA Type 4 and 4X Input Systems
| NEMA 4X Module | NEMA 4 Module |
| 1667-16IA1008X | 1667-16IA1008 |
| 1667-16IA1207X | 1667-16IA1207 |
| — | — |
| ¬ | 1667-16ID1001 |
| 1667-16ID1004X | 1667-16ID1004 |
| 1667-16ID1201X | 1667-16ID1201 |
| ¬ | 1667-16ID1212 |
| — | — |
| ¬ | 1667-16ID2206 |
| ¬ | 1667-16ID2211 |
| — | — |
| ¬ | 1667-32ID1201 |
| ¬ | 1667-32ID1001 |
| ¬ Contact factory for availability | |
PanelConnect™ Specifications
For all PanelConnect dimensions, refer to 16-Point PanelConnect Input or Output Module Dimensions.
For general marker card information, refer to page Marker Cards.
For general adhesive label card information, refer to page Adhesive Label Cards for 16-Point Input PanelConnect Modules.
Refer to the online documentation for new product information.
|
16-Point Input PanelConnect Module with two 10- or 12-pin Mini-Plus Connectors or two 12-pin M23 Connectors
| Mini-Plus 12-pin, 1-1/8 in. |
Mini-Plus 10-pin, 1-1/8 in. |
M23 12-pin, 23 mm |
| Cat. Nos. | Cat. Nos. | Cat. Nos. |
| 1667-16IA1207 | 1667-16IA1008 | 1667-16ID2206 |
| 1667-16ID1201 | 1667-16ID1001 | 1667-16ID2211 |
| 1667-16ID1212 | 1667-16ID1004 |
|
|
32-Point Input PanelConnect Module with four 10- or 12-pin Mini-Plus Connectors
| Mini-Plus 12-pin, 1-1/8 in. |
Mini-Plus 10-pin, 1-1/8 in. |
|
| Cat. Nos. | Cat. Nos. | |
| 1667-32ID1201 | 1667-32ID1001 |
Modules for 16-Point Inputs
|
|
Features:
Specifications
| Cat. No. | 1667-161A1008 | 1667-16ID1001 | 1667-16ID1004 | 1667-16IA1207 | 1667-16ID1201 | 1667-16ID1212 | 1667-16ID2206 | 1667-16ID2211 |
| Field Connector: Number of Pins and Style | 10-Pin Mini Plus (1-1/8 in.) | 12-Pin Mini Plus (1-1/8 in.) |
12-Pin M23 Metric 23 mm | |||||
| Voltage Rating | 10-265V AC | 10-265V DC | 10-265V DC | 10-265V AC | 10-265V DC | 10-265V DC | 10-265V DC | 10-265V DC |
| Module Type | 16 Input | |||||||
| Degree of Protection | IP65; Type 1, 4, 4X, 12 | |||||||
| Maximum Peak Voltage¬ | 600Vp | |||||||
| Maximum Current (per Circuit) | 2 A | |||||||
| Maximum Current (per Module) | 12 A | |||||||
| Indicator Circuit Current (Nominal) | 2 mA | |||||||
| No. of Terminals per Device Common | 2 | |||||||
| Operating Temperate Range | 0°C…+60°C (32°F…+140°F) Noncondensing | |||||||
| Certifications | cULus Listed (File E113724 Guide NRAQ) CE |
|||||||
| Power Supply Connector Specification | ||||||||
| Wire Range (Rated Cross Section) | #22…#12 AWG (0.2…4 mm2) |
|||||||
| Wire Strip Length | 8 mm (0.32 in.) | |||||||
| Recommended Tightening Torque | 0.50…0.60 Nm (4.5…5.5 lb-in.) |
|||||||
¬ Transient voltage greater than 600Vp use a UL Recognized suprpression device rated at 2.5kV withstand.
Application Notes
1. Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.
3. Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.
Distribution Block Connection
Match I/O Program to Distribution Block Outputs in the sequence shown below:
|
PanelConnect Pin to Field-Side Connections
1. Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.
3. Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.
Modules for 32-Point Inputs
|
|
Features:
Specifications
| Catalog Number | 1667-32ID1001 | 1667-32ID1201 | |
| Field Connector: No. pins Style | 10-Pin Mini Plus (1-1/8 in.) | 12-Pin Mini Plus (1-1/8 in.) | |
| Voltage Rating | 10-30V DC | ||
| Module Type | 32 Input | ||
| Degree of Protection | IP65; Type 1, 4, 4X, 12 | ||
| Maximum Peak Voltage¬ | 600Vp | ||
| Maximum Current (per Circuit) | 2 A | ||
| Maximum Current (per Module) | 12 A | ||
| Indicator Circuit Current (Nominal) | 2 mA | ||
| No. of Terminals per Device Common | 2 | ||
| Operating Temperature Range | 0°C…+60°C (32°F…140°F) Noncondensing | ||
| Certifications | |||
| Power Supply Conector Specification | |||
| Wire Range (Rated Cross Section) | #22...#12 AWG (0.2...4 mm2) | ||
| Wire Strip Length | 0.32 in. (8 mm) | ||
| Recommended Tightening Torque | 4.5...5.5lb.-in. (0.50...0.60 Nm) | ||
| ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5kV withstand. | |||
Application Notes
Distribution Block Connection
Match I/O Program to Distribution Block Outputs in the sequence shown below:
|
1. Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.
3. Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.
Pre-Wired Cables for Input PanelConnect
Bulletin 1492 pre-wired cables are designed to minimize control wiring in a panel. These pre-wired cables replace the point-to-point wiring between Allen-Bradley programmable controller I/O modules and the PanelConnect module.
Specifications
|
The pre-wired cables have a Bulletin 1746, 1756, 1762 (MicroLogix 1200, 40 I/O Base), 1764 (MicroLogix), 1769, or 1771 PLC input module on one end and a molded cable connector on the other to connect to the PanelConnect Module. The broad offering of digital pre-wired cables supports 16-point and 32-point Bulletin 1746, 1756, 1762, 1764, 1769, and 1771 digital input modules.
| Pre-Wired Cable Cat. No. |
Standard Cable Lengths | Insulation Rating | No. of Conductors | Conductor Size | Nominal Outer Diameter | I/O Module Connector Cat. No. |
| 1492-CABLE¬ A | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1746-RT25R Red Removable Terminal Block |
| 1492-CABLE¬ B | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1746-RT25B Blue Removable Terminal Block |
| 1492-CABLE¬ F | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1771-WH (16-Point/21 Terminal) Wiring Arm |
| 1492-CABLE¬ X | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1756-TBNH Removable Terminal Block |
| 1492-CAB¬ A69 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1769-RTBN18 Removable Terminal Block |
| 1492-CAB¬ B69 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1769-RTBN18 Removable Terminal Block |
| 1492-CAB¬ J69 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 11.1 mm (0.46 in.) | (2) 1769-RTBN18 Removable Terminal Blocks |
| 1492-CABLE¬ H | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 11.7 mm (0.46 in.) | 1746-N3 40-Pin Cable Connector |
| 1492-CABLE¬ J | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 11.7 mm (0.46 in.) | 1746-WN (32-point/40 Terminal) Wiring Arm |
| 1492-CABLE¬ Z | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 11.7 mm (0.46 in.) | 1746-TBCH Removable Terminal Block |
| 1492-CABLE¬ X | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | #20 AWG | 9.0 mm (0.36 in.) | 1756-TBNH Removable Terminal Block | |
| 1492-CAB¬ A62 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 11.7 mm (0.46 in.) | 1762-L40xxx Input Terminal |
| 1492-CAB¬ A64 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 9.0 mm (0.36 in.) | 1764-24AWA, -24BWA Input Terminal |
| 1492-CAB¬ B64 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 9.0 mm (0.36 in.) | 1764-28BXB Input Terminal |
| ¬ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the cat. no. (005 = 0.5 m, 010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Cat. No. 1492-CABLE005A is for a 0.5 m cable for the 1746-IA16 I/O Module. Also refer to Build-to-Order Length Cables, on [BAD REF 203006 ]. | ||||||
Pinouts
Digital Pre-Wired Cables
The following diagrams illustrate how the individual conductors in the digital pre-wired cables are terminated at both ends. The description listed first is the wire color of the conductor connected to the removable terminal block (Bulletin 1746, 1756, and 1769 I/O) or wiring arm (1771 I/O). The number that follows in parentheses is the corresponding -pin number of the PanelConnect™ mating connect
|
I/O pin Connector Definition
|
PanelConnect Mating Connector
PanelConnect Digital, Module-Ready Cable Specifications
PanelConnect Module-Ready Cable Specifications
|
PanelConnect ready cables have a cable connector on one end to attach to the PanelConnect Module plus 20 and 40 individually colored conductors on the other end (Cat. Nos. CABLE¬ P and CABLE¬ Q respectively). These cables allow the PanelConnect Module to be used in specialty applications that require a custom connection, such as connection to other than Allen-Bradley PLCs.
| Module-Ready Cable Cat. No. |
Cable Lengths | Insulation Rating | Number of Conductors | Conductor Size | Nominal Outer Diameter | Current/ Conductor |
| 1492-CABLE¬ P | 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36") | 2 A |
Each colored conductor is connected to one pin of the molded cable connector as listed in the tables below.
| Connector -pin Number | Wire Color Base/Stripe | Connector pin Number | Wire Color Base/Stripe |
| 1 | Black | 11 | Blue/Black |
| 2 | White | 12 | Black/White |
| 3 | Red | 13 | Red/White |
| 4 | Green | 14 | Green/White |
| 5 | Orange | 15 | Blue/White |
| 6 | Blue | 16 | Black/Red |
| 7 | White/Black | 17 | White/Red |
| 8 | Red/Black | 18 | Orange/Red |
| 9 | Green/Black | 19 | Blue/Red |
| 10 | Orange/Black | 20 | Red/Green |
|
| Cat. No. | Cable Lengths | Insulation Rating | Number of Conductors | Conductor Size | Nominal Outer Diameter | Current/ Conductor |
| 1492-CABLE¬ Q | 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 11.7 mm (0.46") | 2 A |
| Connector -pin Number | Wire Color Base/Stripe | Connector pin Number | Wire Color Base/Stripe |
| 1 | Black | 21 | Orange/Green |
| 2 | White | 22 | Black/White/Red |
| 3 | Red | 23 | White/Black/Red |
| 4 | Green | 24 | Red/Black/White |
| 5 | Orange | 25 | Green/Black/White |
| 6 | Blue | 26 | Orange/Black/White |
| 7 | White/Black | 27 | Blue/Black/White |
| 8 | Red/Black | 28 | Black/Red/Green |
| 9 | Green/Black | 29 | White/Red/Green |
| 10 | Orange/Black | 30 | Red/Black/Green |
| 11 | Blue/Black | 31 | Green/Black/Orange |
| 12 | Black/White | 32 | Orange/Black/Green |
| 13 | Red/White | 33 | Blue/White/Orange |
| 14 | Green/White | 34 | Black/White/Orange |
| 15 | Blue/White | 35 | White/Red/Orange |
| 16 | Black/Red | 36 | Orange/White/Blue |
| 17 | White/Red | 37 | White/Red/Blue |
| 18 | Orange/Red | 38 | Black/White/Green |
| 19 | Blue/Red | 39 | White/Black/Green |
| 20 | Red/Green | 40 | Red/White/Green |
|
¬ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the desired cable length into the cat. no. (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Cat. No. 1492-CABLE025P is for a 2.5 m, 20 conductor PanelConnect ready cable.
|
PanelConnect Output Features and Typical Configuration
PanelConnect Output Features
|
16-Point Output PanelConnect Module with two 12-pin Mini-Plus Connectors
These modules are normally used with Connection systems with LEDs on the distribution box or directly to some pneumatic valve manifolds. Each 12-pin Mini-Plus connector mates with a 12-conductor main patch cord that connects to the distribution box or pneumatic valve manifold. Additionally on the field connection side, various outputs (including pneumatic valves) connect with a variety of connector styles. AC and DC versions of the PanelConnect module are available to meet the output voltage requirements. Up to 16 outputs can be connected to each PanelConnect module. Each PanelConnect Module has an LED to indicate when the module is powered. On the internal panel side, the PanelConnect mates with a cable to connect to a PLC-output module. Cables are available to connect to the most popular Allen-Bradley PLC output modules. Modules are available in NEMA Type 4 or 4X versions.
|
16-Point Output PanelConnect Module with two 12-pin M23 Connectors
These modules are used with Connection systems with or without LEDs on the distribution box or directly to some pneumatic valve manifolds. Each 12-pin M23 connector mates with a ten, eleven, or twelve conductor main patch cord that connects to the distribution box or pneumatic valve manifold. Additionally on the field connection side, various outputs (including pneumatic valves) connect with a variety of connector styles. AC and DC versions of the PanelConnect module are available to meet the output voltage requirements. Up to 16 outputs can be connected to each PanelConnect module. Each PanelConnect Module has an LED to indicate when the module is powered. On the internal panel side, the PanelConnect mates with a cable to connect to a PLC-output module. Cables are available to connect to the most popular Allen-Bradley PLC output modules. Modules are available in NEMA Type 4 or 4X versions.
|
32-Point Output PanelConnect Module with four 12-pin Mini-Plus Connectors
These modules are used with Connection systems with LEDs on the distribution box or directly to some pneumatic valve manifolds. Each 12-pin Mini-Plus connector mates with a twelve conductor main patch cord that connects to the distribution box. Additionally on the field connection side, various outputs (including pneumatic valves) connect with a variety of connector styles. 24V DC versions of the PanelConnect module are available to meet the output voltage requirements. Up to 32 outputs can be connected to each PanelConnect module. Each PanelConnect Module has an LED to indicate when the module is powered. On the internal panel side, the PanelConnect mates with a cable to connect to a PLC-output module. Cables are available to connect to the most popular Allen-Bradley PLC output modules. Modules are available in NEMA Type 4 or 4X versions.
|
Digital Pre-Wired Cables
Bulletin 1492 pre-wired cables are designed to minimize control wiring in a panel. Pre-wired cables, when used with a PanelConnect Module replaces the point-to-point wiring between Allen-Bradley programmable controller I/O modules and individual terminal blocks. The pre-wired cables have a removable terminal block or wiring arm at the I/O end of the cable and a cable connector on the other end to connect to the PanelConnect Module. All of the pre-wired cables use #22 AWG wire and are 100% tested for continuity to make a perfect connection every time. The digital pre-wired cables are offered in four standard lengths of 0.5, 1.0, 2.5, and 5.0 m to fit a variety of applications. Other cable lengths are also available as build-to-order products. Pre-wired cables are available for many of the 1746 SLC I/O, 1756 ControlLogix, 1769 Compact for CompactLogix and MicroLogix 1500, and 1771 (PLC-5) Output Modules.
|
Ready-to-Wire Digital Cables
PanelConnect-ready cables have a cable connector that attaches to the PanelConnect Module, pre-wired to one end, and have free connectors ready to wire to other suppliers I/O modules or other components on the other end. PanelConnect ready cables use #22 AWG wire and have individual color-coded conductors for quick wire-to-terminal coordination. The digital PanelConnect-ready cables are offered in standard lengths of 1.0, 2.5, and 5.0 m to fit a variety of applications. Other cable lengths are also available as build-to-order products.
|
PanelConnect Fuse Module (optional)
The PanelConnect fuse module provides a convenient method of adding overcurrent protection to your PanelConnect inputs and outputs. This module has sixteen or thirty-two (16 or 32) 5x20 fuse holders to protect each individual input or output. The module has two 20-pin or 40-pin connectors with locking tabs. The right connector is used to connect to the back of the PanelConnect (in-panel connector). The left connector is used to connect to the Input or Output PLC module. The connection between the PanelConnect Module and the Fuse Module is done via the PanelConnect Option Module cable while connection to the PLC is done via PanelConnect pre-wired cables. This module is optional so OEMs can add fusing based on the needs of their customers.
|
Digital Option Module Cables
PanelConnect Option Module cable has two over molded cable connectors. The cables use #22 AWG wire and are 100% tested for continuity to make a perfect connection betwen the fuse module and PanelConnect module every time. These cables are offered in five standard lengths of 0.5, 1.0, 1.5, 2.5, and 5.5 meters to fit a variety of applications.
|
|
|
|
Typical Configuration
|
Product Selection — Output Modules
Using Selection Tables to Make Valid Catalog Numbers
Configure the cable catalog number using 1492-CABLE¬ (for digital cables). See footnote ¬ on pages Table 1. AC Output Systems NEMA Type 4 and .
Table 1. AC Output Systems NEMA Type 4
| Catalog Number | ||||||||||
| Distribution Box | 3-pin mini, LED | 898N-L38PS-N12 | — | — | — | |||||
| 3-pin AC micro, LED | — | — | — | 898R-L38PS-N12 | ||||||
| Device Patchcords | 889N-F3AFNU- F | 889R-F3AERM-§ | ||||||||
| Main Patchcords | 12-pin Mini Plus | |||||||||
| 889N-F12ACNU-§ | ||||||||||
| PanelConnect (16-output) | 1667-16OA1201 | 1667-16OA1202 | 1667-16OA1203 | 1667-16OA1201 | 1667-16OA1202 | 1667-16OA1203 | ||||
| System | ||||||||||
| I/O System | Nominal (AC) | I/O Range (AC)T | Type Module | I/O Module | ||||||
| 1746 | 120/240V AC | 85…265V AC | Source | 1746-OA16 | 1492-CABLE¬ C | — | — | 1492-CABLE¬ C | — | — |
| 120/240V AC | 85…265V AC | Source | 1746-OW16 | 1492-CABLE¬ D | — | — | 1492-CABLE¬ D | — | — | |
| 1762§ Ø | 120/240V AC | 5…264V AC | Source | 1762-L40AWA | 1492-CAB¬ C62 | 1492-CAB¬ C62 | — | 1492-CAB¬ C62 | 1492-CAB¬ C62 | — |
| 120/240V AC | 5…264V AC | Source | 1762-L40BWA | 1492-CAB¬ C62 | 1492-CAB¬ C62 | — | 1492-CAB¬ C62 | 1492-CAB¬ C62 | — | |
| 1764 Ø | 120/240V AC | 5…264V AC | Source | 1764-24AWA | 1492-CAB¬ D64 | 1492-CAB¬ D64 | — | 1492-CAB¬ D64 | 1492-CAB¬ D64 | — |
| 120/240V AC | 5…264V AC | Source | 1764-24BWA | 1492-CAB¬ D64 | 1492-CAB¬ D64 | — | 1492-CAB¬ D64 | 1492-CAB¬ D64 | — | |
| 1769 | 120/240V AC | 85…265V AC | Source | 1769-OW16 | 1492-CAB¬ H69 | — | — | 1492-CAB¬ H69 | — | — |
| 120/240V AC | 85…265V AC | Source | 1769-OA16 | 1492-CAB¬ H69 | — | — | 1492-CAB¬ H69 | — | — | |
| 1756 | 120/240V AC | 74…265V AC | Source | 1756-OA16 | — | 1492-CABLE¬ X | — | — | 1492-CABLE¬ X | — |
| 1771 | 120V AC | 12…138V AC | Source | 1771-OAD | — | — | 1492-CABLE¬ F | — | — | 1492-CABLE¬ F |
| 48V AC | 10…60V AC | Source | 1771-OND | — | — | 1492-CABLE¬ F | — | — | 1492-CABLE¬ F | |
| 1794 | 100/120V AC | 85…132V AC | Source | 1794-OA16 | 1492-CABLE¬ P | 1492-CABLE¬ P | — | 1492-CABLE¬ P | 1492-CABLE¬ P | — |
| Other AC PLC Output Modules | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | ||||
| ¬ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the cat. no. (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Cat. No. 1492-CABLE005B is for a 0.5 m cable. Note 1492-CABLE¬ P has a minimum length of 1 m. | ||||||||||
| T Refer to the PLC Installation Manual for details. | ||||||||||
| Mini patchcords are available in standard lengths of 0.9 m, 1.8 m, 3.6 m, and 6 m (3 ft, 6 ft, 12 ft, and 20 ft). To order, insert the desired length in the catalog number. Example: 889NF3AFNU3F represents a mini 0.9 m (3 ft) patchcord. Note catalog number reflects straight male to straight female version with 16 AWG conductors, additional models are also available. |
||||||||||
| § AC micro patchcords are available in standard lengths of 1 m, 2 m, 3 m, 5 m, and 10 m (3.3 ft, 6.5 ft, 9.8 ft, 16.4 ft and 32.8 ft). To order, insert the desired length in the catalog number. Example: 889RF3AERM3 represents an AC micro 3 m (9.8 ft) patchcord. Note catalog number reflects straight male to straight female version with 18 AWG conductors, additional models are also available. | ||||||||||
| § Mini-Plus patchcords are available in standard lengths of 1 m, 2 m, 3 m, 5 m, and 10 m (3.3 ft, 6.5 ft, 9.8 ft, 16.4 ft and 32.8 ft). To order, insert the desired length in the catalog number. Example: 889NF12ACNU2 represents a 2 m (6.5 ft) patchcord. Note catalog number reflects straight male to straight female version with 18/22 AWG conductors, additional models are also available. | ||||||||||
| Ø Refer to Bulletin 1762 and Bulletin 1764 Output Ratings, Table X on 1667-32OD1201 Specifications. | ||||||||||
Table 2. DC Output Systems NEMA Type 4
| Catalog Number | ||||||||||
| Distribution Box | 5-pin DC micro, no LEDs (2 output per connector) | 898D-54DT-N12 | ||||||||
| 5-pin DC micro, no LEDs | 898D-58PT-N12 | |||||||||
| 5-pin DC micro, PNP LEDs | 898D-P58PT-N12 | — | 898D-P58PT-N12 | — | ||||||
| 5-pin DC micro, NPN LEDs | — | 898D-N58PT-N12 | — | — | — | 898D-N58PT-N12 | ||||
| Device Patchcords | 889D-F4ACDM- | |||||||||
| Main Patchcords | 12-pin MIni Plus | |||||||||
| 889N-F12ACNU-§ | ||||||||||
| PanelConnect (16-outputs) | 1667-16OD1201 | 1667-16OD1202 | 1667-16OD1203 | — | — | |||||
| PanelConnect (32-outputs) | — | — | — | — | 1667-32OD1201 | |||||
| System | ||||||||||
| I/O Systems | Nominal (DC) | I/O Range (DC)T | Type Module | I/O Module | ||||||
| 1746 | 24V DC | 10…50V DC | Sourcing | 1746-OB16 | 1492-CABLE¬ E | — | — | — | — | — |
| 24V DC | 10…50V DC | Sourcing | 1746-OB16E | 1492-CABLE¬ E | — | — | — | — | — | |
| 24V DC | 20.4…26.4V DC | Sourcing | 1746-OB16P | 1492-CABLE¬ E | — | — | — | — | — | |
| 24V DC | 10…50V DC | Sinking | 1746-OV16 | — | 1492-CABLE¬ E | — | — | — | — | |
| 24V DC | 20.4…26.4V DC | Sinking | 1746-OV16P | — | 1492-CABLE¬ E | — | — | — | — | |
| 24V DC | 5-125V DC | Sourcing | 1746-OW16 | — | — | — | — | — | — | |
| 24V DC | 10…50V DC | Sourcing | 1746-OB32 | — | — | — | — | 1492-CABLE¬ H | — | |
| 24V DC | 10…30V DC | Sourcing | 1746-OB32E | — | — | — | — | 1492-CABLE¬ H | — | |
| 24V DC | 10…50V DC | Sinking | 1746-OV32 | — | — | — | — | — | 1492-CABLE¬ H | |
| 1756 | 24V DC | 10…31.2V DC | Sourcing | 1756-OB16E | — | — | 1492-CABLE¬ X | — | — | — |
| 24V DC | 10…31.2V DC | Sourcing | 1756-OB32 | — | — | — | — | 1492-CABLE¬ Z | — | |
| 24V DC | 10…31.2V DC | Sinking | 1756-OV32E | — | — | — | — | — | 1492-CABLE¬ Z | |
| 1762§ § | 24V DC | 5…125V DC | Sourcing | 1762-L40AWA | 1492-CAB¬ C62 | — | — | — | — | — |
| 24V DC | 21.6…27.6V DC | Sourcing | 1762-L40BWA | 1492-CAB¬ C62 | — | — | — | — | — | |
| 24V DC | 5…125V DC | Sourcing | 1762-L40BXB | 1492-CAB¬ D62 | — | — | — | — | — | |
| 1764 § | 24V DC | 5…125V DC | Sourcing | 1764-24AWA | 1492-CAB¬ D64 | — | — | — | — | — |
| 24V DC | 20.4…26.4V DC | Sourcing | 1764-24BWA | 1492-CAB¬ D64 | — | — | — | — | — | |
| 24V DC | 5…125V DC | Sourcing | 1764-28BXB | 1492-CAB¬ E64 | — | — | — | — | — | |
| 1769 | 24V DC | 20.4…26.4V DC | Sourcing | 1769-OB16 | 1492-CAB¬ E69 | — | — | — | — | — |
| 24V DC | 20.4…26.4V DC | Sinking | 1769-OV16 | — | 1492-CAB¬ E69 | — | — | — | — | |
| 24V DC | 5-125V DC | Sourcing | 1769-OW16 | 1492-CAB¬ H69 | — | — | — | — | — | |
| 24V DC | 20.4…26.4V DC | Sourcing | 1769-OB32 | — | — | — | — | 1492-CAB¬ K69 | — | |
| 1771 | 24V DC | 10…50V DC | Sourcing | 1771-OBD | — | — | — | 1492-CABLE¬ F | — | — |
| 24V DC | 10…50V DC | Sourcing | 1771-OND | — | — | — | — | — | — | |
| 24V DC | 10…50V DC | Sourcing | 1771-OBN | — | — | — | — | 1492-CABLE¬ L | — | |
| 24V DC | 10…50V DC | Sinking | 1771-OVN | — | — | — | — | — | 1492-CABLE¬ L | |
| 1794 | 24V DC | 10…50V DC | Sourcing | 1794-OB16 | 1492-CABLE¬ P | — | — | — | — | — |
| 24V DC | 10…50V DC | Sourcing | 1794-OB32 | — | — | — | — | 1492-CABLE¬ Q | — | |
| Other 16 Point DC PLC Output Modules | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | — | — | ||||
| Other 32 Point DC PLC Output Modules | — | — | — | — | 1492-CABLE¬ Q | — | ||||
| ¬ Cables are available in standard lengths of 0.5 m, 1.0 m, and 5.0 m (1.6 ft, 3.2 ft, 16.4 ft). To order, insert the desired length code in the catalog number (005 = 0.5 m, 010 = 1 m, 0.25 = 2.5 m 050 = 5 m). Example: 1492CABLE005B is for a 0.5 m cable. Note 1492CABLE¬ P as minimum length of 1 m. | ||||||||||
| T Refer to the PLC Installation Manual for details. | ||||||||||
| DC micro patchcords are available in standard lengths of 1 m, 2 m, 3 m, 5 m, and 10 m (3.3 ft, 6.5 ft, 9.8 ft, 16.4 ft and 32.8 ft). To order, insert the desired length in the catalog number. Example: 889DF4ACDM3 represents an DC micro 3 m (9.8 ft) patchcord. Note catalog number reflects straight male to straight female version with 22 AWG conductors, additional models are also available.For use with outputs, 5-pin versions may be required for earth grounding on pin 5 depending on output field device. | ||||||||||
| § Mini-Plus patchcords are available in standard lengths of 1 m, 2 m, 3 m, 5 m, and 10 m (3.3 ft, 6.5 ft, 9.8 ft, 16.4 ft and 32.8 ft). To order, insert the desired length in the catalog number. Example: 889NF12ACNU2 represents a 2 m (6.5 ft) patchcord. Note catalog number reflects straight male to straight female version with 18/22 AWG conductors, additional models are also available. | ||||||||||
| § Refer to Bulletin 1762 and Bulletin 1764 Output ratings, Table X on 1667-32OD1201 Specifications. | ||||||||||
| Note: PNP type distribution boxes require source type PLC outputs, NPN require sink outputs. | ||||||||||
Table 2. DC Output Systems NEMA Type 4, Continued
| Either with or without LEDs | |||||||
| Allen-Bradley Distribution Box | 5-pin DC micro, no LEDs | 898D-58PT-M12 | |||||
| 5-pin DC micro, PNP LEDs | 898D-P58PT-M12 | — | 898D-P58PT-M12 | ||||
| Allen-Bradley Device Patchcord | 889D-F4ACDM-§ | — | 889D-F4ACDM-§ | ||||
| Allen-Bradley Main Patchcord 12-pin Metric 23 |
889M-R11RMMU-§ | ||||||
| PanelConnect (16 output) | 1667-16OD2201 | 1667-16OD2202 | |||||
| System | |||||||
| Output Systems | Nominal | Output RangeT | @ Module | Output Module | — | — | — |
| 1746 | 24V DC | 10…50V DC | Sourcing | 1746-OB16 | 1492-CABLE¬ E | — | — |
| 24V DC | 10…30V DC | Sourcing | 1746-OB16E | 1492-CABLE¬ E | — | — | |
| 24V DC | 20.4…26.4V DC | Sourcing | 1746-OB16P | 1492-CABLE¬ E | — | — | |
| 24V DC | 10…50V DC | Sinking | 1746-OV16 | — | 1492-CABLE¬ E | — | |
| 24V DC | 20.4…26.4V DC | Sinking | 1746-OV16P | — | 1492-CABLE¬ E | — | |
| 24V DC | 5-125V DC | Sourcing | 1746-OW16 | 1492-CABLE¬ D | — | — | |
| 24V DC | 10…50V DC | Sourcing | 1746-OB32 | — | — | — | |
| 24V DC | 10…30V DC | Sourcing | 1746-OB32E | — | — | — | |
| 24V DC | 10…50V DC | Sinking | 1746-OV32 | — | — | — | |
| 1756 | 24V DC | 10…31.2V DC | Sourcing | 1756-OB16E | — | — | 1492-CABLE¬ X |
| 24V DC | 10…31.2V DC | Sourcing | 1756-OB32 | — | — | — | |
| 1762§ | 24V DC | 5…125V DC | Sourcing | 1762-L40AWA | 1492-CAB¬ C62 | — | — |
| 24V DC | 21.6…27.6V DC | Sourcing | 1762-L40BWA | 1492-CAB¬ C62 | — | — | |
| 24V DC | 5…125V DC | Sourcing | 1762-L40BXB | 1492-CAB¬ D62 | — | — | |
| 1764 | 24V DC | 5…125V DC | Sourcing | 1764-24AWA | 1492-CAB¬ D64 | — | — |
| 24V DC | 20.4…26.4V DC | Sourcing | 1764-24BWA | 1492-CAB¬ D64 | — | — | |
| 24V DC | 5…125V DC | Sourcing | 1764-28BXB | 1492-CAB¬ E64 | — | — | |
| 1769 | 24V DC | 20.4…26.4V DC | Sourcing | 1769-OB16 | 1492-CAB¬ E69 | — | — |
| 24V DC | 20.4…26.4V DC | Sinking | 1769-OV16 | — | 1492-CAB¬ E69 | — | |
| 24V DC | 5…125V DC | Sourcing | 1769-OW16 | 1492-CAB¬ H69 | — | — | |
| 1771 | 24V DC | 10…50V DC | Sourcing | 1771-OBD | — | — | — |
| 24V DC | 10…50V DC | Sourcing | 1771-OND | — | — | — | |
| 24V DC | 10…50V DC | Sourcing | 1771-OBN | — | — | — | |
| 24V DC | 10…50V DC | Sinking | 1771-OVN | — | — | — | |
| 1794 | 24V DC | 10…50V DC | Sourcing | 1794-OB16 | — | — | — |
| 24V DC | 10…50V DC | Sourcing | 1794-OB32 | — | — | — | |
| Other 16-Point DC PLC Output Modules | 1492-CABLE¬ P | 1492-CABLE¬ P | 1492-CABLE¬ P | ||||
| Other 32-Point DC PLC Output Modules | — | — | — | ||||
| ¬ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the cat. no. (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Cat. No. 1492-CABLE025WH is for a 2.5 m cable with a pre-wired 1771-WH Wiring Arm on one end. | |||||||
| T Refer to PLC installation manual for details. | |||||||
| Refer to Bulletin 1764 output ratings, when using PanelConnect, Table X on 1667-32OD1201 (32-Point Output). | |||||||
| § Refer to Bulletin 1762 output ratings, when using PanelConnect, Table X on 1667-32OD1201 (32-Point Output). | |||||||
| § Replace with length of cable in meters (1 m, 2 m, 3 m, 5 m, or 10 m standard). | |||||||
| Note: PNP type distribution boxes require source type PLC outputs, NPN require sink outputs. | |||||||
Table 2. DC Output Systems NEMA Type 4, Continued
| Either with or without LEDs | ||||||
| Allen-Bradley Distribution Box | 5-pin DC micro, no LEDs | 898D-58PT-M12 | ||||
| 5-pin DC micro, PNP LEDs | 898D-P58PT-M12 | |||||
| Allen-Bradley Device Patchcord | 889M-F4ACDM-§ | |||||
| Allen-Bradley Main Patchcord 12-pin Metric 23 |
889M-R11RMMU-§ | |||||
| PanelConnect (16 output) | 1667-16OD2205 | 1667-16OD2203 | ||||
| System | ||||||
| Output Systems | Nominal | Output RangeT | @ Module | Output Module | ||
| 1746 | 24V DC | 10…50V DC | Sourcing | 1746-OB16 | — | — |
| 24V DC | 10…30V DC | Sourcing | 1746-OB16E | — | — | |
| 24V DC | 20.4…26.4V DC | Sourcing | 1746-OB16P | — | — | |
| 24V DC | 10…50V DC | Sinking | 1746-OV16 | — | — | |
| 24V DC | 20.4…26.4V DC | Sinking | 1746-OV16P | — | — | |
| 24V DC | 5-125V DC | Sourcing | 1746-OW16 | — | — | |
| 24V DC | 10…50V DC | Sourcing | 1746-OB32 | — | — | |
| 24V DC | 10…30V DC | Sourcing | 1746-OB32E | — | — | |
| 24V DC | 10…50V DC | Sinking | 1746-OV32 | — | — | |
| 1756 | 24V DC | 10…31.2V DC | Sourcing | 1756-OB16E | 1492-CABLE¬ X | — |
| 24V DC | 10…31.2V DC | Sourcing | 1756-OB32 | — | — | |
| 1769 | 24V DC | 20.4…26.4V DC | Sourcing | 1769-OB16 | — | — |
| 24V DC | 20.4…26.4V DC | Sinking | 1769-OV16 | — | — | |
| 24V DC | 5-125V DC | Sourcing | 1769-OW16 | — | — | |
| 1771 | 24V DC | 10…50V DC | Sourcing | 1771-OBD | — | 1492-CABLE¬ F |
| 24V DC | 10…50V DC | Sourcing | 1771-OND | — | 1492-CABLE¬ F | |
| 24V DC | 10…50V DC | Sourcing | 1771-OBN | — | — | |
| 24V DC | 10…50V DC | Sinking | 1771-OVN | — | — | |
| 1794 | 24V DC | 10…50V DC | Sourcing | 1794-OB16 | — | — |
| 24V DC | 10…50V DC | Sourcing | 1794-OB32 | — | — | |
| Other 16-Point DC PLC Output Modules | 1492-CABLE¬ P | 1492-CABLE¬ P | ||||
| Other 32-Point DC PLC Output Modules | — | — | ||||
| ¬ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the cat. no. (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Cat. No. 1492-CABLE025WH is for a 2.5 m cable with a pre-wired 1771-WH Wiring Arm on one end. Also refer to Build-to-Order Length Cables on [BAD REF 203002 ]. | ||||||
| T Refer to PLC installation manual for details. | ||||||
| § Replace with length of cable in meteres (1 m, 2 m, 3 m, 5 m, or 10 m standard). | ||||||
| Note: PNP type distribution boxes require source type PLC outputs, NPN require sink outputs. | ||||||
Table X. Bulletin 1764 Output Current Ratings
| Output Module Cat. No. | Current per Circuit | Current per Module | Indicator Circuit Current |
| 1764-24AWA (outputs)¬ | 0.5 A (Out 0…4) | 4.0 A | 2 mA |
| 1764-24BWA (outputs)¬ | 0.25 A (Out 4…11) | ||
| 1764-28BXB (outputs)¬ | 2.0 A (Out 0…1) | ||
| 0.6 A (Out 2…7) | |||
| 1.0 A (Out 8…11) | |||
| ¬ Refer to Bulletin 1764 literature for output voltage ratings. A single power supply must be used with and Bulletin 1667 module. | |||
Table Y. Bulletin 1762 Output Current Ratings
| Output Module Cat. No. | Current per Circuit | Current per Module | Indicator Circuit Current |
| 1762-40AWA (outputs)¬ | 0.25 A | 4.0 A | 2 mA |
| 1762-40BWA (outputs)¬ | |||
| 1762-40BXB (outputs)¬ | |||
| ¬ Refer to Bulletin 1762 literature for output voltage ratings. A single power supply must be used with and Bulletin 1667 module. | |||
Table 3. AC Output with Direct Connect to Pneumatic Valves
| AC Output | ||||||||||
| Main Connector Style | Mini-plus (1-1/8 in.) | |||||||||
| Connectors | 12-pin | |||||||||
| Valve Interface | Valve Series | Valve Interface | Valve Interface Cable | |||||||
| Output points | 16 | 16 | 16 | |||||||
| Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | Cat. No. | |||||
| Parker Hannifin | F Series Air Control ValveT | SCC122NB | — | 1667-16OA1201 | 1667-16OA1202 | 1667-16OA1203 | ||||
| Festo | Midi/Maxi Pneumatic Valve Manifold | IMP2-03-1§ | Build to order from Mfg. |
1667-16OA1201 | 1667-16OA1202 | 1667-16OA1203 | ||||
| Festo | Midi/Maxi Pneumatic Valve Manifold | IMP2-03-4§ | Build to order from Mfg. |
1667-16OA1201 | 1667-16OA1202 | 1667-16OA1203 | ||||
| System | ||||||||||
| I/O System | Nominal | Output Range§ | Type Module | I/O Module | ||||||
| 1746 | 120V AC | 120…240V AC | Source | 1746-OA16 | — | — | — | 1492-CABLE¬ C | — | — |
| 1756 | 120V AC | 85…265V AC | Source | 1756-OA16 | — | — | — | — | 1492-CABLE¬ X | — |
| 1769 | 120V AC | 74…265V AC | Source | 1769-OA16 | — | — | — | 1492-CAB¬ H69 | — | — |
| 1771 | 120V AC | 10…138V AC | Source | 1771-OAD | — | — | — | — | — | 1492-CABLE¬ F |
| 1794 | 100/120V AC | 85…132V AC | Source | 1794-OA16 | — | — | — | 1492-CABLE¬ P | — | — |
| ¬ Cables are available in lengths of 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the cat. no. (010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Cat. No. 1492-CABLE025WH is for a 2.5 m cable with a pre-wired 1771-WH Wiring Arm on one end. | ||||||||||
| T Voltage Code 23 and 83 valve (120V AC) | ||||||||||
| 120V AC Solenoid Valves only | ||||||||||
| § Maximum 8 outputs | ||||||||||
| § Refer to PLC installation manual for details. | ||||||||||
Table 4. DC Output with Direct Connect to Pneumatic Valves
The same information for Type 4 applies to Type 4X products as shown in Tables 1…4, 2, and 4…6 for Cables and Distribution Boxes.
Table 5. Type 4X Input and Output Systems
| NEMA 4X Module | NEMA 4 Module |
| 1667-16OA1201X | 1667-16OA1201 |
| 1667-16OA1202X | 1667-16OA1202 |
| ¬ | 1667-16OA1203 |
| ¬ | 1667-16OD1201 |
| ¬ | 1667-16OD1202 |
| ¬ | 1667-16OD1203 |
| ¬ | 1667-16OD1204 |
| ¬ | 1667-16OD1205 |
| ¬ | 1667-16OD1206 |
| ¬ | 1667-16OD1207 |
| 1667-16OD2201X | 1667-16OD2201 |
| 1667-16OD2202X | 1667-16OD2202 |
| ¬ | 1667-16OD2203 |
| ¬ | 1667-16OD2204 |
| ¬ | 1667-16OD2205 |
| ¬ | 1667-32OD1201 |
| ¬ Contact factory for availability. Note: to maintain Type 4X compatibility, refer to Sealing Caps | |
Table 6. Distribution Boxes
| Allen-Bradley Distribution Boxes for Outputs | |||||||||
| Typical PanelConnect Modules for PLC Output Platform |
Connection Systems - 8 output connections | ||||||||
| 1746, 1769 and 1794 Catalog Number |
1756 Catalog Number |
1771 Catalog Number |
Distribution Box Catalog Number | Voltage Type | Voltage Range System | LED on Connection Box | Main Connector Type | Output Connection Type | Individual Valve Supported |
| 1667-16OD1201 | 1667-16OD1202 | 1667-16OD1203 | 898D-58PT-N12 | DC | 10-30V DC | No | 12 pin Mini-Plus (1-1/8 in.) | 5-pin Micro | Single |
| 898D-P58PT-N12 _ | DC | 10-30V DC | Yes PNP | 12 pin Mini-Plus (1-1/8 in.) | 5-pin Micro | Single | |||
| 1667-16OD1201 | — | — | 898D-N58PT-N12 _ | DC | 10-30V DC | Yes NPN | 12 pin Mini-Plus (1-1/8 in.) | 5-pin Micro | Single |
| 1667-16OA1201 | 1667-16OA1202 | 1667-16OA1203 | 898N-L38PS-N12 | AC | 85-132V AC | YES | 12 pin Mini-Plus (1-1/8 in.) | 3-pin Mini | Single |
| 1667-16OA1201 | 1667-16OA1202 | 1667-16OA1203 | 898R-L38PS-N12 | AC | 85-132V AC | YES | 12 pin Mini-Plus (1-1/8 in.) | 3-pin Micro | Single |
| 1667-16OD1201 | 1667-16OD1202 | 1667-16OD1203 | 898D-54DT-N12 | DC | 10-30V DC | NO | 12 pin Mini-Plus (1-1/8 in.) | 5-pin Micro | Double |
| 1667-32OD1201 | 1667-32OD1201 | 1667-32OD1201 | 898D-58PT-N12 | DC | 10-30V DC | No | 12 pin Mini-Plus (1-1/8 in.) | 5-pin Micro | Single |
| 1667-32OD1201 | 1667-32OD1201 | 1667-32OD1201 | 898D-P58PT-N12 _ | DC | 10-30V DC | Yes PNP | 12 pin Mini-Plus (1-1/8 in.) | 5-pin Micro | Single |
| 1667-32OD1201 | — | 1667-32OD1201 | 898D-N58PT-N12 _ | DC | 10-30V DC | Yes NPN | 12 pin Mini-Plus (1-1/8 in.) | 5-pin Micro | Single |
| 1667-32OD1201 | 1667-32OD1201 | 1667-32OD1201 | 898D-54DT-N12 | DC | 10-30V DC | NO | 12 pin Mini-Plus (1-1/8 in.) | 5-pin Micro | Double |
Note:All References to Crouse Hinds, Daniel Woodhead, Lumberg and Turck were obtained from manufacturers commercial literature. Refer to manufacturers literature for specific information.
Note: PNP type distribution boxes require source type PLC outputs, NPN require sink outputs.
|
Note: PNP type distribution boxes require source type PLC outputs, NPN require sink outputs.
Table 7. Pneumatic Valve Direct Interfaces
Festo Interface to Panel Connect
| PanelConnect Module for Pneumatic Valves | Valve Connection | ||||||
| Catalog Number PanelConnect | Valve Series | Catalog Number To Valve Interface | Catalog Number for Cable from Valve to PanelConnect | Voltage Type & Output Points | Voltage Range | Main Connector Type PanelConnect | Main Connector Type Valve Interface |
| 1667-16OD1201 | Midi / Maxi Pneumatic Valve Manifold¬ |
03E-x-MP4 | Build to order by Festo | DC & 16 | 24V DC | 24V DC12-pin Mini-Plus (1-1/8 in.) | 25-Pin D-Shell |
| Compact Performance Valve Manifold |
12P-x-MP-xx-x-x | ||||||
| 1667-32OD1201 | Midi / Maxi Pneumatic Valve Manifold¬ |
03E-x-MP4 | Build to order by Festo | DC & 32 | |||
| Compact Performance Valve Manifold |
12P-x-MP-xx-x-x | ||||||
| 1667-16OD1202 | Midi / Maxi Pneumatic Valve Manifold¬ |
03E-x-MP4 | Build to order by Festo | DC & 16 | |||
| Compact Performance Valve Manifold |
12P-x-MP-xx-x-x | ||||||
| 1667-16OA1203 | Midi / Maxi Pneumatic Valve Manifold¬ |
03E-x-MP4 | |||||
| Compact Performance Valve Manifold |
12P-x-MP-xx-x-x | ||||||
| 1667-16OA1201 | Midi / Maxi Pneumatic Valve ManifoldT |
03E-x-MP4 | Build to order by Festo | AC & 16 | 120V AC | ||
| 1667-16OA1202 | |||||||
| 1667-16OA1203 | |||||||
Parker Hannifin Interface to Panel Connect
| PanelConnect Module for Pneumatic Valves | Valve Connection | ||||||
| Catalog Number PanelConnect | Valve Series | Catalog Number To Valve Interface | Catalog Number for Cable from Valve to PanelConnect | Voltage Type & Output Points | Voltage Range | Main Connector Type PanelConnect | Main Connector Type Valve Interface |
| 1667-16OD1201 | F Series Air Control Valve | SCxxx1MB | 889N-F12ACUØ | DC & 16 | 24V DC | 12-pin Mini-Plus (1-1/8 in.) | |
| 1667-32OD1201 | |||||||
| 1667-16OD1202 | |||||||
| 1667-16OD1203 | |||||||
| 1667-16OA1201 | F Series Air Control Valve§ | SCxxx1MB | AC & 16 | 120V AC | 12-pin Mini-Plus (1-1/8 in.) | ||
| 1667-16OA1202 | |||||||
| 1667-16OA1203 | |||||||
Numatics Interface to Panel Connect
| PanelConnect Module for Pneumatic Valves | Valve Connection | ||||||
| Catalog Number PanelConnect | Valve Series | Catalog Number To Valve Interface | Catalog Number for Cable from Valve to PanelConnect§ | Voltage Type & Output Points | Voltage Range | Main Connector Type PanelConnect | Main Connector Type Valve Interface |
| 1667-16OD2201 | 2005 Valve | AKP… | Available from Distributor | DC & 16 | 24V DC | Metric M23 | |
| 1667-16OD2201 | 2012 Valve | ||||||
| 1667-16OD2201 | ISO 5999/2 | ||||||
| Note:Maximum of 8 Outputs per PanelConnect Connector | |||||||
| ¬ DC 24V DC Solenoid Valves Only | |||||||
| T AC 120V DC Solenoid Valves Only | |||||||
| Voltage Code 19 Valve | |||||||
| § Voltage Code 23 and 83 Valve (120V AC) | |||||||
| § A-B or Numatics distributor that carries on M23 cable. | |||||||
| Ø Mini-Plus patchcords are available in standard legnths of 1 m, 2 m, 3 m, 5 m, and 10 m (0.3 ft, 0.6 ft, 0.9 ft, 1.5 ft and 3 ft). To order, insert the desired length in the catalog number. Example: 889N-F12ACNU-2 represents a 2 m (0.6 ft) patchcord. Note catalog number reflects straight male to straight female version with 18/22 AWG conductors, addtional models are also available. | |||||||
Digital PanelConnect™ Output Specifications
For all PanelConnect dimensions, refer to 16-Point PanelConnect Input or Output Module Dimensions.
For general marker card information, refer to Marker Cards.
For general adhesive label card information, refer to Adhesive Label Cards for 16-Point Input PanelConnect Modules.
|
|
Output PanelConnect Module with two or four 12-pin Mini-Plus connectors or two 12-pin M23 connectors
| 16-Point with Mini-Plus 12-pin, 1-1/8 in. |
32-Point with Mini-Plus 12-pin, 1-1/8 in. |
16-Point with M23 12-pin, 23 mm |
| Cat. No. | Cat. No. | Cat. No. |
| 1667-16OA1201 | 1667-32OD1201 | 1667-16OD2201 |
| 1667-16OA1202 | 1667-16OD2202 | |
| 1667-16OA1203 | 1667-16OD2203 | |
| 1667-16OD1201 | 1667-16OD2204 | |
| 1667-16OD1202 | 1667-16OD2205 | |
| 1667-16OD1203 | ||
| 1667-16OD1204 | ||
| 1667-16OD1205 | ||
| 1667-16OD1206 | ||
| 1667-16OD1207 |
Digital PanelConnect™ Modules for Outputs
|
|
Features:
Application Notes
Distribution Block Connection
Match I/O Program to Distribution Block outputs in the sequence shown below
1667-160Axxxx
|
1667-160Dxxxx
|
1. Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.
3. Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.
|
|
Modules for 16 Outputs (M23)
|
Features:
Specifications
Application Notes
Distribution Block Connection
Match I/O Program to Distribution Block outputs in the sequence shown below:
|
1. Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.
3. Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.
|
|
1667-32OD1201 (32-Point Output)
|
1667-32OD1201 Specifications
| Main PanelConnect Connector | Number of pins | 12 |
| Style | Mini-Plus 1-1/8 in. | |
| Number of points | 32 | |
| Degree of Protection | IP65 Type 1, 4, 4X, 12 |
| Voltage Rating | 10…30V DC |
| Maximum Peak Voltage¬ | 600Vp |
| Maximum Current (per Circuit) | 2 A |
| Maximum Current (per Module) | 12 A |
| Indicator Circuit Current (Nominal) | 2 mA |
| No. of Terminals per Device Common | 2 |
| Operating Temperature Range | 0…+60×C Non-Condensing |
| Certifications | |
| ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5 kV withstand. | |
|
|
Power Supply Connector Specification | |
| Wire Range (Rated Cross Section) | #22…#12 AWG (0.2…4 mm2) | |
| Wire Strip Length | 0.32 in. (8 mm) | |
| Recommended Tightening Torque | 4.5…5.5 lb.-in. (0.50…0.60 Nm) | |
Distribution Block Connection
Match I/O Program to Distribution Block outputs in the sequence shown below:
Pinout
|
|
Application Notes
1. Compatibility — To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring — Refer to the label section on [BAD REF 202766 ].
3. Dimensions — Refer to 16-Point PanelConnect Input or Output Module Dimensions.
|
Note:For configuring to double solenoid valves, refer to Table 6. Distribution Boxes for Distribution Box connections.
Table X. PLC-Specific Current Ratings
| Cat. No. | Current/Circuit | Current/Module | Indicator Circuit Current | Operating Temperature Range |
| 1762-40AWA (Outputs) ¬ | 0.25 A | 4.0 A | 2 mA | 0°…60°C |
| 1762-40BWA (Outputs) ¬ | ||||
| 1762-40BXB (Outputs) ¬ | ||||
| 1764-24AWA (Outputs) ¬ | 0.5 A (Outputs 0…4) 0.25 A (Outputs 4…11) |
|||
| 1764-24BWA (Outputs) ¬ | ||||
| 1764-28BXB (Outputs) ¬ | 2.0 A (Outputs 0…1) 0.6 A (Outputs 2…7) 1.0 A (Outputs 8…11) |
|||
| ¬ Refer to Bulletin 1762 and 1764 literature for output voltage ratings. | ||||
Pre-Wired Cables for Output PanelConnect™
Bulletin 1492 pre-wired cables are designed to minimize control wiring in a panel. Digital pre-wired cables, when used with a PanelConnect™ Module, replace the point-to-point wiring between Allen-Bradley programmable controller I/O modules and individual terminal blocks. The digital ready-to-wire cables provide one end of the cable pre-terminated, for the PanelConnect Module.
Specifications
|
The pre-wired cables have a Bulletin 1746 Removable Terminal Block, 1756 Removable Terminal Block, 1769 Removable Terminal Block, or 1771 Wiring Arm on one end and a cable connector on the other to connect to the PanelConnect Module. The broad offering of digital pre-wired cables supports Bulletin 1746, 1756, 1769, and 1771 digital modules.
| Cat. No. | Standard Cable Lengths | Insulation Rating | No. of Conductors | Conductor Size | Nominal Outer Diameter | I/O Module Connector Cat. No. |
| 1492-CABLE¬ C | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1746-RT25R Red Removable Terminal Block |
| 1492-CABLE¬ D | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1746-RT25C Orange Removable Terminal Block |
| 1492-CABLE¬ E | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1746-RT25B Blue Removable Terminal Block |
| 1492-CABLE¬ F | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1771-WH (16-Point/21 Terminal) Wiring Arm |
| 1492-CABLE¬ H | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 11.7 mm (0.46 in.) | 1746-N3 40-pin cable connector |
| 1492-CABLE¬ L | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 11.7 mm (0.46 in.) | 1771-WN (32-point/40 Terminal) Wiring Arm |
| 1492-CABLE¬ X | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1756-TBNH Removable Terminal Block |
| 1492-CABLE¬ Z | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 11.7 mm (0.46 in.) | 1756-TBCH Removable Terminal Block |
| 1492-CAB¬ B62 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 40 | #22 AWG | 11.7 mm (0.46 in.) | 1762-L40xxx Output Terminal |
| 1492-CAB¬ C64 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1764-24AWA, -24BWA Output Terminal |
| 1492-CAB¬ F64 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1764-28BXB Output Terminal |
| 1492-CAB¬ E69 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | 1769-RTBN18 Removable Terminal Block |
| 1492-CAB¬ H69 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 11.0 mm (0.46 in.) | 1769-RTBN18 Removable Terminal Block |
| 1492-CAB¬ K69 | 0.5, 1.0, 2.5, 5.0 m | 300V 80°C | 20 | #22 AWG | 9.0 mm (0.36 in.) | (2) 1769-RTBN18 Removable Terminal Block |
| ¬ Cables are available in standard lengths of 0.5 m, 1.0 m, 2.5 m, and 5.0 m. To order, insert the code for the desired cable length into the cat. no. (005 = 0.5 m, 010 = 1.0 m, 025 = 2.5 m, and 050 = 5.0 m). Example: Cat. No. 1492-CABLE005A is for a 0.5 m cable for the 1746-IA16 I/O Module. | ||||||
Pinouts
Digital Pre-Wired Cables
The following diagrams illustrate how the individual conductors in the digital pre-wired cables are terminated at both ends. The description listed first is the wire color of the conductor connected to the removable terminal block (Bulletin 1746, 1756, and 1769 I/O) or wiring arm (1771 I/O). The number that follows in parentheses is the corresponding pin number of the PanelConnect™ mating connector.
|
I/O pin Connector Definition
|
PanelConnect Mating Connector
Combination PanelConnect Features
|
32-Point Combination Input/Output PanelConnect Module with four 12-pin Mini-Plus Connectors
These modules are used when input and output devices are in the vicinity of each other (i.e., conveyor systems).
Each 12-pin Mini-Plus connector connects to four (4) input and four (4) output devices. The distribution box used in this application is split between four (4) inputs and four (4) outputs. Each 12-pin Mini-Plus connector mates with a twelve-conductor patchcord that connects to the distribution box.
These modules are normally used with Connection systems with LEDs on the distribution box, for easier identification on the machine. The 32-Point combination modules are available only for DC inputs and outputs.
Each PanelConnect module has an LED to indicate when the module is powered. On the internal panel side, the PanelConnect mates with two 20-pin cables, one for PLC input modules and one for PLC output modules. These cables are available for the most popular Allen-Bradley Input and Output I/O modules. Modules are available in Type 4 and 4X versions.
|
Digital Pre-Wired Cables
Bulletin 1492 pre-wired cables are designed to minimize control wiring in a panel. Pre-wired cables, when used with a PanelConnect Module replaces the point-to-point wiring between Allen-Bradley programmable controller I/O modules and individual terminal blocks. The pre-wired cables have a removable terminal block or wiring arm at the I/O end of the cable and a cable connector on the other end to connect to the PanelConnect Module. All of the pre-wired cables use #22 AWG wire and are 100% tested for continuity to make a perfect connection every time. The digital pre-wired cables are offered in four standard lengths of 0.5, 1.0, 2.5, and 5.0 m to fit a variety of applications. Other cable lengths are also available as build-to-order products. Pre-wired cables are available for many of the 1746 SLC I/O, 1756 ControlLogix, 1769 Compact for CompactLogix and MicroLogix 1500, and 1771 (PLC-5) Output Modules.
|
Ready-to-Wire Digital Cables
PanelConnect-ready cables have a cable connector that attaches to the PanelConnect Module, pre-wired to one end, and have free connectors ready to wire to other suppliers I/O modules or other components on the other end. PanelConnect ready cables use #22 AWG wire and have individual color-coded conductors for quick wire-to-terminal coordination. The digital PanelConnect-ready cables are offered in standard lengths of 1.0, 2.5, and 5.0 m to fit a variety of applications. Other cable lengths are also available as build-to-order products.
|
¬ PanelConnect Combination
32-point Input/Output...Digital Pre-Wired Cables
T Wiring Systems Cable
Main Patchcord (Mini-Plus)
§ Distribution Box
§ Device Patchcords
Ø Sealing Caps…Sealing Caps
z Inductive Proximity...See the Sensors Catalog
ª Photoelectric Sensor…See the Sensors Catalog
v Limit Switch…See the Sensors Catalog
|
|
|
|
Typical Configuration
|
Selecting Combination Products
Follow these steps when starting selection from the I/O Module and PanelConnect:
1. Determine the Input or Output voltage type. Use Table 1 for DC Outputs systems with Distribution Box connection.
2. Determine the PLC I/O system that you are using, 1746, 1756, 1769, 1771, 1762, 1764, 1794
3. The main connector for all combination modules is a Mini-Plus - 1 1/8 in. type.
4. All available Distribution Box have LED indicators
5. Select the appropriate PanelConnect module and a cable
6. If Type 4X system is required, select from Table 2
Note:Appropriate Connection Systems suppliers are noted in Tables 1…3. Appropriate Pneumatic Valve suppliers are noted in Table 1.
Refer to Table 3 for each supplier for Distribution Box details.
Follow these steps when starting selection from Output Distribution Box and connect type:
Determine Output Distribution Box details, first
1. Determine manufacturer of Distribution Box
2. Determine voltage type DC, and nominal voltage
3. Determine Distribution Box with LED
4. Determine connection type
5. Select PanelConnect Module and a cable
Refer to Table 1 to determine appropriate output system and PanelConnect Cable.
Follow these steps when starting selection from direct connect Pneumatic valves Manifold:
Determine Pneumatic Valve Manifold details, first
1. Determine manufacturer of pneumatic valve
2. Determine voltage type AC or DC
3. Determine Pneumatic Valve series
4. Select Valve Interface (Table 2 or 3)
5. Select PanelConnect Module and a cable
Refer to Table 1 to determine appropriate output system and PanelConnect cable
Table 1. 32-Point Combination Modules
| DC Combination Input and Output | ||||||||||||||||
| Distribution Box | 5-pin DC micro, no LEDs, dual input/output per port | 898D-54DT-N12 | — | — | 898D-54DT-N12 | |||||||||||
| 5-pin DC micro, no LEDs | 898D-58PT-N12 | — | — | 898D-58PT-N12 | ||||||||||||
| 5-pin DC micro, PNP LEDs | 898D-P58PT-N12 | — | ||||||||||||||
| 5-pin DC micro, NPN LEDs | — | — | — | 898D-N58PT-N12 | ||||||||||||
| Device Patchcords | 889D-F4ACDM-§ | 889D-F4ACDM-§ | 889D-F4ACDM-§ | 889D-F4ACDM-§ | ||||||||||||
| Main Patchcord Mini-plus ( 1-1/8 in.) 12-pin |
889N-F12ACNU-§ | 889N-F12ACNU-§ | 889N-F12ACNU-§ | 889N-F12ACNU-§ | ||||||||||||
| PanelConnect | 1667-32CD1201 | 1667-32CD1202 | 1667-32CD1203 | 1667-32CD1204 | ||||||||||||
| Allen-Bradley Input Systems | Allen-Bradley Output Systems | |||||||||||||||
| I/O System | Nominal | Input Range | Type Module | Input Module | Input CableT | Output Cable | Input CableT | Output Cable | Input CableT | Output Cable | Input CableT | Output Cable | Nominal | Input Range | Type Module | Output Module |
| 1746 | 24V DC | 10…30V | Sink | 1746-IB16 | 1492-CABLE¬ B | 1492-CABLE¬ E | — | — | — | — | — | — | 24V DC | 10…30V | Source | 1746-OB16E |
| 24V DC | 10…30V AC/DC | Sink | 1746-IN16 | 1492-CABLE¬ B | 1492-CABLE¬ E | — | — | — | — | — | — | 24V DC | 10…30V | Source | 1746-OB16E | |
| 24V DC | 10…30V DC | Sink | 1746-ITB16 | 1492-CABLE¬ B | 1492-CABLE¬ E | — | — | — | — | — | — | 24V DC | 10…30V | Source | 1746-OB16E | |
| 24V DC | 10…30V DC | Source | 1746-ITV16 | — | — | — | — | — | — | 1492-CABLE¬ E | 1492-CABLE¬ E | 24V DC | 10…50V DC | Sink | 1746-OV16 | |
| 24V DC | 10…30V DC | Source | 1746-IV16 | — | — | — | — | — | — | 1492-CABLE¬ B | 1492-CABLE¬ E | 24V DC | 20…26V DC | Sink | 1746-OVP16 | |
| 1756 | 24V DC | 10…30V DC | Sink | 1756-IB16 | — | — | 1492-CABLE¬ X | 1492-CABLE¬ X | — | — | — | — | 24V DC | 10…30V DC | Source | 1756-OB16E |
| 1769 | 24V DC | 10…30V DC | Sink Only | 1769-IQ16 (Sink Mode) | 1492-CAB¬ B69 | 1492-CAB¬ E69 | — | — | — | — | — | — | 24V DC | 20…26V DC | Source | 1769-OB16 |
| 24V DC | 10…30V DC | Source | 1769-IQ16 (Source Mode) | — | — | — | — | — | — | 1492-CAB¬ B69 | 1492-CAB¬ E69 | 24V DC | 20…26V DC | Sink | 1769-OV16 | |
| 1771 | 24V DC | 10…30V DC | Sink Only |
1771-IBD | — | — | — | — | 1492-CABLE¬ F | 1492-CABLE¬ F | — | — | 24V DC | 10…50V DC | Source | 1771-OBD |
| 24V DC | 20…60V DC | Sink | 1771-ICD | — | — | — | — | 1492-CABLE¬ F | 1492-CABLE¬ F | — | — | 24V DC | 10…50V DC | Source | 1771-OBD | |
| 24V DC | 9…30V DC | Sink | 1771-IND | — | — | — | — | 1492-CABLE¬ F | 1492-CABLE¬ F | — | — | 24V DC | 10…50V DC | Source | 1771-OBD | |
| 1794 | 24V DC | 10…30V DC | Sink | 1794-IB16 | 1492-CABLE¬ P | 1492-CABLE¬ P | — | — | — | — | 1492-CABLE¬ P | 1492-CABLE¬ P | 24V DC | 10…30V DC | Source | 1794-OB16 |
| ¬ Cables are available in standard lengths of 0.5 m, 1.0 m, and 5.0 m. To order, insert the desired length code in the catalog number (005 = 0.5 m, 010 = 1.0 m, 0.25 = 2.5 m, and 050 = 5 m). Example: 1492-CABLE005B is for a 0.5 m cable for the 1746-IB16 I/O module. 1492-CABLE¬ P has minimum length of 1.0 m. |
||||||||||||||||
| T The input cable mates to the Allen-Bradley input system input module. | ||||||||||||||||
| The output cable mates to the Allen-Bradley input system output module. | ||||||||||||||||
| § Mini patchcords are available in standard lengths of 0.9 m, 1.8 m, 3.6 m, and 6 m (3 ft., 6 ft., 12 ft., and 20 ft.). To order, insert the desired length in the catalog number. Example: 889N-F12ACNU-2 represents a 2 m (6.5 ft.) patchcord. Note catalog number reflects straigh male to straight female version with 18/22 AWG conductors, additional models are also available. | ||||||||||||||||
| § DC micro patchcords are available in standard lengths of 1 m, 2 m, 3 m, 5 m, and 10 m (3.3 ft, 6.5 ft, 9.8 ft, 16.4 ft and 32.8 ft). To order, insert the desired length in the catalog number. Example: 889D-F4ACDM-2 represents a 2 m (6.5 ft.) patchcord. Note catalog number reflects straight male to straight female version with 18/22 AWG conductors, additional models are also available. | ||||||||||||||||
Note:PNP type disitrubtion boxes require sink type PLC inputs and source type PLC outputs. NPN type distribution boxes require source type PLC inputs and sink type PLC outputs.
Digital PanelConnect™ Combination Specifications
For all PanelConnect dimensions, refer to 16-Point PanelConnect Input or Output Module Dimensions.
For general marker card information, refer to Marker Cards.
For general adhesive label card information, refer to Adhesive Label Cards for 16-Point Input PanelConnect Modules.
Refer to the online documentation for new product information.
1667-32CD1201
|
1667-32CD1201 Specifications
| Main PanelConnect Connector |
No. pins | 12 |
| Style | Mini-Plus 1-1/8 in. | |
| Type | 16 Input / 16 Output | |
| No Points | 32-Point Combination |
| Degree of Protection | IP65 Type 1, 4, 4X, 12 |
| Voltage Rating | 10…30V DC |
| Maximum Peak Voltage¬ | 600Vp |
| Maximum Current (per Circuit) | 2 A |
| Maximum Current (per Module) | 12 A |
| Indicator Circuit Current (Nominal) | 2 mA |
| No. of Terminals per Device Common | 2 |
| Operating Temperature Range | 0°…+60°C (32°…140°F) Non Condensing |
| Certifications | |
| ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5 kV withstand. | |
|
|
Power Supply Connector Specification | |
| Wire Range (Rated Cross Section) | #22…#12 AWG (0.2…4 mm2) | |
| Wire Strip Length | 0.32 in. (8 mm) | |
| Recommended Tightening Torque | 4.5…5.5 lb.-in. (0.50…0.60 Nm) | |
Distribution Block Connection
Match I/O Program to Distribution Block outputs in the sequence shown below:
Pinout
|
|
Application Notes
1. Compatibility — To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring — Refer to the label section on [BAD REF 214245 ].
3. Dimensions — Refer to 16-Point PanelConnect Input or Output Module Dimensions.
|
1667-32CD1202
|
1667-32CD1202 Specifications
| Main PanelConnect Connector |
No. pins | 12 |
| Style | Mini-Plus 1-1/8 in. | |
| Type | 16 Input / 16 Output | |
| No Points | 32-Point Combination |
| Degree of Protection | IP65 Type 1, 4, 4X, 12 |
| Voltage Rating | 10…30V DC |
| Maximum Peak Voltage¬ | 600Vp |
| Maximum Current (per Circuit) | 2 A |
| Maximum Current (per Module) | 12 A |
| Indicator Circuit Current (Nominal) | 2 mA |
| No. of Terminals per Device Common | 2 |
| Operating Temperature Range | 0°…+60°C (32°…140°F) Non Condensing |
| Certifications | |
| ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5 kV withstand. | |
|
|
Power Supply Connector Specification | |
| Wire Range (Rated Cross Section) | #22…#12 AWG (0.2…4 mm2) | |
| Wire Strip Length | 0.32 in. (8 mm) | |
| Recommended Tightening Torque | 4.5…5.5 lb.-in. (0.50…0.60 Nm) | |
Distribution Block Connection
Match I/O Program to Distribution Block outputs in the sequence shown below:
Pinout
|
|
Application Notes
1. Compatibility — To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring — Refer to the label section on Adhesive Label Cards for 16-Point Output PanelConnect Modules.
3. Dimensions — Refer to 16-Point PanelConnect Input or Output Module Dimensions.
|
1667-32CD1203
|
1667-32CD1203 Specifications
| Main PanelConnect Connector |
No. pins | 12 |
| Style | Mini-Plus 1-1/8 in. | |
| Type | 16 Input / 16 Output | |
| No Points | 32-Point Combination |
| Degree of Protection | IP65 Type 1, 4, 4X, 12 |
| Voltage Rating | 10…30V DC |
| Maximum Peak Voltage¬ | 600Vp |
| Maximum Current (per Circuit) | 2 A |
| Maximum Current (per Module) | 12 A |
| Indicator Circuit Current (Nominal) | 2 mA |
| No. of Terminals per Device Common | 2 |
| Operating Temperature Range | 0°…+60°C (32°…140°F) Non Condensing |
| Certifications | |
| ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5 kV withstand. | |
|
|
Power Supply Connector Specification | |
| Wire Range (Rated Cross Section) | #22…#12 AWG (0.2…4 mm2) | |
| Wire Strip Length | 0.32 in. (8 mm) | |
| Recommended Tightening Torque | 4.5…5.5 lb.-in. (0.50…0.60 Nm) | |
Distribution Block Connection
Match I/O Program to Distribution Block outputs in the sequence shown below:
Pinout
|
|
Application Notes
1. Compatibility — To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring — Refer to the label section on Adhesive Label Cards for 16-Point Output PanelConnect Modules.
3. Dimensions — Refer to 16-Point PanelConnect Input or Output Module Dimensions.
|
1667-32CD1204
|
1667-32CD1204 Specifications
| Main PanelConnect Connector |
No. pins | 12 |
| Style | Mini-Plus 1-1/8 in. | |
| Type | 16 Input / 16 Output | |
| No Points | 32-Point Combination |
| Degree of Protection | IP65 Type 1, 4, 4X, 12 |
| Voltage Rating | 10…30V DC |
| Maximum Peak Voltage¬ | 600Vp |
| Maximum Current (per Circuit) | 2 A |
| Maximum Current (per Module) | 12 A |
| Indicator Circuit Current (Nominal) | 2 mA |
| No. of Terminals per Device Common | 2 |
| Operating Temperature Range | 0°…+60°C (32°…140°F) Non Condensing |
| Certifications | |
| ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5 kV withstand. | |
|
|
Power Supply Connector Specification | |
| Wire Range (Rated Cross Section) | #22…#12 AWG (0.2…4 mm2) | |
| Wire Strip Length | 0.32 in. (8 mm) | |
| Recommended Tightening Torque | 4.5…5.5 lb.-in. (0.50…0.60 Nm) | |
Distribution Block Connection
Match I/O Program to Distribution Block outputs in the sequence shown below:
Pinout
|
|
Application Notes
1. Compatibility — To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring — Refer to the label section on Adhesive Label Cards for 16-Point Output PanelConnect Modules.
3. Dimensions — Refer to 16-Point PanelConnect Input or Output Module Dimensions.
|
Accessories
|
PanelConnect Fuse Module
The PanelConnect fuse module provides a convenient method of adding overcurrent protection to your PanelConnect inputs and outputs. This module has sixteen or thirty-two (16 or 32) 5x20 fuse holders to protect each individual input or output. The module has two 20-pin or 40-pin connectors with locking tabs. The right connector is used to connect to the back of the PanelConnect (in-panel connector). The left connector is used to connect to the Input or Output PLC module. The connection between the PanelConnect Module and the Fuse Module is done via the PanelConnect Option Module cable while connection to the PLC is done via PanelConnect pre-wired cables. This module is optional so OEMs can add fusing based on the needs of their customers.
|
Digital Option Module Cables
PanelConnect Option Module cable has two over molded cable connectors. The cables use #22 AWG wire and are 100% tested for continuity to make a perfect connection between the fuse module and PanelConnect Module every time. These cables are offered in five standard lengths of 0.5, 1.0, 1.5, 2.5, and 5.5 meters to fit a variety of applications.
|
Sealing Caps
To maintain the Type 4, 4X, and 12 enclosure rating, these accessory caps must be used if both field side connectors are not permanently terminated. Hand tighten plus one quarter turn.
|
| PanelConnect Catalog Number |
1667-ZC1¬ Mini-Plus 1-1/8 in. |
1667-ZC2¬ M23 |
PanelConnect Catalog Number |
1667-ZC1¬ Mini-Plus 1-1/8 in. |
1667-ZC2¬ M23 |
| 1667-16IA1008 | X | 1667-16OD1202 | X | ||
| 1667-16IA1207 | X | 1667-16OD1203 | X | ||
| 1667-16IA2209 | X | 1667-16OD1204 | X | ||
| 1667-16ID1001 | X | 1667-16OD1205 | X | ||
| 1667-16ID1004 | X | 1667-16OD1206 | X | ||
| 1667-16ID1201 | X | 1667-16OD1207 | X | ||
| 1667-16ID1202 | X | 1667-16OD2201 | X | ||
| 1667-16ID1203 | X | 1667-16OD2202 | X | ||
| 1667-16ID1210 | X | 1667-16OD2203 | X | ||
| 1667-16ID1212 | X | 1667-16OD2204 | X | ||
| 1667-16ID2205 | X | 1667-16OD2205 | X | ||
| 1667-16ID2206 | X | 1667-32CO1201 | X | ||
| 1667-16ID2211 | X | 1667-32CO1202 | X | ||
| 1667-16ID2213 | X | 1667-32CO1203 | X | ||
| 1667-16OA1201 | X | 1667-32CO1204 | X | ||
| 1667-16OA1202 | X | 1667-32ID1201 | X | ||
| 1667-16OA1203 | X | 1667-32ID1202 | X | ||
| 1667-16OD1201 | X | 1667-32OA1201 | X | ||
| ¬ Add X to Cat. No. for NEMA 4X sealing cap | |||||
Mounting Bracket
|
Use the above bracket (1667-ZB) when mounting the PanelConnect module within an enclosure.
Marker Cards
Each PanelConnect is provided with markers ¬ , T installed in the front of the module. The center marker T indicates whether the module is an input or output combined device. The blank markers ¬ are for customer use to mark I/O address or cable reference. In addition, each PanelConnect is provided with a tree of five markers for machine marking. Replacement and spare markers are available as accessories, 1492-M9X20.
Voltage Marking Ring
Each PanelConnect™ module is provided with two voltage marking rings( ). AC modules use the red rings provided and DC modules use the blue rings.
|
|
The same information for Type 4 applies to Type 4X products as shown in Tables 1 and 2 for Cables and Distribution Boxes.
Table 2. Type 4X Input Systems
| Type 4X Module | Type 4 Module |
| ¬ | 1667-32CD1201 |
| ¬ | 1667-32CD1202 |
| ¬ | 1667-32CD1203 |
| ¬ | 1667-32CD1204 |
| ¬ Contact factory for availability | |
Adhesive Label Cards for 16-Point Input PanelConnect Modules
Each PanelConnect™ module is provided with an adhesive label card. The label card is made available for the back of the PanelConnect Module and provides the power supply connector descriptions. The label strips provides the wiring description from the input module power connections.
The label lists ( ) all of the compatible input modules and their respective power wiring descriptions. Depending on the input module that is used, the label strip is simply peeled from the label card and applied to the back side power supply connector ( ).
In addition, blank labels are provided for:
| 1667-16IA1008 | 1667-16ID1001 | 1667-16ID2205 |
| 1667-16IA1207 | 1667-16ID1004 | 1667-16ID2206 |
| 1667-16IA2209 | 1667-16ID1201 | 1667-16ID2211 |
| 1667-16ID1202 | 1667-16ID2213 | |
| 1667-16ID1203 | ||
| 1667-16ID1212 |
|
16-Point Input Label Card with Labels
|
Adhesive Label Cards for 16-Point Output PanelConnect Modules
Each PanelConnect™ module is provided with an adhesive label card. The label card is made available for the back of the PanelConnect Module and provides the power supply connector descriptions. The label strips provides the wiring description from the input module power connections.
The label lists ( )all of the compatible input modules and their respective power wiring descriptions. Depending on the input module that is used, the label strip is simply peeled from the label card and applied to the back side power supply connector ( ).
In addition, blank labels are provided for:
| 1667-16OA1201 | 1667-16OD1201 | 1667-16OD2201 | 1667-16OD2204 |
| 1667-16OA1202 | 1667-16OD1202 | 1667-16OD2202 | 1667-16OD2205 |
| 1667-16OA1203 | 1667-16OD1203 | 1667-16OD2203 | |
| 1667-16OD1204 | |||
| 1667-16OD1205 | |||
| 1667-16OD1206 | |||
| 1667-16OD1207 |
|
16-Point Output Label Card with Labels
|
Adhesive Label Cards for 32-Point Input, Output and Combination Input/Output PanelConnect Modules
Each PanelConnect™ module is provided with an adhesive label card. The label card is made available for the back of the PanelConnect Module and provides the power supply connector descriptions. The label strips provides the wiring description from the input module power connections.
The label lists ( ) all of the compatible input modules and their respective power wiring descriptions. Depending on the input module that is used, the label strip is simply peeled from the label card and applied to the back side power supply connector ( ).
In addition, blank labels are provided for:
| Combination | Input | Output |
| 1667-32CD1201 | 1667-32ID1001 1667-32ID12001 |
1667-32OD1201 |
| 1667-32CD1202 | ||
| 1667-32CD1203 | ||
| 1667-32CD1204 | ||
|
|
Fuse Modules
1667-Z16F
|
1667-Z16F Specifications
| Option Module Connector | No. pins | 20 |
| Style | Male | |
| Degree of Protection | IP20 |
| Voltage Rating | 10…265V AC/DC |
| Maximum Peak Voltage¬ | 600Vp |
| Maximum Current (per Circuit) | 2 A |
| Maximum Current (per Module) | 12 A |
| Operating Temperature Range | 0°…+60°C (32°…140°F) Non-Condensing |
| Certifications | |
| ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5 kV withstand. | |
Pinout
|
Application Notes
1. Compatibility — To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the fuse and PanelConnect Module.
2. Dimensions — Refer to 16-Point PanelConnect Input or Output Module Dimensions.
1667-Z32F
|
1667-Z32F Specifications
| Option Module Connector | No. pins | 40 |
| Style | Male | |
| Degree of Protection | IP20 |
| Voltage Rating | 10…265V AC/DC |
| Maximum Peak Voltage¬ | 600Vp |
| Maximum Current (per Circuit) | 2 A |
| Maximum Current (per Module) | 12 A |
| Operating Temperature Range | 0°…+60°C (32°…140°F) Non-Condensing |
| Certifications | |
| ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5 kV withstand. | |
Pinout
|
| Fuse Module Connections | ||||
| Connector Pin Reference from I/O |
PanelConnect Connector Pin Reference | Connector Pin Reference from I/O | PanelConnect Connector pin Reference from I/O | |