Connection Systems

Catalogs > Industrial Controls Catalog > Connection Systems > Panel Connection Systems

Panel Connection Systems

Description PanelConnect System View PanelConnect Input Features Product Selection — Input Modules PanelConnect™ Specifications Modules for 16-Point Inputs Pre-Wired Cables for Input PanelConnect
PanelConnect Output Features and Typical Configuration Product Selection — Output Modules Digital PanelConnect™ Output Specifications Digital PanelConnect™ Modules for Outputs Pre-Wired Cables for Output PanelConnect™ Combination PanelConnect Features Selecting Combination Products
Digital PanelConnect™ Combination Specifications Accessories Fuse Modules PanelConnect Digital, Option Module Cable Specifications 16-Point PanelConnect Input or Output Module Dimensions Pneumatic Valve Wiring Reference Guide
Digital PanelConnect™ Modules for Outputs

Click to enlarge - 01059002


Click to enlarge - ab_modfront_004945-gray


Features:

  • Direct connection to common 16- and 32-point PLC output cards.


  • AC and DC versions with color-coded ring for voltage indication.


  • LED power indicator.


  • Rugged durable construction.


  • Provides pre-wired connectivity from field device to PLC output module.


  • Cat. No. 1667-16OA1201T  1667-16OA1202T  1667-16OA1203 1667-16OD1201T  1667-16OD1202 1667-16OD1203 1667-16OD1204T  1667-16OD1205 1667-16OD1206 1667-16OD1207
    Field Connector Style 12-Pin Mini Plus (1-1/8 in.)
    Voltage Rating 10-265V AC 10-265V DC
    Module Type 16 Output
    Degree of Protection IP65; Type 1, 4, 4X, 12
    Maximum Peak Voltage¬  600Vp
    Maximum Current (per Circuit) 2 A
    Maximum Current (per Module) 12 A
    Indicator Circuit Current (Nominal) 2 mA
    No. of Terminals per Device Common 2
    Operating Temperature Range 0°C…+60°C (32°F…+140°F); Noncondensing
    Certifications
  • cULus Listed (File E113724 Guide NRAQ)

  • CE
  • Power Supply Connector Specification
    Wire Range (Rated Cross Section) #22…#12 AWG (0.2…4 mm2)
    Wire Strip Length 8 mm (0.32 in.)
    Recommended Tightening Torque 0.50…0.60 N•m (4.5…5.5 lb-in.)
      
    ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5kV withstand.
    T When using 1667-Oxx PanelConnect modules with bulletin 1762 MicroLogix 1200 embedded or Bulletin 1764 MicroLogix 1500 base I/O, the Bulletin 1667 module current ratings are lower. Refer to Table X, .

    Application Notes

    Distribution Block Connection

    Match I/O Program to Distribution Block outputs in the sequence shown below

    1667-160Axxxx

    Click to enlarge - EXPANSION BLOCK_1


    1667-160Dxxxx

    Click to enlarge - EXPANSION BLOCK_2wss


    1.  Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.

    2.  Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.

    3.  Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.


    Panel Connections
    Field Side Connector—12-Pin Mini-Plus
    Click to enlarge - cross box
    Output Connector Pin Reference AC AC AC DC DC DC DC DC DC DC
    1667-16OA1201 1667-16OA1202 1667-16OA1203 1667-16OD1201 1667-16OD1202 1667-16OD1203 1667-16OD1204 1667-16OD1205 1667-16OD1206 1667-16OD1207
    Click to enlarge - blue dot
    1 A11, B11 A11 A11, B11 A12, B12 A12 A12, B12 A12, B12 A12 A10,B10 A10
    2 A7 A11 A10 B11
    3 A10 A10 A10 A1 A1 A1 A7 A7 A1 A1
    4 A1 A1 A1 A2 A2 A2 A6 A6 A2 A2
    5 A12 A12 A12 A3 A3 A3 A5 A5 A3 A3
    6 A2 A2 A2 A4 A4 A4 A4 A4 A4 A4
    7 A3 A3 A3 A5 A5 A5 A3 A3 A5 A5
    8 A4 A4 A4 A6 A6 A6 A2 A2 A6 A6
    9 A5 A5 A5 A7 A7 A7 A1 A1 A7 A7
    10 A6 A6 A6 A8 A8 A8 A8 A8 A8 A8
    11 B10 B10 B10 B1 B1 B1 B7 B7 B1 B1
    12 B1 B1 B1 B2 B2 B2 B6 B6 B2 B2
    13 B12 B12 B12 B3 B3 B3 B5 B5 B3 B3
    14 B2 B2 B2 B4 B4 B4 B4 B4 B4 B4
    15 B3 B3 B3 B5 B5 B5 B3 B3 B5 B5
    16 B4 B4 B4 B6 B6 B6 B2 B2 B6 B6
    17 B5 B5 B5 B7 B7 B7 B1 B1 B7 B7
    18 B6 B6 B6 B8 B8 B8 B8 B8 B8 B8
    19 A11, B11 B11 A11, B11 A11, B11 B12 A12, B12 A10, B10 B12 A11, B11 A10
    20 B7 A7, B7 B11 A11, B11 B10 B11
    Power Pin Reference
    Click to enlarge - blue dot
    C       A12, B12 A12, B12 A12, B12 A12, B12 A12, B12 A10, B10 A10, B10
    D A7, A11, B7, B11 A7, A11, B7, B11 A7, A11, B7, B11 A11, B11 A11, B11 A11, B11 A10, B10 A10, B10 A11, B11 A11, B11
    E A9, B9 A9, B9 A9, B9 A9, B9 A9, B9 A9, B9 A9, B9 A9, B9 A9, B9 A9, B9
      

    Click to enlarge - 16-pt_miniplus_12-pin


    Click to enlarge - 16-pt_PC


    Modules for 16 Outputs (M23)

    Click to enlarge - 01059001


    Features:

  • Direct connection to common 16 point output cards.


  • AC and DC versions with color coded ring for voltage indication.


  • LED power indicator.


  • Rugged durable construction.


  • Provides pre-wired connectivity from field device to PLC output module.


  • Specifications

    Cat. No. 1667-16OD2201T  1667-16OD2202 1667-16OD2203 1667-16OD2204 1667-16OD2205
    Number of Pins 12
    Field Connector Style M23 Metric 23mm
    Voltage Rating 10...265V DC
    Number of Points 16
    Degree of Protection IP65 Type 1, 4, 4X, 12
    Maximum Peak Voltage¬  600Vp
    Maximum Current (per Circuit) 2 A
    Maximum Current (per Module) 12 A
    Indicator Circuit Current (Nominal) 2 mA
    No. of Terminals per Device Column 2
    Operating Temperature Range 0°...+60°C (32°…140°F)
    Non-Condensing
    Certifications
  • cULus Listed (File E113724 Guide NRAQ)

  • CE
  • Power Supply Connector Specifications
    Wire Range (Rated Cross Section) #22...#12 AWG (0.2...4 mm2)
    Wire Strip Length 0.32 in. (8 mm)
    Recommended Tightening Torque 4.5...5.5 lb.-in. (0.50...0.60 N•m)
      
    ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5kV withstand.
    T When using 1667-Oxx PanelConnect modules with bulletin 1762 MicroLogix 1200 embedded or Bulletin 1764 MicroLogix 1500 base I/O, the Bulletin 1667 module current ratings are lower. Refer toTable X, .

    Application Notes

    Distribution Block Connection

    Match I/O Program to Distribution Block outputs in the sequence shown below:

    Click to enlarge - EXPANSION BLOCK_2wss


    1.  Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.

    2.  Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.

    3.  Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.


    Panel Connections
    Field Side Connector—12-Pin M23
    Click to enlarge - cross box
    Output Connector Pin Reference DC DC DC DC DC
    1667-16OD2201 1667-16OD2202 1667-16OD2203 1667-16OD2204 1667-16OD2205
    Click to enlarge - blue dot
    1 A11, B11 A11 A11, B11 A1, B1 A1, B1
    2 A9, A10 A3, B3
    3 A1 A1 A1 A4 A4
    4 A2 A2 A2 A5 A5
    5 A3 A3 A3 A6 A6
    6 A4 A4 A4 A7 A7
    7 A5 A5 A5 A8 A8
    8 A6 A6 A6 A9 A9
    9 A7 A7 A7 A10 A10
    10 A8 A8 A8 A11 A11
    11 B1 B1 B1 B4 B4
    12 B2 B2 B2 B5 B5
    13 B3 B3 B3 B6 B6
    14 B4 B4 B4 B7 B7
    15 B5 B5 B5 B8 B8
    16 B6 B6 B6 B9 B9
    17 B7 B7 B7 B10 B10
    18 B8 B8 B8 B11 B11
    19 A9, A10 B11 A11, B11 A3, B3 A1, B1
    20 B9, B10 B9, B10 A9,A10, B9, B10 A3, B3
    Power Pin Reference
    C A11, B11 A11, B11 A11, B11 A1, B1 A1, B1
    D A9, A10, B9, B10 A9, A10, B9, B10 A9, A10, B9, B10 A3, B3 A3, B3
    E A12, B12 A12, B12 A12, B12 A12, B12 A12, B12

    Click to enlarge - 16-pt_m23_12-pin


    Click to enlarge - 16-pt_PC


    1667-32OD1201 (32-Point Output)

    Click to enlarge - 03019001_1667-32ID1201-Gray


    1667-32OD1201 Specifications

    Main PanelConnect Connector Number of pins 12
    Style Mini-Plus 1-1/8 in.
    Number of points 32
      

    Degree of Protection IP65
    Type 1, 4, 4X, 12
    Voltage Rating 10…30V DC
    Maximum Peak Voltage¬  600Vp
    Maximum Current (per Circuit) 2 A
    Maximum Current (per Module) 12 A
    Indicator Circuit Current (Nominal) 2 mA
    No. of Terminals per Device Common 2
    Operating Temperature Range 0…+60×C
    Non-Condensing
    Certifications
  • cULus Listed (File E113724 Guide NRAQ)

  • CE
  •   
    ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5 kV withstand.

    Click to enlarge - black dot Power Supply Connector Specification
    Wire Range (Rated Cross Section) #22…#12 AWG (0.2…4 mm2)
    Wire Strip Length 0.32 in. (8 mm)
    Recommended Tightening Torque 4.5…5.5 lb.-in. (0.50…0.60 Nm)

    Distribution Block Connection

    Match I/O Program to Distribution Block outputs in the sequence shown below:

    Pinout

    Click to enlarge - Front_12-pin-32-point-Mini-plus-with-callouts


    Click to enlarge - 32-pointPanelConnectPLCPwrContRear


    Panel Connections
    Connector Pin Reference Field Side Connector Connector Pin Reference Field Side Connector
    Click to enlarge - cross box Click to enlarge - blue dot Click to enlarge - cross box Click to enlarge - blue dot
    1 A12, B12, C12, D12 21 B1
    2 22 D1
    3 23 B2
    4 24 D2
    5 A1 25 B3
    6 C1 26 D3
    7 A2 27 B4
    8 C2 28 D4
    9 A3 29 B5
    10 C3 30 D5
    11 A4 31 B6
    12 C4 32 D6
    13 A5 33 B7
    14 C5 34 D7
    15 A6 35 B8
    16 C6 36 D8
    17 A7 37 A11, B11, C11, D11
    18 C7 38
    19 A8 39
    20 C8 40
    Power Pin Reference
    Click to enlarge - black dot
        C A12, B12
        D A11, B11, C11, D11
        E A9, B9, C9, D9

    Application Notes

    1.   Compatibility — To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.

    2.   Wiring — Refer to the label section on [BAD REF 202766 ].

    3.   Dimensions — Refer to 16-Point PanelConnect Input or Output Module Dimensions.


    Click to enlarge - EXPANSION BLOCK_2wss


    Note:For configuring to double solenoid valves, refer to Table 6. Distribution Boxes for Distribution Box connections.

    Table X. PLC-Specific Current Ratings

    Cat. No. Current/Circuit Current/Module Indicator Circuit Current Operating Temperature Range
    1762-40AWA (Outputs) ¬  0.25 A 4.0 A 2 mA 0°…60°C
    1762-40BWA (Outputs) ¬ 
    1762-40BXB (Outputs) ¬ 
    1764-24AWA (Outputs) ¬  0.5 A (Outputs 0…4)
    0.25 A (Outputs 4…11)
    1764-24BWA (Outputs) ¬ 
    1764-28BXB (Outputs) ¬  2.0 A (Outputs 0…1)
    0.6 A (Outputs 2…7)
    1.0 A (Outputs 8…11)
      
    ¬ Refer to Bulletin 1762 and 1764 literature for output voltage ratings.