Connection Systems

Catalogs > Industrial Controls Catalog > Connection Systems > Panel Connection Systems

Panel Connection Systems

Description PanelConnect System View PanelConnect Input Features Product Selection — Input Modules PanelConnect™ Specifications Modules for 16-Point Inputs Pre-Wired Cables for Input PanelConnect
PanelConnect Output Features and Typical Configuration Product Selection — Output Modules Digital PanelConnect™ Output Specifications Digital PanelConnect™ Modules for Outputs Pre-Wired Cables for Output PanelConnect™ Combination PanelConnect Features Selecting Combination Products
Digital PanelConnect™ Combination Specifications Accessories Fuse Modules PanelConnect Digital, Option Module Cable Specifications 16-Point PanelConnect Input or Output Module Dimensions Pneumatic Valve Wiring Reference Guide
Modules for 16-Point Inputs

Click to enlarge - 01059002


Click to enlarge - 01059002


Features:

  • Direct connection to common 16-point PLC input modules.


  • AC and DC versions with color coded ring for voltage indication.


  • LED power indicator.


  • Rugged durable construction.


  • Provides prewired connectivity from on-machine sensor field device to PLC input modules.


  • Specifications

    Cat. No. 1667-161A1008 1667-16ID1001 1667-16ID1004 1667-16IA1207 1667-16ID1201 1667-16ID1212 1667-16ID2206 1667-16ID2211
    Field Connector: Number of Pins and Style 10-Pin Mini Plus (1-1/8 in.) 12-Pin Mini Plus
    (1-1/8 in.)
    12-Pin M23 Metric 23 mm
    Voltage Rating 10-265V AC 10-265V DC 10-265V DC 10-265V AC 10-265V DC 10-265V DC 10-265V DC 10-265V DC
    Module Type 16 Input
    Degree of Protection IP65; Type 1, 4, 4X, 12
    Maximum Peak Voltage¬  600Vp
    Maximum Current (per Circuit) 2 A
    Maximum Current (per Module) 12 A
    Indicator Circuit Current (Nominal) 2 mA
    No. of Terminals per Device Common 2
    Operating Temperate Range 0°C…+60°C (32°F…+140°F) Noncondensing
    Certifications cULus Listed (File E113724 Guide NRAQ)
    CE
    Power Supply Connector Specification
    Wire Range (Rated Cross Section) #22…#12 AWG
    (0.2…4 mm2)
    Wire Strip Length 8 mm (0.32 in.)
    Recommended Tightening Torque 0.50…0.60 N•m
    (4.5…5.5 lb-in.)

    ¬ Transient voltage greater than 600Vp use a UL Recognized suprpression device rated at 2.5kV withstand.


    Application Notes

    1.  Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.

    2.  Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.

    3.  Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.


    Distribution Block Connection

    Match I/O Program to Distribution Block Outputs in the sequence shown below:

    Click to enlarge - distributionblockconnection


    PanelConnect Pin to Field-Side Connections

    Input Connector Pin Reference Field-Side Connector—10-Pin Mini Click to enlarge - x_box Field-Side Connector—12-Pin Mini Click to enlarge - x_box Field-Side Connector—M23 12-Pin
    AC DC DC AC DC DC DC DC
    1667-16IA1008 1667-16ID1001 1667-16ID1004 1667-16IA1207 1667-16ID1201 1667-16ID1212 1667-16ID2206 1667-16ID2211
    Click to enlarge - blue dot
    1 A10,B10 A8,B8 A7,B7 A11,B11 A12,B12 A9,A10, B9. B10 A11, B11
    2
    3 A7 A7 A7 A10 A1 A1 A1 A1
    4 A1 A1 A1 A1 A2 A2 A2 A2
    5 A9 A9 A9 A12 A3 A3 A3 A3
    6 A2 A2 A2 A2 A4 A4 A4 A4
    7 A3 A3 A3 A3 A5 A5 A5 A5
    8 A4 A4 A4 A4 A6 A6 A6 A6
    9 A5 A5 A5 A5 A7 A7 A7 A7
    10 A6 A6 A6 A6 A8 A8 A8 A8
    11 B7 B7 B7 B10 B1 B1 B1 B1
    12 B1 B1 B1 B1 B2 B2 B2 B2
    13 B9 B9 B9 B12 B3 B3 B3 B3
    14 B2 B2 B2 B2 B4 B4 B4 B4
    15 B3 B3 B3 B3 B5 B5 B5 B5
    16 B4 B4 B4 B4 B6 B6 B6 B6
    17 B5 B5 B5 B5 B7 B7 B7 B7
    18 B6 B6 B6 B6 B8 B8 B8 B8
    19 A10, B10 A10,B10 A8,B8 A7,B7 A11,B11 A12,B12 A9, A10, B9, B10 A11, B11
    20
    Power Pin Reference
    C A10, B10 A10, B10 A10, B10 A11, B11 A12, B12 A12, B12 A11, B11 A11, B11
    D A8, B8 A8, B8 A7, B7 A11, B11 A11, B11 A9, A10, B9, B10 A9, A10, B9, B10
    E A8, B8 A9, B9 A9, B9 A9, B9 A12, B12 A12, B12

    1.  Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.

    2.  Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.

    3.  Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.


    Modules for 32-Point Inputs

    Click to enlarge - 03019003_1667-32ID1001-Gray


    Click to enlarge - 03019003_1667-32ID1001-Gray


    Features:

  • Direct connection to common 32-point PLC Input Modules.


  • LED power indicator.


  • Rugged durable construction.


  • Provides prewired connectivity from On-Machine Sensor field device to PLC Input Module.


  • Specifications

    Catalog Number 1667-32ID1001 1667-32ID1201
    Field Connector: No. pins Style 10-Pin Mini Plus (1-1/8 in.) 12-Pin Mini Plus (1-1/8 in.)
    Voltage Rating 10-30V DC
    Module Type 32 Input
    Degree of Protection IP65; Type 1, 4, 4X, 12
    Maximum Peak Voltage¬  600Vp
    Maximum Current (per Circuit) 2 A
    Maximum Current (per Module) 12 A
    Indicator Circuit Current (Nominal) 2 mA
    No. of Terminals per Device Common 2
    Operating Temperature Range 0°C…+60°C (32°F…140°F) Noncondensing
    Certifications
  • cULus Listed (File E113724 Guide NRAQ)

  • CE
  • Power Supply Conector Specification  
    Wire Range (Rated Cross Section) #22...#12 AWG (0.2...4 mm2)
    Wire Strip Length 0.32 in. (8 mm)
    Recommended Tightening Torque 4.5...5.5lb.-in. (0.50...0.60 N•m)
        
    ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5kV withstand.

    Application Notes

    Distribution Block Connection

    Match I/O Program to Distribution Block Outputs in the sequence shown below:

    Click to enlarge - distributionblockconnection2


    1.  Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.

    2.  Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.

    3.  Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.


    Panel Connections
    Input Connector Field-Side
    Connector—10-Pin
    Field-Side
    Connector—12-Pin
    Input Connector Field-Side
    Connector—10-Pin
    Field-Side
    Connector—12-Pin
    Click to enlarge - x_box Click to enlarge - x_box Click to enlarge - x_box Click to enlarge - x_box
    DC DC DC DC
    Click to enlarge - blue dot 1667-32ID1001 1667-32ID1201 Click to enlarge - blue dot 1667-32ID1001 1667-32ID1201
    1 A8, B8, C8, D8 A11, B11, C11, D11 23 B1 B2
    2 24 D1 D2
    3 25 B9 B3
    4 26 D9 D3
    5 A7 A1 27 B2 B4
    6 C7 C1 28 D2 D4
    7 A1 A2 29 B3 B5
    8 C1 C2 30 D3 D5
    9 A9 A3 31 B4 B6
    10 C9 C3 32 D4 D6
    11 A2 A4 33 B5 B7
    12 C2 C4 34 D5 D7
    13 A3 A5 35 B6 B8
    14 C3 C5 36 D6 D8
    15 A4 A6 37 A8, B8, C8, D8 A11, B11, C11, D11
    16 C4 C6 38
    17 A5 A7 39
    18 C5 C7 40
    19 A6 A8 Power Pin Reference
    20 C6 C8 C A10, B10, C10, D10 A12, B12, C12, D12
    21 B7 B1 D A8, B8, C8, D8 A11, B11, C11, D11
    22 D7 D1 E A9, B9, C9, D9