Catalogs > Industrial Controls Catalog > Connection Systems > Panel Connection Systems
Panel Connection Systems
| Description | PanelConnect System View | PanelConnect Input Features | Product Selection — Input Modules | PanelConnect™ Specifications | Modules for 16-Point Inputs | Pre-Wired Cables for Input PanelConnect |
|
|
Features:
Specifications
| Cat. No. | 1667-161A1008 | 1667-16ID1001 | 1667-16ID1004 | 1667-16IA1207 | 1667-16ID1201 | 1667-16ID1212 | 1667-16ID2206 | 1667-16ID2211 |
| Field Connector: Number of Pins and Style | 10-Pin Mini Plus (1-1/8 in.) | 12-Pin Mini Plus (1-1/8 in.) |
12-Pin M23 Metric 23 mm | |||||
| Voltage Rating | 10-265V AC | 10-265V DC | 10-265V DC | 10-265V AC | 10-265V DC | 10-265V DC | 10-265V DC | 10-265V DC |
| Module Type | 16 Input | |||||||
| Degree of Protection | IP65; Type 1, 4, 4X, 12 | |||||||
| Maximum Peak Voltage¬ | 600Vp | |||||||
| Maximum Current (per Circuit) | 2 A | |||||||
| Maximum Current (per Module) | 12 A | |||||||
| Indicator Circuit Current (Nominal) | 2 mA | |||||||
| No. of Terminals per Device Common | 2 | |||||||
| Operating Temperate Range | 0°C…+60°C (32°F…+140°F) Noncondensing | |||||||
| Certifications | cULus Listed (File E113724 Guide NRAQ) CE |
|||||||
| Power Supply Connector Specification | ||||||||
| Wire Range (Rated Cross Section) | #22…#12 AWG (0.2…4 mm2) |
|||||||
| Wire Strip Length | 8 mm (0.32 in.) | |||||||
| Recommended Tightening Torque | 0.50…0.60 Nm (4.5…5.5 lb-in.) |
|||||||
¬ Transient voltage greater than 600Vp use a UL Recognized suprpression device rated at 2.5kV withstand.
Application Notes
1. Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.
3. Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.
Distribution Block Connection
Match I/O Program to Distribution Block Outputs in the sequence shown below:
|
PanelConnect Pin to Field-Side Connections
1. Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.
3. Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.
Modules for 32-Point Inputs
|
|
Features:
Specifications
| Catalog Number | 1667-32ID1001 | 1667-32ID1201 | |
| Field Connector: No. pins Style | 10-Pin Mini Plus (1-1/8 in.) | 12-Pin Mini Plus (1-1/8 in.) | |
| Voltage Rating | 10-30V DC | ||
| Module Type | 32 Input | ||
| Degree of Protection | IP65; Type 1, 4, 4X, 12 | ||
| Maximum Peak Voltage¬ | 600Vp | ||
| Maximum Current (per Circuit) | 2 A | ||
| Maximum Current (per Module) | 12 A | ||
| Indicator Circuit Current (Nominal) | 2 mA | ||
| No. of Terminals per Device Common | 2 | ||
| Operating Temperature Range | 0°C…+60°C (32°F…140°F) Noncondensing | ||
| Certifications | |||
| Power Supply Conector Specification | |||
| Wire Range (Rated Cross Section) | #22...#12 AWG (0.2...4 mm2) | ||
| Wire Strip Length | 0.32 in. (8 mm) | ||
| Recommended Tightening Torque | 4.5...5.5lb.-in. (0.50...0.60 Nm) | ||
| ¬ Transient voltage greater than 600Vp use a UL Recognized suppression device rated at 2.5kV withstand. | |||
Application Notes
Distribution Block Connection
Match I/O Program to Distribution Block Outputs in the sequence shown below:
|
1. Compatiblity- To ensure proper operation with the I/O module, do not exceed the voltage and current ratings of the PanelConnect Module.
2. Wiring- Refer to the label section Pneumatic Valve Wiring Reference Guide.
3. Dimensions- Refer to 16-Point PanelConnect Input or Output Module Dimensions.