Manual Motor Controller / Supplementary Protector

Click to enlarge - 1492-CB-BC_1-1_sm2


Bulletin 1492-CB — Supplementary Protector/Miniature Circuit Breaker - DC Loads


Product Overview

Bulletin 1492-CB devices are specifically rated for DC with trip curves, DF, DG and DH. Screw termination is standard on all Bulletin 1492-CB units. Both line and load side terminals accept #16…4 AWG (1.5…25 mm2) copper wire.

Bulletin 1492-CB are “energy limiting” thermal magnetic type overcurrent protectors meeting UL 1077/CSA C22.2 No. 235, IEC/EN 60934. These devices are designed for the protection of a wide variety of products including:


Trip Curves

Click to enlarge - 1492-CB-BC_26-1 Click to enlarge - 1492-CB-BC_26-2 Click to enlarge - 1492-CB-BC_26-3
Multiple of Rated Current (xIn)DF-Trip Curve
4.5…8
Multiple of Rated Current (xIn)DG-Trip Curve
9.0…16
Multiple of Rated Current (xIn)DH-Trip Curve
18…32

Standards Compliance and Certifications

Standards Compliance


Certifications


Tripping Characteristic DF Trip
Resistive or Slightly
Inductive
DG Trip
Inductive
DH Trip
Highly Inductive
4.5…8 In 9…16 In 18…32 In
Number of Poles Continuous Current Rating
(In) [A]
Cat. No. Cat. No. Cat. No.
1-Pole
1 Piece per Carton
0.5 1492-CB1DF005 1492-CB1DG005
1 1492-CB1DF010 1492-CB1DG010
Click to enlarge - 1492-CB-BC_18-1 2 1492-CB1DF020 1492-CB1DG020
3 1492-CB1DF030 1492-CB1DG030
4 1492-CB1DF040 1492-CB1DG040
5 1492-CB1DF050 1492-CB1DG050
6 1492-CB1DF060 1492-CB1DG060 1492-CB1DH060
7 1492-CB1DF070 1492-CB1DG070 1492-CB1DH070
8 1492-CB1DF080 1492-CB1DG080 1492-CB1DH080
10 1492-CB1DF100 1492-CB1DG100 1492-CB1DH100
12 1492-CB1DF120 1492-CB1DG120 1492-CB1DH120
15 1492-CB1DF150 1492-CB1DG150 1492-CB1DH150
Click to enlarge - 1492-CB-BC_18-3 16 1492-CB1DF160 1492-CB1DG160 1492-CB1DH160
20 1492-CB1DF200 1492-CB1DG200 1492-CB1DH200
25 1492-CB1DF250 1492-CB1DG250 1492-CB1DH250
30 1492-CB1DF300 1492-CB1DG300 1492-CB1DH300
32 1492-CB1DF320 1492-CB1DG320 1492-CB1DH320
40 1492-CB1DF400 1492-CB1DG400 1492-CB1DH400
  

Tripping Characteristic DF Trip
Resistive or Slightly
Inductive
DG Trip
Inductive
DH Trip
Highly Inductive
4.5…8 In 9…16 In 18…32 In
Number of Poles Continuous Current Rating
(In) [A]
Cat. No. Cat. No. Cat. No.
2-Pole
1 Piece per Carton
0.5 1492-CB2DF005 1492-CB2DG005
1 1492-CB2DF010 1492-CB2DG010
Click to enlarge - 1492-CB-BC_18-2 2 1492-CB2DF020 1492-CB2DG020
3 1492-CB2DF030 1492-CB2DG030
4 1492-CB2DF040 1492-CB2DG040
5 1492-CB2DF050 1492-CB2DG050
6 1492-CB2DF060 1492-CB2DG060 1492-CB2DH060
7 1492-CB2DF070 1492-CB2DG070 1492-CB2DH070
8 1492-CB2DF080 1492-CB2DG080 1492-CB2DH080
10 1492-CB2DF100 1492-CB2DG100 1492-CB2DH100
12 1492-CB2DF120 1492-CB2DG120 1492-CB2DH120
15 1492-CB2DF150 1492-CB2DG150 1492-CB2DH150
Click to enlarge - 1492-CB-BC_18-4 16 1492-CB2DF160 1492-CB2DG160 1492-CB2DH160
20 1492-CB2DF200 1492-CB2DG200 1492-CB2DH200
25 1492-CB2DF250 1492-CB2DG250 1492-CB2DH250
30 1492-CB2DF300 1492-CB2DG300 1492-CB2DH300
32 1492-CB2DF320 1492-CB2DG320 1492-CB2DH320
40 1492-CB2DF400 1492-CB2DG400 1492-CB2DH400
  

Accessories

Description Cat. No.
Auxiliary Contacts Auxiliary Contact Module
Switches when protective device is operated manually or tripped electrically 1 N.O. Contact
1492-ACBH1
Auxiliary Contact Module
Switches when protective device is operated manually or tripped electrically 1 N.C. Contact
1492-ACBH2
Signal Alarm Contact Module
Trip indicating contact switches only when the protective device is tripped electrically 1 N.O. Contact
1492-ACBS1
Signal Alarm Contact Module
Trip indicating contact switches only when the protective device is tripped electrically 1 N.C. Contact
1492-ACBS2
Shunt Trip Module Shunt Trip Module
Use the Shunt Trip Module to trip the adjacent breaker poles from a remote location. The module is actuated by applying a voltage (pick-up voltage) to the trip terminals.
  • Shunt Trip Modules are often used in emergency shutdown circuits where multiple power circuits must be switched off from a single location.
  • 5…12V AC/DC 1492-ACBA1
    10…24V AC/DC 1492-ACBA2
    20…48V AC/DC 1492-ACBA3
    40…110V AC/DC 1492-ACBA4
    90…240V AC/DC 1492-ACBA5
      Pieces Per Package Cat. No.
    DIN (#3) Symmetrical Rail
    35 x 7.5 x 1 m
    10 199-DR1
    End Anchor 10 1492-EAH35
    Lockout Attachment 5 1492-ACBLOA
    Bus Bars See for Pin Style Bus Bars
      

    Click to enlarge - revised_busbar_ratings

    Specifications

    Description DF Curve DG Curve DH Curve
    Tripping Characteristic Resistive or Slightly-Inductive Loads Inductive Loads Highly-Inductive Loads
    4.5…8 In 9…16 In 18…32 In
    Dielectric Strength 1960V AC
    Shock 25 G Half Sine Wave for 11 ms (3 axes)
    Vibration Frequency Range: 10…500 Hz
    Max. Amplitude (p-p) = 0.030 in.
    Max. Acceleration = 5 G
    1 hour each of 3 axes
    Operating Temperature Range –40…+140 °F (–40…+60 °C) non-condensing
    Shipment and Short-Term Temperature Limits –40…+185 °F (–40…+85 °C)
    Housing Material Melamine-Phenolic
    Wire Size #16…4 AWG (1.0…25 mm2)
    Recommended Wire Strip Length 0.51 in. (13 mm)
    Electromechanical Life at 240V AC Up to 6 A, 50 000 cycles
    7…16 A, 30 000 cycles
    20…32 A, 20 000 cycles
    40…50 A, 12 000 cycles
    Auxiliary Contact Rating
    Signal Contact Rating
    277V AC, 6 A
    125V AC, 1 A
    50V DC, 6 A
    1-Pole 10 kA @ 120V DC U1 10 kA @ 120V DC U1 5 kA @ 240V DC U1
    2-Pole in Series 10 kA @ 240V DC U1 10 kA @ 240V DC U1 5 kA @ 240V DC U1
      

    Approximate Dimensions

    Dimensions are shown in inches (millimeters). Dimensions are not intended for manufacturing purposes.

    Click to enlarge - 1492-CB-BC_29-1


    Number of Poles and Accessories 1 2 3 4 5
    Width (inches) 0.7 1.4 2.1 2.8 3.5
    Width (millimeters) 17.8 35.6 53.3 71.1 88.9
      
    Note: Accessories and one pole width are identical.