Catalogs > Industrial Controls Catalog > Control Circuit and Load Protection > Miniature Circuit Breakers / Supplemental Protectors > Manual Motor Controller / Supplementary Protector
Manual Motor Controller / Supplementary Protector
| Introduction | Standards Compliance and Certifications | Product Selection | Accessories | Specifications | Approximate Dimensions |
| Description | DF Curve | DG Curve | DH Curve |
| Tripping Characteristic | Resistive or Slightly-Inductive Loads | Inductive Loads | Highly-Inductive Loads |
| 4.5…8 In | 9…16 In | 18…32 In | |
| Dielectric Strength | 1960V AC | ||
| Shock | 25 G Half Sine Wave for 11 ms (3 axes) | ||
| Vibration | Frequency Range: 10…500 Hz Max. Amplitude (p-p) = 0.030 in. Max. Acceleration = 5 G 1 hour each of 3 axes |
||
| Operating Temperature Range | 40…+140 °F (40…+60 °C) non-condensing | ||
| Shipment and Short-Term Temperature Limits | 40…+185 °F (40…+85 °C) | ||
| Housing Material | Melamine-Phenolic | ||
| Wire Size | #16…4 AWG (1.0…25 mm2) | ||
| Recommended Wire Strip Length | 0.51 in. (13 mm) | ||
| Electromechanical Life at 240V AC | Up to 6 A, 50 000 cycles 7…16 A, 30 000 cycles 20…32 A, 20 000 cycles 40…50 A, 12 000 cycles |
||
| Auxiliary Contact Rating Signal Contact Rating |
277V AC, 6 A 125V AC, 1 A 50V DC, 6 A |
||
| 1-Pole | 10 kA @ 120V DC U1 | 10 kA @ 120V DC U1 | 5 kA @ 240V DC U1 |
| 2-Pole in Series | 10 kA @ 240V DC U1 | 10 kA @ 240V DC U1 | 5 kA @ 240V DC U1 |