Catalogs > Industrial Controls Catalog > Control Circuit and Load Protection > Circuit Breakers > Bulletin 1489 DC Circuit Breaker
Bulletin 1489 DC Circuit Breaker
| Product Overview |
|
Bulletin 1489-D Circuit Breakers
- Specially designed for higher voltage DC circuits with a permanent magnet to direct the arc into the arc splitters.
- Field-mountable options for selective applications
- IP2x Finger-Protection (Front)
- North America certifications: UL 489, CSA C22.2 No. 5
- International standards: CE Marked for IEC 60947-2 standards for worldwide acceptance
- 10 kA interrupt rating
- UL/CSA — 1 pole: max. 125V DC, 2 pole: max. 250V DC
IEC — 1 pole: max. 250V DC, 2 pole: max. 500V DC
- A positively trip-free mechanism (breaker operation cannot be defeated by holding the handle in the ON position)
- Trip curves: C
- Superior shock and vibration resistance capabilities — helps to prevent nuisance tripping
- Mounts on DIN Rail
- Wire connect, follow polarity requirements
Industrial Circuit Breakers for North American Applications
- Field mountable options for selective applications
- IP2x Finger-Protection (Front)
- North America certifications: UL 489, CSA 22.2 No. 5
- International standards: CE Marked for IEC 60947-2 standards for worldwide acceptance
- 10 kA interrupt rating
- UL/CSA — 1 pole: max. 125V DC, 2 pole: max. 250V DC
IEC — 1 pole: max. 250V DC, 2 pole: max. 500V DC
- A positively trip-free mechanism (breaker operation cannot be defeated by holding the handle in the ON position)
- Trip curves: C
- Superior shock and vibration resistance capabilities — helps to prevent nuisance tripping
- Mounts on DIN Rail
- Wire connect, line and load (reversible)
- Follow polarity requirements.
The Bulletin 1489-D line includes:
- UL 489, CSA C22.2 No. 5
- 1 pole, 125V DC, 2...40 A
2 pole, 250V DC, 2...40 A
- Miniature Circuit Breaker for EN/IEC Applications
EN/IEC 60947-2
1 pole, 250V DC, 2...40 A
2 pole, 500V DC, 2...40 A
Miniature Circuit Breaker for IEC Applications:
1 pole, 250V DC, 2...40 A
2 pole, 500V DC, 2...40 A
Standards Compliance
-
UL 489
CSA C22.2 No. 5
EN/IEC 60947-2
Certifications
-
UL Listed
CSA Certified
CE Marked
Features
- Designed manufactured and listed to UL 489 (CSA 22.2 No. 5)
- Thermal-magnetic protection
- up to 10 kA Interrupting rating
- Finger-safe design (front)
- DIN Rail mounting
- Line and load wire connections
- Follow polarity requirements