| Standards Compliance
|
UL 489, CSA C22.2 No. 5.1
|
| Certifications
|
UL Listed, CSA Certified
|
| Rated Voltage
|
120/240V AC, 240V AC
|
| Continuous Current rating @ 40°C (104°F)
|
10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 70, 80 90, 100 Amp
|
| Rated short circuit capability
|
10 kA 120/240V AC and 240V AC 14 kA 480Y/277V AC
|
| Degree of protection
|
Open Device 1/2 in. wide circuit breakers are finger safe from front per IEC. Terminal Covers available for 1 in. wide circuit breaker at 120/240 and 240V AC.
|
| Mounting
|
DIN Rail (check product for specific)
|
| Operating Temperature
|
0…60°C (32...140°F) (non-condensing)
|
| Shipment and short term storage limits
|
-40°C…+80°C (-40...176°F)
|
| Wire Size
|
See Terminal Table
|
| Terminal Torque
|
See Terminal Table
|
| Recommended Wire Strip Length
|
See Terminal Table
|
|
|
| Cat. No.
|
Continuous Current Rating
|
Wire Type
|
Wire Range [AWG]
|
Terminal Torque
|
Line Strip Length
|
Line and Load Terminals
|
| 1492-MCAAxxx
|
10…60 A
|
Copper (Cu)
|
14…10
|
20 lbin. (2.3 Nm)
|
7/16 in.
|
|
| 8
|
25 lbin. (2.8 Nm)
|
| 6…4
|
27 lbin. (3.0 Nm)
|
| 1492-MCBAxxx
|
35…60 A
|
14…10
|
20 lbin. (2.3 Nm)
|
1/8 in. Allen Head
|
| 8…4
|
32 lbin. (3.6 Nm)
|
|
| 70…100 A
|
4…1/0
|
50 lbin. (5.6 Nm)
|
| 1492-MCEAxxx
|
15…50 A
|
14…10
|
20 lbin (2.3 Nm)
|
9/16 in.
|
Line
|
| 8
|
25 lbin (2.8 Nm)
|
—
|
|
| 1492-MCGAxxx
|
6…4
|
27 lbin (3.0 Nm)
|
—
|
Load
|
|
|
|