Bulletin 1489 Circuit Breaker

Product Overview


Click to enlarge - 1489 single


Bulletin 1489 Circuit Breakers


Industrial Circuit Breakers for North American Applications


The Bulletin 1489 line includes:


Miniature Circuit Breaker for IEC Applications:
    415V AC 0.5...40 A


Standards Compliance


Certifications


Features


Description

Bulletin 1489 Circuit Breakers for Branch Circuit protection are available in 1-, 2-, and 3-pole construction and are rated 0.5...40 A at 240V AC and 0.5...32 A at 480Y/277V AC for North American applications (UL 489 and CSA C22.2 No. 5). The circuit breakers also have a 1-pole 48V DC, 2-pole (series) 96V DC rating. For EN\IEC applications the products are rated 415V AC, 48V AC 0.5...40 A.

Thermal Magnetic Circuit Breakers

The Bulletin 1489 Thermal Magnetic Circuit Breakers are general-purpose devices suitable for the majority of industrial, inverse time circuit breaker applications.

They combine thermal and magnetic trip actions and provide accurate overload and short-circuit protection for conductors and connected equipment.


Circuit Breaker Application Information

Selection of a Bulletin 1489 circuit breaker with appropriate circuit protection includes consideration of:



  • Circuit Voltage


  • Circuit Frequency


  • Available Short Circuit Current


  • Continuous Current Rating


  • Application Considerations


  • Special Operating Conditions




  • The following discussion is based upon National Electric Code and UL requirements. Similar considerations are appropriate for Canadian applications.


    Circuit Voltage

    The Bulletin 1489 circuit breakers are rated by voltage class. Applications should not exceed the listed voltage and current range (see Table 1).

    Circuit Frequency

    The Bulletin 1489 circuit breakers may be applied to frequencies of 50 Hz and 60 Hz without derating. For applications above 60 Hz, contact Rockwell Automation with specific application information for the derating of the circuit breakers.

    Available Short Circuit Current

    The Bulletin 1489 circuit breakers should only be applied in those applications in which the available short-circuit (or fault) current is less than or equal to 10 kA...14 kA (US/Canada) and 15 kA (IEC).

    Table 1. Voltage and Current Ranges

    Region Max. Voltage Current Range [A]
    EN/IEC Regions 415V AC 0.5...40
    48V DC 0.5...40
    North America (UL 489 & CSA C22.2 No. 5) 240V AC 0.5...40
    480Y/277V AC 0.5...32
    1-pole 48V DC 0.5...40
    2-pole 96V DC 0.5...40
      

    Continuous Current Rating

    Standard current ratings are: 0.5, 1, 1.5, 2, 3, 4, 5, 6, 7, 8, 10, 15, 16, 20, 25, 30, 32, 35, and 40 A.



    The Bulletin 1489 circuit breakers are rated in RMS amperes at a 40 °C (104 °F) ambient temperature per the UL 489 (CSA 22.2 No. 5) standard. This temperature is generally used as the average temperature within an industrial enclosure. If a circuit breaker is applied in a temperature that exceeds the 40 °C (104 °F) ambient, then the circuit breaker should be derated. For IEC 60 947-2 standard, the products carry an ambient rating of 30 °C. Follow standard IEC application considerations for temperature rating in different ambient temperatures.



    The characteristic trip curves are shown on . The trip bands shown for each breaker represent current tripping limits for a circuit breaker and are within the limits established by UL. For a specific current at 40 °C (104 °F), a circuit breaker will open ("clear the circuit") automatically at some total time that will be within the "Minimum" and "Maximum" time shown on the curves. For example, page shows that a one-pole, 15 A, Bulletin 1489 circuit breaker trips in not less than 10 s and not more than 120 s on a 30 A current. Because the UL standard defines this time spread, users should not specify exact tripping time. The lower current portion of the curves (upper left) depict the time to trip due to thermal action and reflect overload protection of the wire and connect load. The higher current portion of the curves (lower right) depicts the trip due to magnetic action of the circuit breaker and reflects protection due to short circuit level currents.


    Application Considerations

    The following is a discussion of application considerations related to North American applications. When applying product to IEC regional requirements, follow IEC practices and guidelines.



    The selection of a specific ampere rating for a specific application is dependent on the type of load and duty cycle and is governed by the National Electric Code (Canadian Electric Code) and UL/CSA. In general, the codes require that overcurrent protection is at the current supply and at points where wire sizes are reduced. In addition, the codes state that conductors be protected according to their current carrying capacity. There are specific situations that require application consideration, such as motor circuit, and guidelines for the selection for transformer protection.



    The Bulletin 1489 circuit breakers are “non 100 percent rated” as defined by UL 489, para 7.1.4.2. As such, the circuit breaker's rating should be loaded to no more than 80% if used with continuous loads.



    Line and load may be reversed. The Bulletin 1489 circuit breaker may be bottom fed.


    Branch Circuits:

    Bulletin 1489 circuit breakers may be used to protect branch circuits. A branch circuit is the wiring portion of a system extending beyond the final overcurrent device protecting the circuit.

    Guidelines established in NEC, CEC, UL, and CSA should be used to determine the specific device. For example:



    1) Motor Branch Circuit

    Bulletin 1489 circuit breakers are not horsepower rated because they are able to safely interrupt currents far in excess of the locked rotor value for a selected motor. This ability is recognized in the codes and standards and is also established by the UL and CSA tests described in UL 489 and CSA C22.2 No. 5 standards.

    The size of a Bulletin 1489 circuit breaker should be determined following the guidelines for an Inverse Time Circuit Breaker.

    References: NEC 430.51 and UL 489. Also see CEC and appropriate Canadian Standards.



    2) Transformer Protection

    Bulletin 1489 circuit breakers may be used for transformer protection following the guidelines established.

    References: NEC 450 and UL 489. Also see CEC and appropriate Canadian Standards.



    3) Heater Load, Lighting, and Other Load Protection

    Bulletin 1489 circuit breakers may be used for protection of heater loads, lighting loads, and other loads following the guidelines established.

    References: NEC Article 31 and UL 508A. Also see CEC and appropriate Canadian Standards.



    Coordinated Overcurrent Protection

    Where an orderly shutdown is required to minimize the hazards to personnel and equipment, a system of coordination based upon the faulted or overloaded circuit is isolated by selective operation of only the overcurrent protective device closest to the overcurrent condition. The user should select devices that meet this requirement.



    References: NEC 240.12. Also see CEC.


    HACR Rating

    Bulletin 1489 Circuit Breakers are rated as Heating, Air Conditioning and Refrigeration circuit breakers as defined by UL 489, paragraph 6.7 and may used in this type of application.



    SWD Rating

    The Bulletin 1489 breakers (0.5 … 20 A) are rated as SWD and as such may be applied to switch fluorescent lighting loads up to their current and voltage maximum.



    Current Limiting

    Bulletin 1489 Circuit Breakers are rated as current limiting circuit breakers as defined by UL 489, paragraph 8.6.



    The Bulletin 1489 line features the ability to achieve short circuit interruptions far more effectively than conventional breakers. In conventional circuit breakers, the short circuit interruption time required is approximately one or two half cycles of an AC sine wave. When the contacts open, the resulting arc continues to burn until the current level passes through zero. The arc may re-ignite because of the insufficient width of the contact gap. The current that flows until the arc is extinguished produces a heating effect proportional to the I2t value (let-through-energy) of the fault current.



    The Bulletin 1489 device is designed to substantially reduce the amount of let-through-current and the resulting let-through-energy that can damage protected components. The Bulletin 1489 has the ability to interrupt short circuit current within the first half cycle of the fault. Limiting let-through current and energy will protect against the harmful effects of overcurrent and is focused primarily on avoiding the following:

  • Excessive Heat


  • Mechanical Damage




  • Both of these factors are proportional to the square of the current. Thermal energy is proportional to the square of the RMS value and magnetic forces are proportional to the square of the peak value. The most effective way to provide protection is to substantially limit let-through-energy. This provides the following advantages

  • Far less damage at the location of the short circuit.


  • Fast electric separation of a faulty unit from the system, especially power supplies connected in parallel that are switched off when the voltage of the power bus drops below a certain level.


  • Far less wear on the miniature circuit breaker itself. This means more safe interruptions.


  • Better protection of all components in the short circuit path.


  • Far wider range of selective action when used with an upstream protective device. (No nuisance shut downs from feeder line interruptions, causing a blackout in all connected branches.)




  • The following values are applicable to the whole product range with frequency of 50/60 Hz.



    The values were derived from worst case V AC testing of:

    D trip 40 A, 240V AC @ 10 kA

    D trip 32 A, 480Y/277V AC @ 10 kA

    D trip 20 A, 480Y/277V AC @ 14 kA



    Current-Limiting at 240V / 10 kA1p, 2p, 3p I²t = 43 kA²s and Ipeak = 6.2 kA

    Current-Limiting at 480Y/277V / 10 kA 1p, 2p, 3p I²t = 60 kA²s and Ipeak = 6.2 kA

    Current-Limiting at 480Y/277V / 14 kA 1p, 2p, 3p I²t = 65 kA²s and Ipeak = 7.5 kA







    Determining Ratings

    The standard tripping characteristic for Bulletin 1489 is Type C. Type C has a magnetic trip activated at 5…10 times the rated current of the circuit breaker. The reference temperature for the thermal tripping characteristics is 40 °C. The Type C characteristic will suit most applications.

    In rare occurrences when the Type C characteristic does not fully meet the application, the following additional magnetic trip characteristic is available:

    Type D allows for transients approximately twice as high as the standard Type C.

    Use the following table and graph to determine the current rating for the breaker if the ambient is significantly different than 40 °C.


    Device Marked Current Rating [A] @ 40 °C In [A] at Ambient Temperature
    15 °C 20 °C 25 °C 30 °C 40 °C 50 °C 55 °C
    0.5 0.6 0.5 0.5 0.5 0.5 0.5 0.5
    1.0 1.1 1.1 1.1 1.0 1 1.0 0.9
    1.5 1.7 1.6 1.6 1.6 1.5 1.4 1.4
    2.0 2.2 2.2 2.1 2.1 2 1.9 1.9
    3.0 3.3 3.2 3.2 3.1 3 2.9 2.8
    4.0 4.4 4.3 4.2 4.2 4 3.8 3.8
    5.0 5.5 5.4 5.3 5.2 5 4.8 4.7
    6.0 6.6 6.5 6.4 6.2 6 5.8 5.6
    7.0 7.7 7.6 7.4 7.3 7 6.7 6.6
    8.0 8.8 8.6 8.5 8.3 8 7.7 7.5
    10.0 11.0 10.8 10.6 10.4 10 9.6 9.4
    13.0 14.3 14.0 13.8 13.5 13 12.5 12.2
    15.0 16.5 16.2 15.9 15.6 15 14.4 14.1
    16.0 17.6 17.3 17.0 16.6 16 15.4 15.0
    20.0 22.0 21.6 21.2 20.8 20 19.2 18.8
    25.0 27.5 27.0 26.5 26.0 25 24.0 23.5
    30.0 33.0 32.4 31.8 31.2 30 28.8 28.2
    32.0 35.2 34.6 33.9 33.3 32 30.7 30.1
    40.0 44.0 43.2 42.4 41.6 40 38.4 37.6
      
    Note: The table shows the corrected values of the rated current dependent on the ambient temperature.

    Ambient Temperature Graph

    Click to enlarge - temp_graph


    Terminals

    Standard wire (cable) connection

    The standard configuration of the Bulletin 1489 is with terminals suitable for connection of stranded copper wire of the wire size #18 … 8 AWG (1.0 … 10 mm2). Strip length for the termination is 0.5 in. (12 mm). Terminals are shipped in the open position for ease of installation.



    Optional Ring Termination

    An optional terminal configuration (suffix R) is available for use with a ring terminal. This configuration is shipped so that the terminal screw may be unscrewed and withdrawn for the insertion of the ring terminal at proper connection point. The screw is then retightened to provide proper wire termination.



    This unique terminal may be field converted to open the wire termination to allow standard wire termination of the converted terminal.



    Bus Bars

    UL Recognized bus bars and UL Listed feeder terminals are available for group connection of circuit breakers. They are available in 1-, 2-, and 3- pole configurations for connection of multiple circuit breakers.



    Lock-out Attachment

    A sturdy lock-out attachment may be added to a circuit breaker. This lock-out may be padlocked so that the circuit breaker is locked in the off position.



    Shunt Trip

    A shunt trip may be added to a circuit breaker to allow the device to be tripped from a remote source. One version is for tripping voltages of 12…110V AC (12…60V DC) and another for tripping voltages of 110…415V AC (110…230V DC).



    Auxiliary Contacts

    An auxiliary contact module may be added to a circuit breaker to provide pilot duty contacts to indicate the position of circuit breaker, off or on. This contact changes state when the circuit breaker is operated either manually or electrically.



    Signal Contacts

    A signal/auxiliary contact module may be added to a circuit breaker to provide auxiliary contact information off and on and signal contact pilot duty contacts. With signal contacts, the contacts change state only when the circuit breaker changes state from On to Off because of an electrical operation. The module contains one signal contact, form C contact (N.O. and N.C contact with common) and one auxiliary contact (N.O. and N.C contact with common).



    Time Current Curve – 1-, 2-, and 3-Pole Circuit Breaker

    Click to enlarge - C_D_curve

    Bulletin 1489 Cat. No. Explanation

    1489 - A   1   C   005   R
          a b c d e

    a
    Body Style
    Code Description
    A Standard configuration, AC Device

    b
    Poles
    Code Description
    1 1-Pole
    2 2-Pole
    3 3-Pole

    c
    Trip Curve
    Code Trip Curve
    B Trip Curve B
    C Trip Curve C
    D Trip Curve D

    d
    Rated Current (In)
    Code Current [A]
    005 0.5
    010 1
    015 1.5
    020 2
    030 3
    040 4
    050 5
    060 6
    070 7
    080 8
    100 10
    130 13
    150 15
    160 16
    200 20
    250 25
    300 30
    320 32
    350 35
    400 40

    e
    Factory Modifications
    Code Description
    blank Standard Terminal
    R Ring Terminal

    Product Selection

    Bulletin 1489 AC Miniature Circuit Breakers

    Bulletin 1489 1-Pole AC Miniature Circuit Breakers

    No. of Poles EN/IEC Maximum Voltage Trip Curve UL/CSA Max. Volt. Rated Current [A] Standard Wire Configuration Cat. No. Ring Terminal Configuration Cat. No.
    1 415V AC,
    48V DC
    C 277V AC, 48V DC 0.5 1489-A1C005 1489-A1C005R
    1 1489-A1C010 1489-A1C010R
    1.5 1489-A1C015 1489-A1C015R
    2 1489-A1C020 1489-A1C020R
    3 1489-A1C030 1489-A1C030R
    4 1489-A1C040 1489-A1C040R
    5 1489-A1C050 1489-A1C050R
    6 1489-A1C060 1489-A1C060R
    7 1489-A1C070 1489-A1C070R
    8 1489-A1C080 1489-A1C080R
    10 1489-A1C100 1489-A1C100R
    13 1489-A1C130 1489-A1C130R
    15 1489-A1C150 1489-A1C150R
    16 1489-A1C160 1489-A1C160R
    20 1489-A1C200 1489-A1C200R
    25 1489-A1C250 1489-A1C250R
    30 1489-A1C300 1489-A1C300R
    32 1489-A1C320 1489-A1C320R
    240V AC, 48V DC 35 1489-A1C350 1489-A1C350R
    40 1489-A1C400 1489-A1C400R
    D 277V AC, 48V DC 0.5 1489-A1D005 1489-A1D005R
    1 1489-A1D010 1489-A1D010R
    1.5 1489-A1D015 1489-A1D015R
    2 1489-A1D020 1489-A1D020R
    3 1489-A1D030 1489-A1D030R
    4 1489-A1D040 1489-A1D040R
    5 1489-A1D050 1489-A1D050R
    6 1489-A1D060 1489-A1D060R
    7 1489-A1D070 1489-A1D070R
    8 1489-A1D080 1489-A1D080R
    10 1489-A1D100 1489-A1D100R
    13 1489-A1D130 1489-A1D130R
    15 1489-A1D150 1489-A1D150R
    16 1489-A1D160 1489-A1D160R
    20 1489-A1D200 1489-A1D200R
    25 1489-A1D250 1489-A1D250R
    30 1489-A1D300 1489-A1D300R
    32 1489-A1D320 1489-A1D320R
    240V AC, 48V DC 35 1489-A1D350 1489-A1D350R
    40 1489-A1D400 1489-A1D400R
      

    Bulletin 1489 2-Pole AC Miniature Circuit Breakers

    No. of Poles EN/IEC Maximum Voltage Trip Curve UL/CSA Max. Volt. Rated Current [A] Standard Wire Terminal Cat. No. Ring Terminal Configuration Cat. No.
    2 415V AC, 48V DC C 480Y/277V AC, 96V DC 0.5 1489-A2C005R 1489-A2C005R
    1 1489-A2C010 1489-A2C010R
    1.5 1489-A2C015 1489-A2C015R
    2 1489-A2C020 1489-A2C020R
    3 1489-A2C030 1489-A2C030R
    4 1489-A2C040 1489-A2C040R
    5 1489-A2C050 1489-A2C050R
    6 1489-A2C060 1489-A2C060R
    7 1489-A2C070 1489-A2C070R
    8 1489-A2C080 1489-A2C080R
    10 1489-A2C100 1489-A2C100R
    13 1489-A2C130 1489-A2C130R
    15 1489-A2C150 1489-A2C150R
    16 1489-A2C160 1489-A2C160R
    20 1489-A2C200 1489-A2C200R
    25 1489-A2C250 1489-A2C250R
    30 1489-A2C300 1489-A2C300R
    32 1489-A2C320 1489-A2C320R
    240V AC, 96V DC 35 1489-A2C350 1489-A2C350R
    40 1489-A2C400 1489-A2C400R
    D 480Y/277V AC, 96V DC 0.5 1489-A2D005 1489-A2D005R
    1 1489-A2D010 1489-A2D010R
    1.5 1489-A2D015 1489-A2D015R
    2 1489-A2D020 1489-A2D020R
    3 1489-A2D030 1489-A2D030R
    4 1489-A2D040 1489-A2D040R
    5 1489-A2D050 1489-A2D050R
    6 1489-A2D060 1489-A2D060R
    7 1489-A2D070 1489-A2D070R
    8 1489-A2D080 1489-A2D080R
    10 1489-A2D100 1489-A2D100R
    13 1489-A2D130 1489-A2D130R
    15 1489-A2D150 1489-A2D150R
    16 1489-A2D160 1489-A2D160R
    20 1489-A2D200 1489-A2D200R
    25 1489-A2D250 1489-A2D250R
    30 1489-A2D300 1489-A2D300R
    32 1489-A2D320 1489-A2D320R
    240V AC, 96V DC 35 1489-A2D350 1489-A2D350R
    40 1489-A2D400 1489-A2D400R
      

    Bulletin 1489 3-Pole AC Miniature Circuit Breakers

    No. of Poles EN/IEC Maximum Voltage Trip Curve UL/CSA Max. Volt. Rated Current [A] Standard Wire Terminal Cat. No. Ring Terminal Configurations Cat. No.
    3 415V AC, 48V DC C 480Y/277V AC 0.5 1489-A3C005 1489-A3C005R
    1 1489-A3C010 1489-A3C010R
    1.5 1489-A3C015 1489-A3C015R
    2 1489-A3C020 1489-A3C020R
    3 1489-A3C030 1489-A3C030R
    4 1489-A3C040 1489-A3C040R
    5 1489-A3C050 1489-A3C050R
    6 1489-A3C060 1489-A3C060R
    7 1489-A3C070 1489-A3C070R
    8 1489-A3C080 1489-A3C080R
    10 1489-A3C100 1489-A3C100R
    13 1489-A3C130 1489-A3C130R
    15 1489-A3C150 1489-A3C150R
    16 1489-A3C160 1489-A3C160R
    20 1489-A3C200 1489-A3C200R
    25 1489-A3C250 1489-A3C250R
    30 1489-A3C300 1489-A3C300R
    32 1489-A3C320 1489-A3C320R
    240V AC, 96V DC 35 1489-A3C350 1489-A3C350R
    40 1489-A3C400 1489-A3C400R
    D 480Y/277V AC 0.5 1489-A3D005 1489-A3D005R
    1 1489-A3D010 1489-A3D010R
    1.5 1489-A3D015 1489-A3D015R
    2 1489-A3D020 1489-A3D020R
    3 1489-A3D030 1489-A3D030R
    4 1489-A3D040 1489-A3D040R
    5 1489-A3D050 1489-A3D050R
    6 1489-A3D060 1489-A3D060R
    7 1489-A3D070 1489-A3D070R
    8 1489-A3D080 1489-A3D080R
    10 1489-A3D100 1489-A3D100R
    13 1489-A3D130 1489-A3D130R
    15 1489-A3D150 1489-A3D150R
    16 1489-A3D160 1489-A3D160R
    20 1489-A3D200 1489-A3D200R
    25 1489-A3D250 1489-A3D250R
    30 1489-A3D300 1489-A3D300R
    32 1489-A3D320 1489-A3D320R
    240V AC 35 1489-A3D350 1489-A3D350R
    40 1489-A3D400 1489-A3D400R
      

    Miniature Circuit Breaker Accessories

    Description CSA/UL Certifications IEC 60947-2 Compliance CE EN/IEC Max. Volt. UL/CSA Max. Volt. Connection Cat. No.
    Lockout Attachment Yes Yes 1489-AALOA
    Auxiliary Contact, 2 sets, each are Form C, 1 N.O. & 1 N.C. Yes Yes 3 A, 250V AC (AC13)
    0.5 A, 110V DC
    2 A, 240V AC
    0.5 A, 110V DC
    Cable ¬  1489-AAHH3
    Auxiliary/Signal Contact, each are form C, 1 N.O. & 1 N.C Yes Yes 3 A, 250V AC (AC13)
    0.5 A, 110V DC
    2 A, 240V AC
    0.5 A, 110V DC
    Cable ¬  1489-AAHS3
    Auxiliary Contact, Feed Through, 1 N.O. & 1 N.C.
    Yes Yes 3 A, 250V AC (AC13)
    0.5 A, 110V DC
    2 A, 230V AC
    0.5 A, 110V DC
    Cable T  1489-ABH12
    Shunt Trip Module Yes Yes 110...415V AC
    110…230V DC
    110...415V AC
    110…230V DC
    Cable 1489-AASTA1
    Shunt Trip Module Yes Yes 12...110V AC
    12…60V DC
    12...110V AC
    12…60V DC
    Cable 1489-AASTA2
     
    ¬ Use of auxiliary or signal contact limits the circuit breaker to a maximum voltage of 240V AC for UL/CSA applications.
    T Use of this auxiliary contact allows application of the circuit breaker to full rating of 480Y/ 277V AC for UL/CSA applications.

    Bulletin 1489 Bus Bar

    Description No. of Poles No. of Phases Pkg Qty. Number of Circuit Breakers Cat. No.
    Bus BarT  6 1 10 6 1489-AACL106
    12 12 1489-AACL112
    18 18 1489-AACL118
    6 2 3 1489-AACL206
    12 6 1489-AACL212
    18 9 1489-AACL218
    6 3 2 1489-AACL306
    12 4 1489-AACL312
    18 6 1489-AACL318
     
    T  UL Recognized (E300325), CE Marked

    Bulletin 1489 Bus Bar Accessories

    Description No. of Poles Pkg Qty. Wire Range Cat. No.
    Terminal Lug 1-pole for circuit breaker termination 10 #14 … 2 AWG
    2.5 … 35 mm2
    1489-AACLT35
    Protective Cover for unused termination 3-pole set (may be separated) 10 1489-AACLPS
     

    Specifications

    Number of Poles 1, 2, and 3
    Standards UL 489
    CSA C22.2 No. 5.1
    EN/IEC 60947-2
    Certifications UL Listed Circuit Breaker (File Number E197878)
    CSA Certified, VDE Certified, MCB, CE Marked
    HACR Rating (USA/Canada) Yes
    SWD Rating (USA/Canada) Yes (0.5...20 A)
    Calibration Temperature UL/CSA: 40 °C EN/IEC: 30 °C
    Rated Interrupting Capacity EN/IEC - Icu: 15 000 A
    UL/CSA (See Below)
    Trip Curve Rated Current (In) Interrupt Rating (UL/CSA)
    C Curve 0.5...15 A 10,000 A
    16...25 A 14,000 A
    30...40 A 10,000 A
    D Curve 0.5...10 A 10,000 A
    13...20 A 14,000 A
    25...40 A 10,000 A
    Rated Tripping Current UL/CSA: 0.5...32 A, 480Y/277V AC
        0.5...40 A, 240V AC
        0.5…40 A 48V DC 1-pole
        0.5…40 A 96V DC 2-pole
    EN/IEC: 0.5...40 A, 415V AC 48V DC
    Degree of Protection Finger-safe from front:
    -IP20 per IEC 529 from front
    -IP00 at wire terminals
    Dielectric Strength 1960V AC
    Shock 25 G Half sine wave for 11 ms (3 axes)
    Vibration Frequency range: 10…200 Hz
    Max. Amplitude (p-p) = 0.030 in.
    Max. Acceleration = 5 G
    2 hours each of 3 axes
    Normal Operating Environment -5…+55 °C (23...131 °F) (non-condensing)
    Trip Curves C curve (Inductive) 5...10 IN
    D curve (Highly Inductive) 10...20 IN
    Shipment and Short-Term Storage Limits -40...+85 °C (-40...+185 °F)
    Wire Size 1 wire: #18...6 AWG
    2 wires: #18...10 AWG
    Terminal Torque #18...12 AWG: 21 lb•in.
    #10...8 AWG: 25 lb•in.
    #6 AWG: 36 lb•in.
    #2 PoziDriv
    Recommended Wire Strip Length 0.5 in.
      

    Bulletin 1489 Circuit Breaker Approximate Dimensions

    Note: All unites are in millimeters unless indicated. Dimensions are not intended for manufacturing purposes.


    Click to enlarge - 1489_dims


    Click to enlarge - 1489-AAHH3_AAHS3_dims
    1489-AAHH3 & 1489-AAHS3


    Click to enlarge - 1489-ABH12_DIMS
    1489-ABH12


    Click to enlarge - 1489-AAST_Dims
    1489-AAST1, 1489-AAST2


    Click to enlarge - 1489-AACL106
    1489-AACL106


    Click to enlarge - 1489-AACL112
    1489-AACL112


    Click to enlarge - 1489-AACL118
    1489-AACL118


    Click to enlarge - 1489-AACL206
    1489-AACL206


    Click to enlarge - 1489-AACL212
    1489-AACL212


    Click to enlarge - 1489-AACL218
    1489-AACL218


    Click to enlarge - 1489-AACL306
    1489-AACL306


    Click to enlarge - 1489-AACL312
    1489-AACL312


    Click to enlarge - 1489-AACL318
    1489-AACL318


    Click to enlarge - 1489-AACLT35
    1489-AACLT35


    Click to enlarge - 1489-AACLPS
    1489-AACLPS