Circuit Breakers

Catalogs > Industrial Controls Catalog > Control Circuit and Load Protection > Circuit Breakers > Bulletin 1489 Circuit Breaker

Bulletin 1489 Circuit Breaker

Introduction Description Bulletin 1489 Cat. No. Explanation Product Selection Miniature Circuit Breaker Accessories Specifications Bulletin 1489 Circuit Breaker Approximate Dimensions
Specifications

Number of Poles 1, 2, and 3
Standards UL 489
CSA C22.2 No. 5.1
EN/IEC 60947-2
Certifications UL Listed Circuit Breaker (File Number E197878)
CSA Certified, VDE Certified, MCB, CE Marked
HACR Rating (USA/Canada) Yes
SWD Rating (USA/Canada) Yes (0.5...20 A)
Calibration Temperature UL/CSA: 40 °C EN/IEC: 30 °C
Rated Interrupting Capacity EN/IEC - Icu: 15 000 A
UL/CSA (See Below)
Trip Curve Rated Current (In) Interrupt Rating (UL/CSA)
C Curve 0.5...15 A 10,000 A
16...25 A 14,000 A
30...40 A 10,000 A
D Curve 0.5...10 A 10,000 A
13...20 A 14,000 A
25...40 A 10,000 A
Rated Tripping Current UL/CSA: 0.5...32 A, 480Y/277V AC
    0.5...40 A, 240V AC
    0.5…40 A 48V DC 1-pole
    0.5…40 A 96V DC 2-pole
EN/IEC: 0.5...40 A, 415V AC 48V DC
Degree of Protection Finger-safe from front:
-IP20 per IEC 529 from front
-IP00 at wire terminals
Dielectric Strength 1960V AC
Shock 25 G Half sine wave for 11 ms (3 axes)
Vibration Frequency range: 10…200 Hz
Max. Amplitude (p-p) = 0.030 in.
Max. Acceleration = 5 G
2 hours each of 3 axes
Normal Operating Environment -5…+55 °C (23...131 °F) (non-condensing)
Trip Curves C curve (Inductive) 5...10 IN
D curve (Highly Inductive) 10...20 IN
Shipment and Short-Term Storage Limits -40...+85 °C (-40...+185 °F)
Wire Size 1 wire: #18...6 AWG
2 wires: #18...10 AWG
Terminal Torque #18...12 AWG: 21 lb•in.
#10...8 AWG: 25 lb•in.
#6 AWG: 36 lb•in.
#2 PoziDriv
Recommended Wire Strip Length 0.5 in.