Bulletin 1489 AC Circuit Breaker

Introduction Description Bulletin 1489 Cat. No. Explanation Product Selection Miniature Circuit Breaker Accessories Bulletin 1489-A Specifications Bulletin 1489-A Circuit Breaker Approximate Dimensions
Bulletin 1489-A Specifications

Number of Poles 1, 2, and 3
Standards UL 489
CSA C22.2 No. 5
EN/IEC 60947-2
Certifications UL Listed Circuit Breaker (File Number E197878)
CSA Certified, VDE Certified, MCB, CE Marked
HACR Rating (USA/Canada) Yes
SWD Rating (USA/Canada) Yes (0.5...20 A)
Calibration Temperature UL/CSA: 40 °C EN/IEC: 30 °C
Rated Interrupting Capacity EN/IEC - Icu: 15 000 A
UL/CSA (See Below)
Trip Curve Rated Current (In) Interrupt Rating (UL/CSA)
C Curve 0.5...13 A 10,000 A
15...25 A 14,000 A
30...40 A 10,000 A
D Curve 0.5...10 A 10,000 A
13...20 A 14,000 A
25...40 A 10,000 A
Rated Tripping Current UL/CSA: 0.5...32 A, 480Y/277V AC
    0.5...40 A, 240V AC
    0.5…40 A 48V DC 1-pole
    0.5…40 A 96V DC 2-pole
EN/IEC: 0.5...40 A, 415V AC 48V DC
Degree of Protection Finger-safe from front:
-IP20 per IEC 529 from front
-IP00 at wire terminals
Dielectric Strength 1960V AC
Shock 25 G Half sine wave for 11 ms (3 axes)
Vibration Frequency range: 10…2000 Hz
Max. amplitude (p-p) = 0.030 in.
Max. acceleration = 5 G
2 hours each of 3 axes
Normal Operating Environment -30…+60 °C (-22... 140 °F) (non-condensing)
Trip Curves C curve (Inductive) 5...10 IN
D curve (Highly Inductive) 10...20 IN
Shipment and Short-Term Storage Limits -40...+85 °C (-40...+185 °F)
Wire Size 1 wire: #18...6 AWG
2 wires: #18...10 AWG
Terminal Torque #18...12 AWG: 21 lb•in
#10...8 AWG: 25 lb•in
#6 AWG: 36 lb•in
#2 PoziDriv
Recommended Wire Strip Length 0.5 in. (12 mm)