Control Circuit and Load Protection

Catalogs > Industrial Controls Catalog > Control Circuit and Load Protection > Residual Current Devices

Residual Current Devices

Introduction Standards Compliance Description Approximate Dimensions Specifications
Specifications

Design according to: IEC/EN 61008
Certifications VDE, CE Marked
Tripping Time Undelayed; 40 ms for "D" suffix
Rated Voltage 230/400V, 50 Hz
Rated Tripping Current 30, 100, 300, 500 mA
Sensitivity AC and Pulsating DC
  Click to enlarge - Wave4
Rated Short Circuit Capability 10 kA with 63 A gG/gL Back-Up Fuse for up to 63 A
10 kA with 80 A gG/gL Back-Up Fuse for 80 A
Maximum Back-Up Fuse for Short Circuit Protection 63 A gG/gL for up to 63 A
80 A gG/gL for 80
Maximum Back-Up Fuse for Overload Protection 25 A gG/gL (25 A and 40 A devices)
40 A gG/gL (63 A device)
50 A gG/gL (80 A device)
Resistance to Climatic Conditions Per IEC/EN 61008
Degree of Protection Built-in switch IP40
Electrical Life ³ 4000 change-overs
Mechanical Life ³ 10000 change-overs
Mounting DIN Rail
Housing Material Halogen-Free
Electrical Life ³ 4000 change-overs
Operating Temperature -25°C…+40°C (Non-Condensing)
Shipment and Short-Term Storage Limits -35°C…+60°C
Wire Size 1.5…35 mm2 Copper
Terminal Torque 2.4 N•m £ 40 A, 3.0 N•m ³ 63 A
Recommended Wire Strip Length 13 mm
  

Heat Loss Due to Current

At rated current in Watts

Rated Current
Rated Tripping Current
30 mA 100 mA 300 mA 500 mA
2-Pole 16 A 1.2
25 A 2 1.3 1.3
40 A 5.8 5.4 5.4
63 A
80 A
  

Rated Current
Rated Tripping Current
30 mA 100 mA 300 mA 500 mA
4-pole 16 A 1.8 1.8
25 A 3.1 2.8 2.8 2.8
40 A 9.6 8.4 8.4 8.4
63 A 10.5 10.5 10.5 10.5
80 A 11.4 11.4 11.4