Catalogs > Industrial Controls Catalog > Control Circuit and Load Protection > Product Overview
Product Overview
|
|
|
|
||||||
| Bulletin | 1489 | 1492-FB | 140F | |||||
| Type | 480Y/277V AC | 240V AC | For Class CC Fuse | For Class J Fuse | For Midget Fuse | For Class CC Fuse or Midget Fuse | For IEC 10 x 38 mm Fuse | |
| 0.5…25 A | 0.5…40 A | 30 A | 30 A | 60 A | 30 A | 30 A | 32 A | |
| Features | - 0.5...40 A @ 240, 415V AC - 15 000 A interrupting |
|||||||
| Certifications | UL 489 Listed (CSA C22.2 No. 5.1), UL File Number E197878 VDE (IEC 60 947-2) |
UL 512, CSA C22.2 No. 39, CE, EN/IEC 60947-3 | UR, CSA | UL 512, CSA C22.2 No. 39, CE, EN/IEC 60947-3 | ||||
| Maximum Voltage Rating | 480Y/277V AC | 600V AC/DC | 600V AC | 690V AC | ||||
| Shock | 25 G half sine wave for 11 ms (three axes) | |||||||
| Tripping Characteristic Reference Temperature | 40 °C (UL/CSA) 30 °C (IEC) |
NA | NA | |||||
| Tripping Characteristic | C Curve: 5…10 D Curve: 10…20 |
NA | NA | |||||
| Vibration | 100...500 Hz for 1 hour Amplitude — 10...57 Hz; 0.030 inches peak to peak; 57...500 Hz; 5 G peak |
5 G peak or 0.030 in. peak-to-peak displacement for 2 hours in each perpendicular direction. Vibration sweep 10 to 2000 to 10 Hz (15 minutes long) |
— | |||||
| Operating Temperature | -13...+140 °F (-25...+55 °C), non-condensing |
-4...+130 °F (20…+55 °C) | -4...+130 °F (20…+55 °C) | |||||
| Housing Material | Nylon | Nylon | — | |||||
| Working Voltage | — | 110…600V AC/DC or 12…72V AC/DC | 110…600V AC/DC | 110…600V AC/DC or 12…72V AC/DC | — | |||
| Leakage Current with Indicator LED | — | 2.0 mA | — | |||||
| Wire Size | 0.8...13 mm2/#18...6 AWG Cu | #16…4 AWG Cu | #14…1 AWG Cu | #10…1 AWG Cu | #16…4 AWG Cu | #16…10 AWG Cu (1…4 mm2) | ||
| Interrupt Rating | 10 kA @ 240V AC and 480Y/277V AC (UL/CSA) |
200 kA | 50 kA | 200 kA - Class CC 100 kA - Midget |
||||
| 10 kA @ 240V AC and 480Y/277V AC (UL/CSA) |
Fuse dependent | Fuse dependent | ||||||
| Product Selection | Bulletin 1489 Circuit Breakers | Bulletin 1492-FB — DIN Rail Mounting Fuse Holders | Bulletin 140F Fuse Holders | |||||
|
|
|
|
|
| Bulletin | 1492-MC | 1492-MCGA, -MCEA | 1492-SP |
| Type | Branch Circuit Breaker | Ground Fault Detection | Miniature Circuit Breaker Supplementary Protector |
| Features | |||
| Number of Poles | 1-, 2-, 3-pole | 1- and 2-pole with Neutral | 1-, 2-, 3-pole 1-pole + neutral, 3-pole + neutral |
| Maximum Voltage | 120/240V AC 240V AC |
120/240V AC 60 Hz | 480Y/277V AC 1-pole — 48V DC 2-pole — 125V DC |
| Tripping Characteristic Reference Temperature |
40 °C | 40 °C | 25 °C |
| Tripping Characteristic | UL 489 Standard (CSA 22.2 No. 5.1) | UL/CSA Standard | B Curve 3...5 In C Curve 5...10 In D Cruve 10...20 In |
| Certifications | UL 489 Listed Circuit Breaker (CSA 22.2 No. 5.1) UL File Number E197878 |
UL 489, 943 and 1053 CSA 22.2 No. 5.1 |
UL 1077 CSA 22.2 No. 235 VDE (IEC 60898) |
| Dielectric Strength | 1960V AC | 1960V AC | 1960V AC |
| Shock | 25 G half sine wave for 11 ms (3 axes) | ||
| Vibration | 100...500 Hz for 1 Hour | 100...500 Hz for 1 Hour | 100...500 Hz for 1 Hour |
| Wire Size | #14...1/0 AWG | #14...4 AWG 75°C (Cu only) | #18...4 AWG (1.0...25 mm2) |
| Electromechanical Life | UL 489 specifications | UL 489 specifications | ³6000 operations |
| Interrupt Rating | 10 kA @ 240V AC | 10 kA @ 120/240V AC | IEC 60898 10 kA @ 415V AC UL/CSA 10 kA U2 |
| Operating Temperature (non-condensing) | 32...140 °F (0…+60 °C) | 32...140 °F (0…+60 °C) | 23...104 °F (-5…+40 °C) |
| Product Selection | Bulletin 1492-MC Circuit Breakers | 1492-MC Ground Fault Sensing | Bulletin 1492-SP — Supplementary Protector/Miniature Circuit Breaker |