Multi-Pole Lighting Contactors

Catalogs > Industrial Controls Catalog > Lighting Control > Multi-Pole Lighting Contactors > Bulletin 500LG Electrically and Mechanically Held Lighting Contactors

Bulletin 500LG Electrically and Mechanically Held Lighting Contactors

Introduction Standards Compliance and Certifications Catalog Number Explanation Product Selection Accessories — Field Installed
Modifications — Factory Installed Wiring Diagrams Specifications Approximate Dimensions
Specifications

Main Power Poles — Max. AC Voltage and Amp Rating

Load Type Continuous Ampere Rating [A] Poles
1-Phase 3-Phase
Ballast 30 347V AC 600V AC
General Use 30 600V AC 600V AC
Tungsten 20 277V AC 480V AC
AC Resistive 30 600V AC 600V AC
  

Control Circuit Characteristics

Coil
Description Ratings [VA]
Inrush 248
Sealed 28
  

Control Module Characteristics

Control Module
Description Ratings
Min. pulse duration (3-wire control module) 250 ms
Max. allowable leakage current 1.8 mA
EMI 35 V/m
Surge transient peak 6 kV
Frequency range 40…70 Hz
Input Voltage Steady State Current @ Rated Voltage (mA) Max. VA
12…24V DC 42 2
24V AC 80 5
115…120V AC 83 12
200…277V AC 91 30
  

Auxiliary Contact Rating

A600, 24V DC, 24VA

Wire Size

Component No. of Cables Wire Range AWG
(Solid or Stranded)
Wire Temp.
Power Poles 1 #14…8 75°C Cu
2 #14…8★  75°C Cu
Coil 1 or 2 #18…14 60°/75°C Cu
Control Module 1 or 2 #22…12 60°/75°C Cu
Auxiliary Switch 1 or 2 #22…12 60°/75°C Cu
  
★ #8 AWG stranded only.

Short Circuit Current Rating

Available Symmetrical Amperes RMS
  When used with molded case circuit breakers contained in UL67 listed panelboards Fuse (30 A)
At AC Service Voltage Short Circuit Current Rating [A] Max. Breaker Size [A] SCCR
J Fuse
SCCR
RK1 Fuse
240V
277V
480V
600V
14 000
10 000
5000
5000
30
30
40
40
100 kA 50 kA
  

Ambient Temperature

-25…+40 °C (-13…+104 °F) — Operating

-30…+65 °C (-22…+149 °F) — Storage