Catalogs > Industrial Controls Catalog > Lighting Control > Feeder Disconnect Lighting Contactors > Bulletin 500LP Top Wiring Permanent Magnet Latching Contactors For Non-Motor and Lighting Loads
Bulletin 500LP Top Wiring Permanent Magnet Latching Contactors For Non-Motor and Lighting Loads
| Introduction | Standards Compliance and Certifications | Catalog Number Explanation | Product Selection | Typical Wiring Diagram | Modifications for Non-Combination Devices |
| Accessories | Specifications | Full Load Motor Currents | Approximate Dimensions | Renewal Parts |
For Use on Bulletins 500, 500F, 500L, 500LP, 505, 505V, 509, 520, and 520V
Listed on this and the following pages are factory-installed modifications and special features that are available for the low voltage (600V maximum) contactors/starters listed in this catalog. To order, add a dash followed by the suffix number listed in these tables to the end of the product cat. no. Example: Cat. No. 509-BAD-A2E-1.
| Bulletin 500 | Size Rating | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
| Bulletin 500L | Ampere Rating | 15/20 | 30 | 60 | 100 | 200 | 300 | 540 | 810 | 1215 | 2250 |
| Description of Modification | Suffix No. |
Enclosure Type |
NEMA Size | ||||||||||
| 00 | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | |||
| Pilot Devices in Cover or Flange Full Voltage Non-Reversing Single Speed Contactors or Starters (Buls. 500, 500F, 500L, 500LP, 509) |
|||||||||||||
| START-STOP Push Button I/O (Canada only) |
1 1 1 1 |
1¬ 3R/4/12, 4/4X BoltedT Unilock |
A NA NA NA |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A NA NA NA |
| ON-OFF Push Button | 1E 1E 1E 1E |
1¬ 3R/12, 4/4X, 4X BoltedT Unilock |
A NA NA NA |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A NA NA NA |
| HAND-OFF-AUTO Selector Switch | 3 3 3 3 |
1¬ 3R/12, 4/4X, 4X BoltedT Unilock |
A NA NA NA |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A NA A |
A A NA A |
A NA NA NA |
| OFF-ON Selector Switch | 3E 3E 3E 3E |
1¬ 3R/12, 4/4X, 4X BoltedT Unilock |
A NA NA NA |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A A A A |
A NA NA NA |
A NA NA NA |
A NA NA NA |
| HAND-OFF-AUTO Selector Switch (For Permanent Magnet Latch Type Contactor Only) |
3 | All Listed¬ | NA | A | A | A | A | A | A | NA | NA | NA | NA |
| PILOT LIGHT (Red Lens) | 4R 4R 4R |
1, 3R/12, 4/4X, 4X¬ § BoltedT Unilock |
NA NA NA |
A A A |
A A A |
A A A |
A A A |
A A A |
A A A |
A NA NA |
A NA NA |
A NA NA |
A NA NA |
| PUSH-TO-TEST PILOT LIGHT (Red Lens) |
5R 5R |
1, 3R/12, 4/4X, 4X BoltedT |
NA NA |
A A |
A A |
A A |
A A |
A A |
A A |
NA NA |
NA NA |
NA NA |
NA NA |
| Full Voltage Reversing and Multi-Speed Starters (Buls. 505, 505V, 520V, 520V) |
|||||||||||||
| FOR-REV-STOP Push Button | 1 1 1 |
1, 3R/12, 4/4X, 4X BoltedT Unilock |
A NA NA |
A A NA |
A A NA |
A A NA |
A A NA |
A A NA |
A A NA |
A A NA |
A NA NA |
A NA NA |
A NA NA |
| FOR-OFF-REV Selector Switch | 3 3 3 |
1, 3R/12, 4/4X, 4X BoltedT Unilock |
A NA NA |
A A A |
A A A |
A A NA |
A A NA |
A A NA |
A A NA |
A NA NA |
A NA NA |
A NA NA |
A NA NA |
| HIGH-LOW-STOP Push Button | 1 1 |
1, 3R/12, 4/4X, 4X BoltedT |
A NA |
A A |
A A |
A A |
A A |
A A |
A A |
A NA |
A NA |
A NA |
A NA |
| HIGH-OFF-LOW Selector Switch | 3 3 |
1, 3R/12, 4/4X, 4X BoltedT |
A NA |
A A |
A A |
A A |
A A |
A A |
A A |
A NA |
A NA |
A NA |
A NA |
| HIGH-LOW-OFF-AUTO Selector Switch | 3J | 1, 3R/12, 4/4X, 4X | NA | A | A | A | A | A | A | A | A | A | A |
| PILOT LIGHTS (2) | 4R | 1, 3R/12, 4/4X, 4X§ | NA | A | A | A | A | A | A | A | A | A | A |
| A = Available NA = Not Available |
|||||||||||||
| ¬ Bulletin 500L and 500FL require a normally open auxiliary contact when used with a push button. See Contactor Accessories, continued. Only one push button or one selector switch (not both) may be added to a Bulletin 509 for NEMA Type 1 without transformers. Only one pilot light may be added to a Bulletin 509 Type 1 without transformers. | |||||||||||||
| T Bolted suitable for Type 7 & 9 or Type 3R, 7 & 9. | |||||||||||||
| Unilock suitable for Type 7 & 9 or Type 3R, 7 & 9 with the addition of a drain or breather and drain. | |||||||||||||
| § OFF pilot lights for non-reversing and non-multi-speed applications require a normally closed auxiliary contact add -91 to Cat. No. Red and amber are the only colors available on Type 1 non-combination starters. On Type 3R/12 non-combination starters, specify other lens colors by changing the letter to: A = Amber; B = Blue; C = Clear; G = Green; W = White. | |||||||||||||
| § For multi-speed and reversing starters, one pilot light for each contactor. Add additional letters to identify two lens colors. The first letter specifies FORWARD, HIGH, or ON; the second letter specifies REVERSE, LOW, or OFF; e.g., 4AG. | |||||||||||||
For Use on Bulletins 500, 500F, 500L, 500LP, 505, 505V, 509, 520, and 520V, Continued
| Description of Modification | Suffix No. |
Enclosure Type |
NEMA Size | |||||||||||
| 00 | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | ||||
| Control Circuit Transformer¬ | ||||||||||||||
| Includes 2 primary fuses and 1 secondary fuse with standard capacity 60 or 50 Hz |
6PT 6PT 6PT |
1, 3R/12, 4/4X, 4X Bolted Unilock§ |
NA NA NA |
A A A |
A A A |
A A A |
A A A |
A A A |
A A A |
STD STD STD |
STD NA NA |
STD NA NA |
STD NA NA |
|
| With 100 W extra capacity 60 or 50 Hz | 6XP 6XP 6XP |
1, 3R/12, 4/4X, 4X Bolted Unilock§ |
NA NA NA |
A A A |
A A A |
A A A |
A A A |
A A A |
A A A |
STD STD STD |
STD NA NA |
STD NA NA |
STD NA NA |
|
| Control Circuit Auxiliary contact installed on contactor |
||||||||||||||
| N.O. N.C. |
90§ Ø 91§ Ø |
All listed All listed |
NA NA |
A A |
A A |
A A |
A A |
A A |
A A |
A A |
A A |
A A |
A A |
|
| Fused control circuit for applications less transformer | ||||||||||||||
| (1 Fuse — Fuse Included) (2 Fuses — Fuses Included) |
21 22 |
1, 3R/12, 4/4X, 4X 1, 3R/12, 4/4X, 4X |
NA NA |
A A |
A A |
A A |
A A |
A A |
A A |
NA NA |
NA NA |
NA NA |
NA NA |
|
| Surge suppression for 120 or 240V AC Coil | 17 | All listed | NA | A | A | A | A | A | A | NA | NA | NA | NA | |
| Terminal blocks (Cat. No. 1492-CA1 or similar) per block | z | 1, 3R/12, 4/4X, 4X | NA | A | A | A | A | A | A | A | NA | NA | NA | |
| DC operation of control circuit (power circuit remains AC) Add letters DC to Bulletin No. (add per solenoid) |
z | Open 1, 4/4X, 4X, 12 |
NA NA |
A z |
A z |
A z |
A z |
A z |
NA NA |
NA NA |
NA NA |
NA NA |
NA NA |
|
| Overload Relays (Eutectic Alloy) | ||||||||||||||
| N.O. alarm contact adder N.C. alarm contact adder Omit 3 overload relays |
(Bulletin 592) (Bulletin 592) (For Bulletins 505 and 520 only) |
9 9A 23ª |
All listed All listed All listed |
NA NA A |
A A A |
A A A |
A A A |
A A A |
A A A |
A A A |
A A A |
NA NA NA |
NA NA NA |
NA NA NA |
| Auxiliary Relays (Indicate Contact Arrangement and Coil Voltage) | ||||||||||||||
| 3Æ Powermonitor (Timemark Model 258) | 400 | 1, 3R/12, 4/4X, 4X | NA | A | A | A | A | A | A | NA | NA | NA | NA | |
| Control relay (4-pole maximum)z | v | 1, 3R/12 4/4X, 4X Unilock§ |
NA NA NA |
NA NA NA |
A A A |
A A A |
A A A |
A A A |
A A NA |
A A NA |
NA NA NA |
NA NA NA |
NA NA NA |
|
| Addition of timing relayz | v | 1, 3R/12 4/4X, 4X Unilock§ |
NA NA NA |
A A NA |
A A NA |
A A NA |
A A A |
A A A |
A A A |
NA NA NA |
NA NA NA |
NA NA NA |
NA NA NA |
|
| Add Bulletin 813Sz | (Line voltage monitor) (Line current monitor) |
v v |
— — |
NA NA |
NA NA |
A A |
A A |
A A |
A A |
A A |
A A |
A A |
A A |
A A |
| Bulletin 596 (used on Bulletin 500…509, 3-pole maximum) (Coil - 180 s timing range) |
||||||||||||||
| ON Delay OFF Delay |
87A 87B |
Open Type Open Type |
NA NA |
A A |
A A |
A A |
A A |
A A |
A A |
NA NA |
NA NA |
NA NA |
NA NA |
|
| Extra strong coil for addition of power pole adders required for sizes 2…4 | 88 | All listed | NA | NA | NA | A | A | A | NA | NA | NA | NA | NA | |
| Form A compelling relayª (used on Bulletin 520) | 70 | 1, 3R/12, 4/4X, 4X | NA | A | A | A | A | A | A | A | NA | NA | NA | |
| Form B auto. seq. accelerating relay for each higher speed -controls the sequence of acceleration from low to high speed. (Used on Bulletin 520) |
71 |
1, 3R/12, 4/4X, 4X |
NA |
A |
A |
A |
A |
A |
A |
A |
NA |
NA |
NA |
|
| Form C auto. seq. decelerating relay for each lower speed -interposes a time delay between each lower speed. (Used on Bulletin 520) |
72 |
1, 3R/12, 4/4X, 4X |
NA |
A |
A |
A |
A |
A |
A |
A |
NA |
NA |
NA |
|
| Enclosure | ||||||||||||||
| Breather | 136 | Bolted | NA | A | A | A | A | A | A | NA | NA | NA | NA | |
| Breather and drain | 137 | Unilock§ | ||||||||||||
| and Bolted | NA | A | A | A | A | A | A | NA | NA | NA | NA | |||
| Drain | 138 | Unilock§ | ||||||||||||
| and Bolted | NA | A | A | A | A | A | A | NA | NA | NA | NA | |||
| Protective Covers for Contactors and Starters | 426 | 1, 3R/12, 4/4X, 4 | ||||||||||||
| NA | A | A | A | A | A | A | NA | NA | NA | NA | ||||
| A = Available NA = Not Available STD = Standard |
||||||||||||||
| ¬ If the transformer secondary is to be grounded, add the suffix letter G at no aditional charge. Example: 6GP. | ||||||||||||||
| T When ordering in Canada, use suffix 6. Primary fusing is not required by the Canadian Electrical Code. | ||||||||||||||
| Bolted suitable for Type 7 & 9 or Type 3R, 7 & 9. | ||||||||||||||
| § Unilock suitable for Type 7 & 9 or Type 3R, 7 & 9. | ||||||||||||||
| § Multiple auxiliary contacts are to be group coded: e.g. use 9 followed by second digit for each auxiliary used: 90-91-98 group coded to 9018. Maximum quantity of auxuliary contacts (any type) group coded shall be 5. | ||||||||||||||
| Ø For Bulletins 505 and 520 devices, one auxiliary contact is installed on each of the two contactors. | ||||||||||||||
| z Order by description. | ||||||||||||||
| ª Contactors provided on short mounting plate, please contact your local Rockwell Automation sales office or Allen-Bradley distributor for dimensions. | ||||||||||||||
| v Only one relay per starter. | ||||||||||||||
| ª Through control wiring the starter is forced to operate in the low speed before switching to high speed. | ||||||||||||||