DIN Rail AC Surge Protective Device — Bulletin 4983-DS

Bulletin 4983-DS DIN Rail AC Surge Protective Devices

Click to enlarge - 4983-DS230-401 (4-POL Left)_sm


Features


Bulletin 4983-DS offers a number of options to meet your basic surge protection needs. The Bulletin 4983-DS products are connected in parallel and use an MOV to clamp high-voltage surges. The Bulletin 4983-DS devices are primarily used in the main electrical panel for the protection of 1- and 3-phase systems.

Standards Compliance


Certifications


Cat. No. Explanation

4983 D S 120 40 1
      a b c    d e

a
Mount
Code Description
D DIN Rail

b
Type
Code Description
S Standard duty

c
Voltage
Code Description
120 120V
230 230V
277 480Y/277V

d
Current Rating
Code Description
40 40 kA

e
Poles
Code Description
1 1-pole
2 2-pole
4 4-pole
1G 1-pole + 1
3G 3-pole + 1

Product Selection

North American Applications

AC Network No. of Poles No. of Devices Needed Connection Mode Max. Continuous Operating Voltage (MCOV) (Uc) [V AC] Nominal Discharge Current 8/20ms (In) [kA] Max. Discharge Current 8/20ms (Imax) [kA] Protection Level
(Up) [kV]
UL 1449 Suppressed Voltage Rating (SVR) [kV] Appropriate Fuse¬  Cat. No.
110…120V AC (1-wire) 1 1 L/G or N/G 150 20 40 0.7 0.5 125 A Max. 4983-DS120-401
120V AC Single phase 1 1 L/G or N/G 4983-DS120-402
120/280V AC 4 1 L/G and N/G 4983-DS120-404
230V AC
(1-phase, 1-pole)
1 1 L/N and N/G 275 20 40 1.25 0.9 4983-DS230-401
230V AC
(1-phase, 2-pole)
2 2
230V AC
(3-phase)
3 3
230/240V AC (3-phase + N) 4 1 L/N and N/G 275 20 40 1.5 0.9 4983-DS230-404
or
230/240V AC (3-phase + N) 4983-DS230-403G
277/480V AC (3-phase + N) 4 1 L/G and N/G 400 20 40 2 1.5 4983-DS277-404
  
¬ Fuses required to protect the surge protector in case of short-circuit failure. They must be installed in series with each pole of the surge protector.
Note:N = Neutral
L/N = Line/neutral
N/G = Neutral/ground

IEC Applications

AC Network No. of Poles No. of Devices Needed Connection Mode Max. Continuous Operating Voltage (MCOV) (Uc) Nominal Discharge Current 8/20ms (In) Max. Discharge Current 8/20ms (Imax) Protection Level
(Up)
UL 1449 Supressed Voltage Rating (SVR) Appropriate Fuse¬  Cat. No.
230/400V AC
(1-pole)
1 1 L/G or N/G 275 20 40 1.25 0.9 125 A Max. 4983-DS230-401
230/400V
(1-phase: TNS)
2 2
230/400V AC
(3-phase:TNC)
3 3
230/400V AC
(1-phase: TT-TN)
2 1 L/N and N/G 275 20 40 1.5 0.9 4983-DS230-401G
230/400V AC
(3-phase + N: TNS)
4 1 L/G and N/G 275 20 40 1.5 0.9 4983-DS230-404
230/400V AC
(3-phase + N:TT-NS
4 1 L/G and N/G 275 20 40 1.5 0.9 4983-DS230-403G
230/400V AC
(1-phase: TT-TN-IT)
2 2 L/G or N/G 400 20 40 2 1.5 4983-DS277-401
230/400V AC
(1-phase: TNC-IT)
3 3
230/400V AC
(3-phase + N: TT-TN-IT)
4 1 L/G and N/G 400 20 40 2 1.5 4983-DS277-404
  
¬ Fuses required to protect the surge protector in case of short-circuit failure. They must be installed in series with each pole of the surge protector.
Note:N = Neutral
L/N = Line/neutral
N/G = Neutral/ground

Specifications

Connection/Mounting Type Parallel/DIN Rail mount
Standards Compliance UL 1449, IEC 61643-1
Certifications CE marked
Conductor Material Cu, solid or stranded
Conductor Range #10…4 AWG (4…28 mm2)
Strip Length 0.4 in. (10 mm)
Tightening Torque 17.8…22.1 lb•in. (2.0…2.5 N•m)
No. of Conductors/Terminal 1
Operating Temperature -40…+85 °C
  

Approximate Dimensions

Note: Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.


Click to enlarge - 4983-DS_dims