Surge and Filter Protection

Catalogs > Industrial Controls Catalog > Surge and Filter Protection > DIN Rail AC Surge Protective Device — Bulletin 4983-DS

DIN Rail AC Surge Protective Device — Bulletin 4983-DS

Introduction Standards Compliance Cat. No. Explanation Product Selection Specifications Approximate Dimensions
Product Selection

North American Applications

AC Network No. of Poles No. of Devices Needed Connection Mode Max. Continuous Operating Voltage (MCOV) (Uc) [V AC] Nominal Discharge Current 8/20ms (In) [kA] Max. Discharge Current 8/20ms (Imax) [kA] Protection Level
(Up) [kV]
UL 1449 Suppressed Voltage Rating (SVR) [kV] Appropriate Fuse¬  Cat. No.
110…120V AC (1-wire) 1 1 L/G or N/G 150 20 40 0.7 0.5 125 A Max. 4983-DS120-401
120V AC Single phase 1 1 L/G or N/G 4983-DS120-402
120/280V AC 4 1 L/G and N/G 4983-DS120-404
230V AC
(1-phase, 1-pole)
1 1 L/N and N/G 275 20 40 1.25 0.9 4983-DS230-401
230V AC
(1-phase, 2-pole)
2 2
230V AC
(3-phase)
3 3
230/240V AC (3-phase + N) 4 1 L/N and N/G 275 20 40 1.5 0.9 4983-DS230-404
or
230/240V AC (3-phase + N) 4983-DS230-403G
277/480V AC (3-phase + N) 4 1 L/G and N/G 400 20 40 2 1.5 4983-DS277-404
  
¬ Fuses required to protect the surge protector in case of short-circuit failure. They must be installed in series with each pole of the surge protector.
Note:N = Neutral
L/N = Line/neutral
N/G = Neutral/ground

IEC Applications

AC Network No. of Poles No. of Devices Needed Connection Mode Max. Continuous Operating Voltage (MCOV) (Uc) Nominal Discharge Current 8/20ms (In) Max. Discharge Current 8/20ms (Imax) Protection Level
(Up)
UL 1449 Supressed Voltage Rating (SVR) Appropriate Fuse¬  Cat. No.
230/400V AC
(1-pole)
1 1 L/G or N/G 275 20 40 1.25 0.9 125 A Max. 4983-DS230-401
230/400V
(1-phase: TNS)
2 2
230/400V AC
(3-phase:TNC)
3 3
230/400V AC
(1-phase: TT-TN)
2 1 L/N and N/G 275 20 40 1.5 0.9 4983-DS230-401G
230/400V AC
(3-phase + N: TNS)
4 1 L/G and N/G 275 20 40 1.5 0.9 4983-DS230-404
230/400V AC
(3-phase + N:TT-NS
4 1 L/G and N/G 275 20 40 1.5 0.9 4983-DS230-403G
230/400V AC
(1-phase: TT-TN-IT)
2 2 L/G or N/G 400 20 40 2 1.5 4983-DS277-401
230/400V AC
(1-phase: TNC-IT)
3 3
230/400V AC
(3-phase + N: TT-TN-IT)
4 1 L/G and N/G 400 20 40 2 1.5 4983-DS277-404
  
¬ Fuses required to protect the surge protector in case of short-circuit failure. They must be installed in series with each pole of the surge protector.
Note:N = Neutral
L/N = Line/neutral
N/G = Neutral/ground