DIN Rail Heavy Duty AC Surge Protective Device — Bulletin 4983-DH
Bulletin 4983-DH DIN Rail Heavy-Duty AC Surge Protective Devices
|
Features
- UL 1449
- Highest energy absorption capability of all Bulletin 4893 products
- Robust design avoids uneccessary replacement
- Visual fault indicator linked to internal thermal disconnect
- Automatic trigger for SPD replacement
- Safety remote signaling standard
Bulletin 4983-DH is a heavy-duty surge protector. This SPD combines a high-energy varistor (MOV) network with a gas discharge tube to increase performance in protection level, life duration, and suppression of leakage current. The Bulletin 4983-DH product is connected in parallel and can be located in the feeder circuit.
Standards Compliance
- UL 1449
- CSA C22.2, No. 8
- IEC 61643-1
- EN 61643-11
Certifications
- CE Marked
- UR Recognized Component (File E317208, Guide XUHT2, XUHT8)
Cat. No. Explanation
| 4983 | — | D | H | 120 | — | 25 |
| a | b | c | d |
| a | |
| Mount | |
| Code | Description |
| D | DIN Rail |
| b | |
| Type | |
| Code | Description |
| H | Heavy Duty |
| c | |
| Voltage | |
| Code | Description |
| 120 | 120V |
| 300 | 230V and 480Y/277V |
| d | |
| Current Rating | |
| Code | Description |
| 25 | 25 kA |
| 50 | 50 kA |
Product Selection
North American Applications
| AC Network | No. of Poles and Devices Needed | Connection Mode | Max. Continuous Operating Voltage (MCOV) (Uc) [V AC] | Lightning Current 10/350 ms (Iimp) [kA] | Max. Discharge Current 8/20ms (Imax) [kA] | Protection Level (Up) [kV] | UL 1449 Suppressed Voltage Rating (SVR) [kV] | Appropriate Fusing¬ | Cat. No. |
| 120/208V | 1 | L/G or N/G | 150 | 25 | 70 | 1 | 0.4 | 250 A Max. | 4983-DH120-25 |
| 120/208V AC (3-phase + N) |
4 | ||||||||
| 230/400V 480Y/277V |
1 | L/G or N/G | 330 | 25 | 70 | 1.5 | 0.6 | 250 A Max. | 4983-DH300-25 |
| 220…230V AC (2-pole) |
2 | ||||||||
| 230V AC (3-phase) |
3 | ||||||||
| 230V AC (3-phase + N) |
4 | ||||||||
| 480Y/277V AC (3-phase + N) |
4 | ||||||||
| 230/400V 480Y/277V |
1 | L/G or N/G | 330 | 50 | 70 | 1.5 | 0.6 | 500 A Max. | 4983-DH300-50 |
| 220…230V AC (2-pole) |
2 | ||||||||
| 230V AC (3-phase) |
3 | ||||||||
| 230V AC (3-phase + N) |
4 | ||||||||
| 480Y/277V AC (3-phase + N) |
4 | ||||||||
| ¬ Fuses required to protect the surge protector in case of short-circuit failure. They must be installed in series with each pole of the surge protector. | |||||||||
| Note:N = Neutral L/N = Line/neutral N/G = Neutral/ground |
|||||||||
IEC Applications
| AC Network | No. of Poles and Devices Needed | Connection Mode | Max. Continuous Operating Voltage (MCOV) (Uc) [V AC] | Lightning Current 10/350 ms (Iimp) [kA] | Max. Discharge Current 8/20ms (Imax) [kA] | Protection Level (Up) | UL 1449 Supressed Voltage Rating (SVR) [kV] | Appropriate Fusing¬ | Cat. No. | |
| 230/400V 480Y/277V |
1 | L/G or N/G | 330 | 25 | 70 | 1.5 | 0.6 | 250 A Max. | 4983-DH300-25 | |
| 230/400V (1-phase: TNS) |
2 | |||||||||
| 230/400V (3-phase: TNC |
3 | |||||||||
| 220…230V (3-phase + N: TNS) |
4 | |||||||||
| 230/400V (1-pole) |
1 | L/G or N/G | 330 | 50 | 70 | 1.5 | 0.6 | 500 A Max. | 4983-DH300-50 | |
| 230/400V (1-phase: TNS) |
2 | |||||||||
| 230/400V (3-phase: TNC) |
3 | |||||||||
| 230/400V (3-phase + N: TNS) |
4 | |||||||||
| ¬ Fuses required to protect the surge protector in case of short-circuit failure. They must be installed in series with each pole of the surge protector. | ||||||||||
| Note:N = Neutral L/N = Line/neutral N/G = Neutral/ground |
||||||||||
Specifications
| Connection/Mounting Type | Parallel/DIN Rail mount |
| Standards Compliance | UL 1449, IEC 61643-1 |
| Certifications | cURus recognized, CE marked |
| Conductor Material | Cu, solid or stranded |
| Conductor Range | #10…2 AWG (6…35 mm2) |
| Strip Length | 0.5 in. (12 mm) |
| Tightening Torque | 22.1…26.6 lbin. (2.5…3 Nm) |
| No. of Conductors/Terminal | 1 |
| Operating Temperature | -40…+85 °C |
Approximate Dimensions
Note: Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.
|