DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC

Bulletin 4983-DC DIN Rail Filter and Surge Protective Devices

Click to enlarge - 4983-DC24005 (Left))sm


Features


Bulletin 4983-DC is the combination of a filter and a surge protective device. The Bulletin 4983-DC product meets both UL 1449 and UL 1283. This product allows transient and noise protection in one small package.

Standards Compliance


Certifications


Cat. No. Explanation

4983 D C 120 3
      a b c d

a
Mount
Code Description
D DIN Rail

b
Type
Code Description
C Combo UL 1449/UL 1283

c
Voltage
Code Description
120 120V
240 240V

d
Current Rating
Code Description
3 3 A
5 5 A
10 10 A
20 20 A

DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC

Operating Voltage Max. Continuous Operating Voltage Line Frequency [Hz] Max. Discharge Current 8/20 ms (Imax) [kA] UL 1449 Suppressed Voltage Rating (SVR) Ampacity [A] Cat. No.
120V AC 150 Vrms (125%) @ 120V AC 47…63 All Mode Unit
Line to Neutral — 25
Line to Ground — 10
Neutral to Ground — 10
Normal Mode — 330V
Common Mode — 400V
3.0 4983-DC120-03
120V AC 150 Vrms (125%) @ 120V AC 47…63 5.0 4983-DC120-05
120V AC 150 Vrms (125%) @ 120V AC 47…63 10 4983-DC120-10
120V AC 150 Vrms (125%) @ 120V AC 47…63 20 4983-DC120-20
240V AC 320 Vrms (115%) @ 240V AC 47…63 Normal Mode — 600V
Common Mode — 1000V
3.0 4983-DC240-03
240V AC 320 Vrms (115%) @ 240V AC 47…63 5.0 4983-DC240-05
240V AC 320 Vrms (115%) @ 240V AC 47…63 10 4983-DC240-10
240V AC 320 Vrms (115%) @ 240V AC 47…63 20 4983-DC240-20
  

Specifications

Connection/Mounting Type Series/DIN Rail mount
Enclosure Metal, DIN Rail mount, product label
Approximate Weight 3 A — 1 lb
5 A — 1 lb
10 A — 1.5 lbs
20 A — 1.5 lbs
Modes of Protection Line — Neutral
Line — Line
Line — PE
Neutral — PE
Certifications UR Recognized, CE Marked
Typical Cat. A Ringwave Rating < 60V peak
Typical Cat. B Ringwave Rating < 100V peak
Status Indication Single green LED indicating MOV integrity
Single form C contact (10 A @ 250V AC, 5 A @ 100V DC)
Response Time Normal mode: < 0.5 ns
Common Mode: < 5 ns
Operating Temperature -40…+60 °C derate linearly to 60% @ +70 °C
Fusing Appropriate external fusing is required
Frequency Response 100 kHz…50 MHz Normal Mode (100 kHz…50 MHz) — 90 dB min.
Common Mode (5…50MHz) — 60 dB min.
50 kHz cut-off frequency
  

Approximate Dimensions

Note: Dimensions are shown in inches (millimeters). Dimensions are not intended for manufacturing purposes.


Click to enlarge - 4983-DCxxx-03_05_dims
Cat. Nos. 4983-DCxxx-03, -DCxxx-05


Click to enlarge - 4983-DCxxx-10_20_dims
Cat. Nos. 4983-DCxxx-10, -DCxxx-20