DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC
Bulletin 4983-DC DIN Rail Filter and Surge Protective Devices
|
Features
- Small combination (filter and SPD) package size
- Features Isatrol technology
- All-mode transient protection with exceptional Line to Neutral value of 25 kA
- LED power indication
- Form C contact for remote status indication
- DIN Rail mountable
Bulletin 4983-DC is the combination of a filter and a surge protective device. The Bulletin 4983-DC product meets both UL 1449 and UL 1283. This product allows transient and noise protection in one small package.
Standards Compliance
- UL 1283
- UL 1449
- IEC 61643-1
- EN 61643-11
Certifications
- cURus Recognized Component (File No. E317208, Guide XUHT2, XUHT8)
- CE Marked
Cat. No. Explanation
| 4983 | — | D | C | 120 | 3 |
| a | b | c | d |
| a | |
| Mount | |
| Code | Description |
| D | DIN Rail |
| b | |
| Type | |
| Code | Description |
| C | Combo UL 1449/UL 1283 |
| c | |
| Voltage | |
| Code | Description |
| 120 | 120V |
| 240 | 240V |
| d | |
| Current Rating | |
| Code | Description |
| 3 | 3 A |
| 5 | 5 A |
| 10 | 10 A |
| 20 | 20 A |
DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC
| Operating Voltage | Max. Continuous Operating Voltage | Line Frequency [Hz] | Max. Discharge Current 8/20 ms (Imax) [kA] | UL 1449 Suppressed Voltage Rating (SVR) | Ampacity [A] | Cat. No. |
| 120V AC | 150 Vrms (125%) @ 120V AC | 47…63 | All Mode Unit Line to Neutral — 25 Line to Ground — 10 Neutral to Ground — 10 |
Normal Mode — 330V Common Mode — 400V |
3.0 | 4983-DC120-03 |
| 120V AC | 150 Vrms (125%) @ 120V AC | 47…63 | 5.0 | 4983-DC120-05 | ||
| 120V AC | 150 Vrms (125%) @ 120V AC | 47…63 | 10 | 4983-DC120-10 | ||
| 120V AC | 150 Vrms (125%) @ 120V AC | 47…63 | 20 | 4983-DC120-20 | ||
| 240V AC | 320 Vrms (115%) @ 240V AC | 47…63 | Normal Mode — 600V Common Mode — 1000V |
3.0 | 4983-DC240-03 | |
| 240V AC | 320 Vrms (115%) @ 240V AC | 47…63 | 5.0 | 4983-DC240-05 | ||
| 240V AC | 320 Vrms (115%) @ 240V AC | 47…63 | 10 | 4983-DC240-10 | ||
| 240V AC | 320 Vrms (115%) @ 240V AC | 47…63 | 20 | 4983-DC240-20 | ||
Specifications
| Connection/Mounting Type | Series/DIN Rail mount |
| Enclosure | Metal, DIN Rail mount, product label |
| Approximate Weight | 3 A — 1 lb 5 A — 1 lb 10 A — 1.5 lbs 20 A — 1.5 lbs |
| Modes of Protection | Line — Neutral Line — Line Line — PE Neutral — PE |
| Certifications | UR Recognized, CE Marked |
| Typical Cat. A Ringwave Rating | < 60V peak |
| Typical Cat. B Ringwave Rating | < 100V peak |
| Status Indication | Single green LED indicating MOV integrity Single form C contact (10 A @ 250V AC, 5 A @ 100V DC) |
| Response Time | Normal mode: < 0.5 ns Common Mode: < 5 ns |
| Operating Temperature | -40…+60 °C derate linearly to 60% @ +70 °C |
| Fusing | Appropriate external fusing is required |
| Frequency Response 100 kHz…50 MHz | Normal Mode (100 kHz…50 MHz) — 90 dB min. Common Mode (5…50MHz) — 60 dB min. 50 kHz cut-off frequency |
Approximate Dimensions
Note: Dimensions are shown in inches (millimeters). Dimensions are not intended for manufacturing purposes.
|
|