Catalogs > Industrial Controls Catalog > Surge and Filter Protection > DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC
DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC
| Introduction | Standards Compliance | Cat. No. Explanation | DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC | Specifications | Approximate Dimensions |
| Operating Voltage | Max. Continuous Operating Voltage | Line Frequency [Hz] | Max. Discharge Current 8/20 ms (Imax) [kA] | UL 1449 Suppressed Voltage Rating (SVR) | Ampacity [A] | Cat. No. |
| 120V AC | 150 Vrms (125%) @ 120V AC | 47…63 | All Mode Unit Line to Neutral — 25 Line to Ground — 10 Neutral to Ground — 10 |
Normal Mode — 330V Common Mode — 400V |
3.0 | 4983-DC120-03 |
| 120V AC | 150 Vrms (125%) @ 120V AC | 47…63 | 5.0 | 4983-DC120-05 | ||
| 120V AC | 150 Vrms (125%) @ 120V AC | 47…63 | 10 | 4983-DC120-10 | ||
| 120V AC | 150 Vrms (125%) @ 120V AC | 47…63 | 20 | 4983-DC120-20 | ||
| 240V AC | 320 Vrms (115%) @ 240V AC | 47…63 | Normal Mode — 600V Common Mode — 1000V |
3.0 | 4983-DC240-03 | |
| 240V AC | 320 Vrms (115%) @ 240V AC | 47…63 | 5.0 | 4983-DC240-05 | ||
| 240V AC | 320 Vrms (115%) @ 240V AC | 47…63 | 10 | 4983-DC240-10 | ||
| 240V AC | 320 Vrms (115%) @ 240V AC | 47…63 | 20 | 4983-DC240-20 | ||