Surge and Filter Protection

Catalogs > Industrial Controls Catalog > Surge and Filter Protection > DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC

DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC

Introduction Standards Compliance Cat. No. Explanation DIN Rail Filter and Surge Protective Device — Bulletin 4983-DC Specifications Approximate Dimensions
Specifications

Connection/Mounting Type Series/DIN Rail mount
Enclosure Metal, DIN Rail mount, product label
Approximate Weight 3 A — 1 lb
5 A — 1 lb
10 A — 1.5 lbs
20 A — 1.5 lbs
Modes of Protection Line — Neutral
Line — Line
Line — PE
Neutral — PE
Certifications UR Recognized, CE Marked
Typical Cat. A Ringwave Rating < 60V peak
Typical Cat. B Ringwave Rating < 100V peak
Status Indication Single green LED indicating MOV integrity
Single form C contact (10 A @ 250V AC, 5 A @ 100V DC)
Response Time Normal mode: < 0.5 ns
Common Mode: < 5 ns
Operating Temperature -40…+60 °C derate linearly to 60% @ +70 °C
Fusing Appropriate external fusing is required
Frequency Response 100 kHz…50 MHz Normal Mode (100 kHz…50 MHz) — 90 dB min.
Common Mode (5…50MHz) — 60 dB min.
50 kHz cut-off frequency