Catalogs > Essential Components Catalog (Europe) > Power > Motor Protection Circuit Breakers > Product Line Overview
Product Line Overview
| Motor Protection Circuit Breakers 1…45 A |
Motor Protection Circuit Breakers 16…630 A |
Motor Circuit Breakers 0.16…1200 A |
0.16…1200 A
- Current range 0.16…1200 A
- UL Listed/Recognized for motor loads
- Short-circuit protection (magnetic trip only)
- Overload protection must be provided separately
- Short-circuit protection (magnetic trip only)
- Visible trip indication
- High current limiting
- High switching capacity
|
|
|
|
|
|
|
|
| C-Frame | D-Frame | F-Frame | H-Frame | J-Frame | L-Frame | N-Frame | |
| Max. Current Ie | 2.5 A | 32 A | 45 A | 100 A | 250 A | 600 A | 1200 A |
| Current Rating | 0.16…2.5 A | 2.5…32 A | 25…45 A | 3…100 A | 70…250 A | 125…600 A | 640…1200 A |
| Short Circuit Protection | ü | ü | ü | ü | ü | ü | ü |
| Standards Compliance: | |||||||
| CSA 22.2, No. 14 |
ü | ü | ü | ||||
| CSA 22.2, No. 5 |
— | — | — | ü | ü | ü | ü |
| UL 508 (Group Install.) | ü | ü | ü | ||||
| UL489 (Recognized) | — | — | — | ü | ü | ü | ü |
| IEC 60947-2 | ü | ü | ü | ü | ü | ü | ü |
| CE | ü | ü | ü | ü | ü | ü | ü |
| CCC | — | ü (up to 25 A) |
ü | — | — | — | — |
| Accessories | |||||||
| Ext. Rotary Operator | ü | ü | ü | ü | ü | ü | ü |
| Flex Cable Operator | — | — | — | ü | ü | ü | ü |
| Auxiliary Contacts | ü | ü | ü | ü | ü | ü | ü |
| Trip Indication Contacts | ü | ü | ü | ü | ü | ü | ü |
| Product Selection | See Circuit Breakers 140M, Short-Circuit Protection for Starters | See Motor Circuit Protectors (MCP) | |||||