Manual Motor Starters 140A

Manual Motor Starters 140A

Click to enlarge - 140A-C2A_4c



Rated Operational Current (Ie) Motor Current Adjustment Range Switching of 3-Phase AC Motors
AC-2, AC-3 @ 400/415V (50 Hz) ⋆ 
Cat. No.
[A] [A] [kW] Icu = Ics [kA]
0.16 0.1…0.16 0.02 65 140A-C2A-A16
0.25 0.16…0.25 0.06 65 140A-C2A-A25
0.4 0.25…0.4 0.09 65 140A-C2A-A40
0.63 0.4…0.63 0.12/0.18 65 140A-C2A-A63
1 0.63…1.0 0.25 65 140A-C2A-B10
1.6 1.0…1.6 0.37/0.55 65 140A-C2A-B16
2.5 1.6…2.5 0.75 50 140A-C2A-B25
4 2.5…4.0 1.1/1.5 10 140A-C2A-B40
6.3 4.0…6.3 2.2 10 140A-C2A-B63
10 6.3…10 3.0/4.0 8 140A-C2A-C10
16 10…16 5.5/7.5 6 140A-C2A-C16
  
⋆ Power ratings: Preferred values according to IEC 60072-1

  Description Term. No. Click to enlarge - 100M-66-3 Click to enlarge - 100M-66-4 For Use With Cat. No.
N.O. N.C.
Click to enlarge - 140A-C-AEA10 pp_bw Auxiliary Contact for Flush Mounting
1-pole
No additional space required
13-14 1 0 140A 140A-C-AEA10
33-34 1 0 140A-C-AEA210
11-12 0 1 140A-C-AEA01
31-32 0 1 140A-C-AEA201
Click to enlarge - 140A-C-ASA11 pp_bw Auxiliary Contact for Left-side Mounting
2-pole
Adds 9 mm to the width of the Manual Motor Starter
Use compact bus bars with 54 mm spacing
13-14
23-24
2 0 140A 140A-C-ASA20
13-14
21-22
1 1 140A-C-ASA11
11-12
21-22
0 2 140A-C-ASA02
  

  Description For Use With Cat. No.
Click to enlarge - 140A-C-UXJ pp_bw Undervoltage Trip Release
For right-side mounting
Adds 18 mm to the width of the Manual Motor Starter
24V 50 Hz 140A 140A-C-UXK
220…230V 50 Hz 140A-C-UXF
400V 50 Hz / 460V 60 Hz 140A-C-UXN
415V 50 Hz / 480V 60 Hz 140A-C-UXB
110V 50 Hz / 120V 60 Hz 140A-C-UXD
110V 50 / 60 Hz 140A-C-UXKD
Click to enlarge - 140A-C-SXJ pp_bw Shunt Trip Release
For right-side mounting
Adds 18 mm to the width of the Manual Motor Starter
24V 50 Hz 140A 140A-C-SXK
220…230V 50 Hz 140A-C-SXF
400V 50 Hz / 460V 60 Hz 140A-C-SXN
415V 50 Hz / 480V 60 Hz 140A-C-SXB
110V 50 Hz / 120V 60 Hz 140A-C-SXD
110V 50 / 60 Hz 140A-C-SXKD
Click to enlarge - 140A-C-W544 pp_bw Compact Bus Bars
45 mm spacing for manual motor starters with flush-mounted auxiliary contact blocks
2 x 3  Terminal links 140A 140A-C-W452
3 x 3  Terminal links 140A-C-W453
4 x 3  Terminal links 140A-C-W454
5 x 3  Terminal links 140A-C-W455
Compact Bus Bars
54 mm spacing for manual motor starters with side-mounted auxiliary contact blocks
2 x 3  Terminal links 140A 140A-C-W542
3 x 3  Terminal links 140A-C-W543
4 x 3  Terminal links 140A-C-W544
5 x 3  Terminal links 140A-C-W545
Click to enlarge - 140A-C-WT_4c Bus Bar Feeder Terminal
Supply of compact busbars
Increases wiring capacity
140A-C-W 140A-C-WT
Click to enlarge - 140A-C-WS pp_bw Blank Space Cover
For covering unused terminal links
140A-C-W 140A-C-WS
Click to enlarge - 140A-C-PNC23_4c Connecting Module
Contactor and Manual Motor Starter MUST BE mounted separately on (2) DIN Rails
Electrical interconnection between 140A and 100-C09…-C23 contactor (with AC coils)
140A 140A-C-PNC23
  

  Description For Use With Cat. No.
Click to enlarge - 140A-C-EA55_4c Enclosures for Surface Mounting
With centre marks for two indicator lights
Includes protective earth and neutral wire terminals

Protection Class: IP41
140A 140A-C-EA41
Protection Class: IP55
(with seal and protective membrane)
140A 140A-C-EA55
Click to enlarge - 140A-C-EE_ pp_bw Enclosures for Flush Mounting
Includes protective earth and neutral wire terminals

Protection Class: IP41
140A 140A-C-EE41
Protection Class: IP55
(with seal and protective membrane)
140A 140A-C-EE55
Click to enlarge - 140A-C-MT_4c Emergency-Stop Push Button Set
For use with enclosures
Twist to release
140A-C-E… 140A-C-MT
Emergency-Stop Push Button Set
For use with enclosures
Key release
140A-C-E… 140A-C-MK
Click to enlarge - 140A-C-N18_4c Button Membrane
For IP55 enclosures
Replacement part with four screws (mounting frame included)
140A-C-EA55
140A-C-EE55
140A-C-N55
Click to enlarge - 140-L_Pilot_Lights_002_4c Pilot Lights
Length of connection leads 180 mm, includes lamp, protection class IP54.
Green 120V 198E-A…, 198E-C…, 140A-C-E… 140-LG120
240V 140-LG240
400V 140-LG400
Red 120V 198E-A…, 198E-C…, 140A-C-E… 140-LR120
240V 140-LR240
400V 140-LR400
White 120V 198E-A…, 198E-C…, 140A-C-E… 140-LW120
240V 140-LW240
400V 140-LW400
Click to enlarge - 140A-C-N3E_4c Locking Arrangement
Suitable for enclosures 140A-C-E…
For 1…3 padlocks with ø 4…8 mm
140A-C-E… 140A-C-M3E
Click to enlarge - 140A-C-M3 pp_bw Locking Arrangement
For locking ON-button of the Manual Motor Starter
For 1…3 padlocks with ø 4…6 mm
140A 140A-C-M3
Click to enlarge - 140A-C-N12 pp_bw Screw Adapter
Hat (DIN) Rail 35 x 7.5 mm, length 44 mm
140A 140A-C-N12
  

See Publication A117 for complete product information.