| Rated Operational Current (Ie)
|
Motor Current Adjustment Range
|
Switching of 3-Phase AC Motors AC-2, AC-3 @ 400/415V (50 Hz) ⋆
|
Cat. No.
|
| [A]
|
[A]
|
[kW]
|
Icu = Ics [kA]
|
| 0.16
|
0.1…0.16
|
0.02
|
65
|
140A-C2A-A16
|
| 0.25
|
0.16…0.25
|
0.06
|
65
|
140A-C2A-A25
|
| 0.4
|
0.25…0.4
|
0.09
|
65
|
140A-C2A-A40
|
| 0.63
|
0.4…0.63
|
0.12/0.18
|
65
|
140A-C2A-A63
|
| 1
|
0.63…1.0
|
0.25
|
65
|
140A-C2A-B10
|
| 1.6
|
1.0…1.6
|
0.37/0.55
|
65
|
140A-C2A-B16
|
| 2.5
|
1.6…2.5
|
0.75
|
50
|
140A-C2A-B25
|
| 4
|
2.5…4.0
|
1.1/1.5
|
10
|
140A-C2A-B40
|
| 6.3
|
4.0…6.3
|
2.2
|
10
|
140A-C2A-B63
|
| 10
|
6.3…10
|
3.0/4.0
|
8
|
140A-C2A-C10
|
| 16
|
10…16
|
5.5/7.5
|
6
|
140A-C2A-C16
|
|
|
| ⋆ Power ratings: Preferred values according to IEC 60072-1
|
|
|
Description
|
Term. No.
|
|
|
For Use With
|
Cat. No.
|
| N.O.
|
N.C.
|
|
Auxiliary Contact for Flush Mounting 1-pole No additional space required
|
13-14
|
1
|
0
|
140A
|
140A-C-AEA10
|
| 33-34
|
1
|
0
|
140A-C-AEA210
|
| 11-12
|
0
|
1
|
140A-C-AEA01
|
| 31-32
|
0
|
1
|
140A-C-AEA201
|
|
Auxiliary Contact for Left-side Mounting 2-pole Adds 9 mm to the width of the Manual Motor Starter Use compact bus bars with 54 mm spacing
|
13-14 23-24
|
2
|
0
|
140A
|
140A-C-ASA20
|
13-14 21-22
|
1
|
1
|
140A-C-ASA11
|
11-12 21-22
|
0
|
2
|
140A-C-ASA02
|
|
|
|
|
Description
|
For Use With
|
Cat. No.
|
|
Undervoltage Trip Release For right-side mounting Adds 18 mm to the width of the Manual Motor Starter
|
24V 50 Hz
|
140A
|
140A-C-UXK
|
| 220…230V 50 Hz
|
140A-C-UXF
|
| 400V 50 Hz / 460V 60 Hz
|
140A-C-UXN
|
| 415V 50 Hz / 480V 60 Hz
|
140A-C-UXB
|
| 110V 50 Hz / 120V 60 Hz
|
140A-C-UXD
|
| 110V 50 / 60 Hz
|
140A-C-UXKD
|
|
Shunt Trip Release For right-side mounting Adds 18 mm to the width of the Manual Motor Starter
|
24V 50 Hz
|
140A
|
140A-C-SXK
|
| 220…230V 50 Hz
|
140A-C-SXF
|
| 400V 50 Hz / 460V 60 Hz
|
140A-C-SXN
|
| 415V 50 Hz / 480V 60 Hz
|
140A-C-SXB
|
| 110V 50 Hz / 120V 60 Hz
|
140A-C-SXD
|
| 110V 50 / 60 Hz
|
140A-C-SXKD
|
|
Compact Bus Bars 45 mm spacing for manual motor starters with flush-mounted auxiliary contact blocks
|
2 x 3 Terminal links
|
140A
|
140A-C-W452
|
| 3 x 3 Terminal links
|
140A-C-W453
|
| 4 x 3 Terminal links
|
140A-C-W454
|
| 5 x 3 Terminal links
|
140A-C-W455
|
Compact Bus Bars 54 mm spacing for manual motor starters with side-mounted auxiliary contact blocks
|
2 x 3 Terminal links
|
140A
|
140A-C-W542
|
| 3 x 3 Terminal links
|
140A-C-W543
|
| 4 x 3 Terminal links
|
140A-C-W544
|
| 5 x 3 Terminal links
|
140A-C-W545
|
|
Bus Bar Feeder Terminal Supply of compact busbars Increases wiring capacity
|
140A-C-W
|
140A-C-WT
|
|
Blank Space Cover For covering unused terminal links
|
140A-C-W
|
140A-C-WS
|
|
Connecting Module Contactor and Manual Motor Starter MUST BE mounted separately on (2) DIN Rails Electrical interconnection between 140A and 100-C09…-C23 contactor (with AC coils)
|
140A
|
140A-C-PNC23
|
|
|
|
|
Description
|
For Use With
|
Cat. No.
|
|
Enclosures for Surface Mounting With centre marks for two indicator lights Includes protective earth and neutral wire terminals
|
Protection Class: IP41
|
140A
|
140A-C-EA41
|
Protection Class: IP55 (with seal and protective membrane)
|
140A
|
140A-C-EA55
|
|
Enclosures for Flush Mounting Includes protective earth and neutral wire terminals
|
Protection Class: IP41
|
140A
|
140A-C-EE41
|
Protection Class: IP55 (with seal and protective membrane)
|
140A
|
140A-C-EE55
|
|
Emergency-Stop Push Button Set For use with enclosures Twist to release
|
140A-C-E…
|
140A-C-MT
|
Emergency-Stop Push Button Set For use with enclosures Key release
|
140A-C-E…
|
140A-C-MK
|
|
Button Membrane For IP55 enclosures Replacement part with four screws (mounting frame included)
|
140A-C-EA55 140A-C-EE55
|
140A-C-N55
|
|
Pilot Lights Length of connection leads 180 mm, includes lamp, protection class IP54.
|
Green
|
120V
|
198E-A…, 198E-C…, 140A-C-E…
|
140-LG120
|
| 240V
|
140-LG240
|
| 400V
|
140-LG400
|
| Red
|
120V
|
198E-A…, 198E-C…, 140A-C-E…
|
140-LR120
|
| 240V
|
140-LR240
|
| 400V
|
140-LR400
|
| White
|
120V
|
198E-A…, 198E-C…, 140A-C-E…
|
140-LW120
|
| 240V
|
140-LW240
|
| 400V
|
140-LW400
|
|
Locking Arrangement Suitable for enclosures 140A-C-E… For 1…3 padlocks with ø 4…8 mm
|
140A-C-E…
|
140A-C-M3E
|
|
Locking Arrangement For locking ON-button of the Manual Motor Starter For 1…3 padlocks with ø 4…6 mm
|
140A
|
140A-C-M3
|
|
Screw Adapter Hat (DIN) Rail 35 x 7.5 mm, length 44 mm
|
140A
|
140A-C-N12
|
|
|