Motor Protection Circuit Breakers

Catalogs > Essential Components Catalog (Europe) > Power > Motor Protection Circuit Breakers > Manual Motor Starters 140A

Manual Motor Starters 140A

Introduction Product Selection Accessories
Rated Operational Current (Ie) Motor Current Adjustment Range Switching of 3-Phase AC Motors
AC-2, AC-3 @ 400/415V (50 Hz) ⋆ 
Cat. No.
[A] [A] [kW] Icu = Ics [kA]
0.16 0.1…0.16 0.02 65 140A-C2A-A16
0.25 0.16…0.25 0.06 65 140A-C2A-A25
0.4 0.25…0.4 0.09 65 140A-C2A-A40
0.63 0.4…0.63 0.12/0.18 65 140A-C2A-A63
1 0.63…1.0 0.25 65 140A-C2A-B10
1.6 1.0…1.6 0.37/0.55 65 140A-C2A-B16
2.5 1.6…2.5 0.75 50 140A-C2A-B25
4 2.5…4.0 1.1/1.5 10 140A-C2A-B40
6.3 4.0…6.3 2.2 10 140A-C2A-B63
10 6.3…10 3.0/4.0 8 140A-C2A-C10
16 10…16 5.5/7.5 6 140A-C2A-C16
  
⋆ Power ratings: Preferred values according to IEC 60072-1