Motor Protection Circuit Breakers 140M-C, -D, -F and 140-CMN

Motor Protection Circuit Breakers 140M, 140-CMN

Click to enlarge - 140M-C2E-C_L



Rated Operational Current (Ie) Motor Current Adjustment Range Switching of 3-Phase AC Motors
AC-2, AC-3 @ 400/415V (50 Hz)
  Standard
Magnetic Trip
High
Magnetic Trip
[A] [A] [kW] Icu [kA] Ics [kA] Cat. No. Cat. No.
C-Frame
0.16 0.10…0.16 0.02 100 100 ⋆  140M-C2E-A16 140M-C2T-A16
0.25 0.16…0.25 0.04 100 100 ⋆  140M-C2E-A25 140M-C2T-A25
0.4 0.25…0.40 0.09 100 100 ⋆  140M-C2E-A40 140M-C2T-A40
0.63 0.40…0.63 0.18 100 100 ⋆  140M-C2E-A63 140M-C2T-A63
1 0.63…1.0 0.25 100 100 ⋆  140M-C2E-B10 140M-C2T-B10
1.6 1.0…1.6 0.55 100 100 ⋆  140M-C2E-B16 140M-C2T-B16
2.5 1.6…2.5 0.75 100 100 ⋆  140M-C2E-B25 140M-C2T-B25
4 2.5…4.0 1.5 100 100 ⋆  140M-C2E-B40 140M-C2T-B40
6.3 4.0…6.3 2.2 100 100 ⋆  140M-C2E-B63 140M-C2T-B63
10 6.3…10 4 100 100 ⋆  140M-C2E-C10 140M-C2T-C10
16 10…16 7.5 65 (50) ‡  50 ⋆  140M-C2E-C16 140M-C2T-C16
20 14.5…20 10 50 15 ⋆  140M-C2E-C20
25 18…25 11 15 15 ⋆  140M-C2E-C25
29 24…29 13 15 15 ⋆  140M-C2E-C29
32 27…32 15 15 15 ⋆  140M-C2E-C32
D-Frame
2.5 1.6…2.5 0.75 100 100   140M-D8E-B25
4 2.5…4.0 1.5 100 100   140M-D8E-B40
6.3 4.0…6.3 2.2 100 100   140M-D8E-B63
10 6.3…10 4 100 100   140M-D8E-C10
16 10…16 7.5 100 (65) ‡  50 (25) ‡    140M-D8E-C16 140M-D8T-C16
20 14.5…20 10 100 25   140M-D8E-C20 140M-D8T-C20
25 18…25 11 65 25   140M-D8E-C25
29 24…29 13 50 25 ⋆  140M-D8E-C29
32 27…32 15 50 15 ⋆  140M-D8E-C32
F-Frame
10 6.3…10 4 100 50   140M-F8E-C10
16 10…16 7.5 100 50   140M-F8E-C16
20 14.5…20 10 100 50   140M-F8E-C20
25 18…25 11 100 50   140M-F8E-C25 140M-F8T-C25
32 23…32 15 65 50   140M-F8E-C32 140M-F8T-C32
45 32…45 22 65 50   140M-F8E-C45
CMN-Frame
25 16…25 13 50 65   140-CMN-2500
40 25…40 22 30 50   140-CMN-4000 140-CMT-4000
63 40…63 32 20 50   140-CMN-6300 140-CMT-6300
90 63…90 45 20 25   140-CMN-9000
  
⋆ May be ordered in package quantities of 20. Add letter M to the end of the cat. no. (Example: 140M-C2E-A16M).
‡ ( ) for High Magnetic Trip

Product Selection

Motor Protection Circuit Breakers 140M — Spring Clamp Terminals


Click to enlarge - 140M-RC2E-C16 Product Shot_BW


Rated Operational Current (Ie) Motor Current Adjustment Range Switching of 3-Phase AC Motors
AC-2, AC-3 @ 400/415V (50 Hz)
Cat. No.
[A] [A] [kW] Icu [kA] Ics [kA]
C-Frame
0.16 0.10…0.16 0.02 100 100 140M-RC2E-A16
0.25 0.16…0.25 0.04 100 100 140M-RC2E-A25
0.4 0.25…0.40 0.09 100 100 140M-RC2E-A40
0.63 0.40…0.63 0.18 100 100 140M-RC2E-A63
1 0.63…1.0 0.25 100 100 140M-RC2E-B10
1.6 1.0…1.6 0.55 100 100 140M-RC2E-B16
2.5 1.6…2.5 0.75 100 100 140M-RC2E-B25
4 2.5…4.0 1.5 100 100 140M-RC2E-B40
6.3 4.0…6.3 2.2 100 100 140M-RC2E-B63
10 6.3…10 4.0 100 100 140M-RC2E-C10
16 10…16 7.5 65 50 140M-RC2E-C16
  

Accessories 140M, 140-CMN
Accessories 140M