Motor Circuit Protectors 140M-H, -J, -L, -N
Motor Circuit Protectors (MCP)- Short Circuit Protection — Magnetic Trip (Adjustable at 3...10 x Ie)
- Overload Protection — None (Magnetic Trip Only)
|
|
|
| Cat. No. 140M-H | Cat. No. 140M-J | Cat. No. 140M-L |
| Rated Operational Current (Ie) | Magnetic Trip Current | Switching of 3-Phase AC Motors AC-2, AC-3 @ 400/415V (50 Hz) |
Cat. No. | |
| [A] | [A] | [kW] | Icu [kA] ⋆ | |
| H-Frame | ||||
| 3 | 9…33 | 0.75 | (65) | 140M-H8P-B30 |
| 7 | 21…77 | 2.2 | (65) | 140M-H8P-B70 |
| 15 | 45…165 | 5.5 | (65) | 140M-H8P-C15 |
| 30 | 90…330 | 11 | (65) | 140M-H8P-C30 |
| 50 | 150…550 | 22 | (65) | 140M-H8P-C50 |
| 70 | 210…770 | 30 | (65) | 140M-H8P-C70 |
| 100 | 300…1100 | 45 | (65) | 140M-H8P-D10 |
| 100 | 500…1500 | 55 | (65) | 140M-H8R-D10 |
| J-Frame | ||||
| 100 | 500…1000 | 37 | (65) | 140M-J8P-D10 |
| 125 | 625…1250 | 45 | (65) | 140M-J8P-D12 |
| 150 | 750…1500 | 55 | (65) | 140M-J8P-D15 |
| 175 | 875…1750 | 55 | (65) | 140M-J8P-D17 |
| 200 | 1000…2000 | 75 | (65) | 140M-J8P-D20 |
| 225 | 1125…2250 | 90 | (65) | 140M-J8P-D22 |
| 250 | 1250…2500 | 90 | (65) | 140M-J8P-D25 |
| L-Frame | ||||
| 225 | 1125…2250 | 90 | (65) | 140M-L8P-D22 |
| 250 | 1250…2500 | 90 | (65) | 140M-L8P-D25 |
| 300 | 1500…3000 | 110 | (65) | 140M-L8P-D30 |
| 350 | 1750…3500 | 132 | (65) | 140M-L8P-D35 |
| 400 | 2000…4000 | 160 | (65) | 140M-L8P-D40 |
| 450 | 2250…4500 | 160 | (65) | 140M-L8P-D45 |
| 500 | 2500…5000 | 200 | (65) | 140M-L8P-D50 |
| 600 | 3000…6000 | 250 | (65) | 140M-L8P-D60 |
| N-Frame | ||||
| 800 | 1600…6400 | 250 | (65) | 140M-N8P-D80 |
| 1200 | 2400…9600 | 400 | (65) | 140M-N8P-E12 |
| ⋆ Tested @ 480V 60 Hz according UL 489 | ||||
| Accessories for 140M-H, -J, -L, N see Accessories 140UE | ||||
Internal Accessories — Field Installed
External Accessories