Contactors 100-D
Contactors 100-D
|
|
|
| 100-D105 | 100-D420 | 100-D860 |
- Conventional and Electronic Coils
- 3 Main Contacts
Coil Voltage Codes
Ä Coil Voltage Codes for AC Control
| Conventional Coil | [V] | 24 | 48 | 110 | 120 | 220-230 | 230 | 240 | 380-400 | 440 | 550 | |
| -D115…-D180 | 50 Hz | K | Y | D | — | A | — | — | N | — | C | |
| 60 Hz | J | X | — | D | — | — | A | — | N | — | ||
| -D115 | 50/60 Hz | — | — | KN | — | — | KF | — | — | — | — | |
| Electronic Coil w/ EI Interface ⋆ | [V] | 24 | 42-64 | 110-130 | 208-277 | 380-415 | 440-480 | 380-500 | |
| -D115…-D300 | 50/60 Hz | EJ | EY | ED | EA | — | — | EN | |
| -D420 | 50/60 Hz | — | — | ED | EA | — | — | EN | |
| -D630…-D860 | 50/60 Hz | — | — | ED | EA | EN | EB | — | |
Ä Coil Voltage Codes for DC Control
| Conventional Coil | [V] | 24 | 48 | 110 | 220 | |
| -D115…-D180 § | DC | ZJ | ZY | ZD | ZA | |
| Electronic Coil w/ EI Interface ⋆ | [V] | 24 | 48-72 | 110-130 | 200-255 | |
| -D115…-D300 | DC | EZJ | EZY | EZD | EZA | |
| -D420 | DC | — | — | EZD | EZA | |
| -D630…-D860 | DC | — | — | ED | EA | |
| ⋆ Signal voltage of the electronic interface (100-D…, 100S-D…): nominal Ue: 24V DC/Ie: 15 mA Pickup voltage: 13.0V DC…30.2V DC Dropout Voltage: 3.0V DC…+5.0V DC. |
||||||
| Not available with 100(S)-D300 | ||||||
| § For conventional DC coils, the pickup winding must be interconnected with the N.C. late-breaking auxiliary contact(s). | ||||||
Accessories for 100-D, 100S-D