Contactors 100-D

Contactors 100-D

Click to enlarge - 100-D95_bw Click to enlarge - 100-D420_bw Click to enlarge - 100-D860_bw
100-D105 100-D420 100-D860


Rated Operational Current (Ie) [A] Ratings for Switching AC Motors — AC-2, AC-3, AC-4 Auxiliary Contacts   Cat. No.
(60 °C) (40 °C) 3Æ kW (50 Hz) Click to enlarge - 100M-66-3 Click to enlarge - 100M-66-4
AC-3 AC-1 400/415V N.O. N.C.
3-Pole AC-Operated Contactors
115 250 63 1 1   100-D115Ä11
140 250 78 1 1   100-D140Ä11
180 250 100 1 1   100-D180Ä11
210 350 118 1 1   100-D210Ä11
250 350 140 1 1   100-D250Ä11
300 450 170 1 1   100-D300Ä11
420 540 238 1 1   100-D420Ä11
630 800 355 1 1   100-D630Ä11
860 1000 500 1 1   100-D860Ä11
3-Pole DC-Operated Contactors
115 250 63 2 1/1L ‡  100-D115Ä22L
1 1   100-D115Ä11
140 250 78 2 1/1L ‡  100-D140Ä22L
1 1   100-D140Ä11
180 250 101 2 1/1L ‡  100-D180Ä22L
1 1   100-D180Ä11
210 350 118 1 1   100-D210Ä11
250 350 140 1 1   100-D250Ä11
300 450 170 1 1   100-D300Ä11
420 540 238 1 1   100-D420Ä11
630 800 355 1 1   100-D630Ä11
860 1000 500 1 1   100-D860Ä11
  
‡ Conventional Coil: The pickup winding must be interconnected with the N.C. late-breaking auxiliary contact.

Coil Voltage Codes

Ä Coil Voltage Codes for AC Control

Conventional Coil [V] 24 48 110 120 220-230 230 240 380-400 440 550
-D115…-D180 50 Hz K Y D A N C
60 Hz J X D A N
-D115 50/60 Hz KN KF
  

Electronic Coil w/ EI Interface ⋆  [V] 24 42-64 110-130 208-277 380-415 440-480 380-500
-D115…-D300 50/60 Hz EJ ‡  EY ED EA EN
-D420 50/60 Hz ED EA EN
-D630…-D860 50/60 Hz ED EA EN EB
  

Ä Coil Voltage Codes for DC Control

Conventional Coil [V] 24 48 110 220
-D115…-D180 §  DC ZJ ZY ZD ZA
  

Electronic Coil w/ EI Interface ⋆  [V] 24 48-72 110-130 200-255
-D115…-D300 DC EZJ EZY EZD EZA
-D420 DC EZD EZA
-D630…-D860 DC ED EA
  
⋆ Signal voltage of the electronic interface (100-D…, 100S-D…): nominal Ue: 24V DC/Ie: 15 mA
Pickup voltage: 13.0V DC…30.2V DC         Dropout Voltage: –3.0V DC…+5.0V DC.
‡ Not available with 100(S)-D300
§ For conventional DC coils, the pickup winding must be interconnected with the N.C. late-breaking auxiliary contact(s).

Accessories for 100-D, 100S-D