Catalogs > Essentials Catalog (Europe) > Power > Motor Protection > Product Line Overview
Product Line Overview
Overload Relays
|
|
|
| Bulletin | 193-EC1/-EC2 | 825-P |
| Type | Electronic Overload Relay E3 and E3 Plus | Modular Protection System |
| Rated Current (Range) | 0.4…5000 A | 0.5…5000 A |
| Operating Voltage, Nominal | 690V / 1000V ¬ | 690V/1000V |
| Overload Type | Microprocessor Based | Microprocessor Based |
| Trip Class (Adjustable) | 5…30 | 1…600 |
| Ambient Compensated | ü | ü |
| Reset Type | Automatic, Manual and Remote |
Automatic, Manual and Remote |
| Adjustment Range | 5:1 | 4:1 |
| Phase Loss | Imbalance Sensing | Imbalance Sensing |
| Phase Reversal | — | ü |
| Ground (Earth) Fault | E3 Plus: Sensitive | Residual or Sensitive |
| Overcurrent (Jam) Detection | ü | ü |
| Stall Detection | ü | ü |
| Starts/Hour Monitoring | — | ü |
| Underload Detection | ü | ü |
| Current Imbalance | ü | ü |
| Short Circuit Protection | — | ü |
| PTC Thermistor Monitoring | ü (E3 Plus) | ü |
| RTD Monitoring | — | 12-Channel Optional Scanner |
| Warning Settings | ü | ü |
| Trip Contact N.C. | ü | ü |
| Alarm Contact N.O. | ü | ü |
| Number of Outputs | E3: 1/E3 Plus: 2 | 3 (Basic)/7 (with I/O Expansion) |
| Number of Inputs | E3: 2/E3 Plus: 4 | 2 (Basic)/5 (with I/O Expansion) |
| Number of Analog Outputs | — | 1(with I/O Expansion) |
| ODVA (DeviceNet) Conformance |
ü | ü |
| Atex Certification | In Preparation | — |
| Variable Frequency (VFD) Compatible |
ü | — |
| Mounts to Contactor | 100-C, 100-D | 100-D (825-MCM) |
| Product Selection | See Electronic Overload Relays E3 and E3 Plus 193-EC | See Modular Protection System 825-P |
| ¬ 193-EC_F, 193-EC_G, 193-EC_H | ||