Motor Protection

Catalogs > Essential Components Catalog (Europe) > Power > Motor Protection > Bimetallic Overload Relays 193-T1

Bimetallic Overload Relays 193-T1

Introduction Product Selection Add-On Modules
For Use With ⋆  Setting Range [A]
‡ § 
Max. Back-up gL/gG fuse [A]
50 kA, 690V AC
IEC/EN 60947-4-1 Coordination
Cat. No.
Type 1 Type 2
100-C09…100-C23 0.1…0.16 50 193-T1AA16
0.16…0.25 50 193-T1AA25
0.25…0.40 50 2 193-T1AA40
0.35…0.50 50 2 193-T1AA50
0.45…0.63 50 2 193-T1AA63
0.55…0.80 50 4 193-T1AA80
0.75…1.0 50 4 193-T1AB10
0.90…1.3 50 6 193-T1AB13
1.1…1.6 50 6 193-T1AB16
1.4…2.0 50 10 193-T1AB20
1.8…2.5 50 16 193-T1AB25
2.3…3.2 50 16 193-T1AB32
2.9…4.0 50 16 193-T1AB40
3.5…4.8 50 16 193-T1AB48
4.5…6.3 50 20 193-T1AB63
5.5…7.5 50 25 193-T1AB75
7.2…10 50 25 193-T1AC10
9.0…12.5 50 35 193-T1AC12
100-C12…100-C23 11.3…16 50 35 193-T1AC16
100-C16…100-C23 15…20 80 40 193-T1AC20
17.5…21.5 80 50 193-T1AC21
100-C23 21…25 80 50 193-T1AC25
100-C30…100-C37 15…20 80 40 193-T1BC20
17.5…21.5 80 50 193-T1BC21
21…25 80 50 193-T1BC25
24.5…30 100 63 193-T1BC30
29…36 125 63 193-T1BC36
100-C37 33…38 125 63 193-T1BC38
100-C43 17…25 100 50 193-T1CC25
24.5…36 125 80 193-T1CC36
35…47 160 100 193-T1CC47
100-C60…100-C97 35…47 160 100 193-T1DC47
45…60 200 125 193-T1DC60
100-C72…100-C97 58…75 200 125 193-T1DC75
100-C85…100-C97 72…90 250 160 193-T1DC90
  
⋆ Bulletin 193-T1 overload relays shall not be used with conventional DC controlled contactors. Use electronic controlled DC versions.
‡ To select the setting range for use in Y-D Starters, multiply the rated operating current of the motor by a factor of 0.58.
§ For motors with service factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor nameplate full load current.

For Use With ⋆  Setting Range [A]
‡ § 
Max. Back-up gL/gG fuse [A]
50 kA, 690V AC
IEC/EN 60947-4-1 Coordination
Cat. No.
Type 1 Type 2
Separate mounting required (Panel-mounted device) 35…47 160 100 193-T1DC47P
45…60 200 125 193-T1DC60P
58…75 200 125 193-T1DC75P
72…90 250 160 193-T1DC90P
  
⋆ Bulletin 193-T1 overload relays shall not be used with conventional DC controlled contactors. Use electronic controlled DC versions.
‡ To select the setting range for use in Y-D Starters, multiply the rated operating current of the motor by a factor of 0.58.
§ For motors with service factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor nameplate full load current.