Electronic Overload Relays 193-EC
E3 and E3 Plus Electronic Overload and Current Monitor Relays
|
- DeviceNet™ communication integrated
- IEC/NEMA configurations
- True RMS current sensing
- Single-/three-phase
- LED indicators
- Test/reset button
- Adjustable trip class (5…30)
- Motor Diagnostics
| Bulletin | No. Inputs | No. Outputs | PM Diagnostics | PTC Thermistor | DeviceLogix | Ground Fault |
| 193-EC1 | 2 | 1 | ü | — | — | — |
| 193-EC2 | 4 | 2 | ü | ü | ü | Internal (1…5 A) |
| 193-EC3 | 4 | 2 | ü | ü | ü | External (20 mA…5 A) |
| 193-EC5 | 6 | 2 | ü | — | ü | External (20 mA…5 A) |
| External ground fault sensor, Cat. No. 193-CBCT_, required | ||||||
Electronic Motor Protection Relays 193-EC1 Direct Contactor Mount
| Mounts to Contactor | Adjustment Range [A] | Cat. No. | |
| 100-C09…100-C23 | 0.4…2 | 193-EC1PB | |
| 1…5 | 193-EC1AB | ||
| 3…15 | 193-EC1BB | ||
| 5…25 | 193-EC1CB | ||
| 100-C30…100-C43 | 1…5 | 193-EC1AD | |
| 3…15 | 193-EC1BD | ||
| 5…25 | 193-EC1CD | ||
| 9…45 | 193-EC1DD | ||
| 100-C60…100-C97 | 9…45 | 193-EC1DE | |
| 18…90 | 193-EC1EE | ||
| 100-D115…100-D180 | 28…140 | ⋆ | 193-EC1FF |
| 42…210 | ⋆ | 193-EC1GF | |
| 100-D210…100-D420 | 42…210 | ⋆ | 193-EC1GG |
| 60…302 | ⋆ | 193-EC1HG | |
| 84…420 | ⋆ | 193-EC1JG | |
| 100-D630…100-D860 | 125…630 | ⋆ | 193-EC1KH |
| 172…860 | ⋆ | 193-EC1LH | |
| ⋆ Does not include terminal lugs. Rated operating voltage IEC: 1000V AC. |
|||
Electronic Motor Protection Relay 193-EC2 Direct Contactor Mount
| Mounts to Contactor | Adjustment Range [A] | Cat. No. |
| 100-C09…100-C23 | 0.4…2 | 193-EC2PB |
| 1…5 | 193-EC2AB | |
| 3…15 | 193-EC2BB | |
| 5…25 | 193-EC2CB | |
| 100-C30…100-C43 | 1…5 | 193-EC2AD |
| 3…15 | 193-EC2BD | |
| 5…25 | 193-EC2CD | |
| 9…45 | 193-EC2DD | |
| 100-C60…100-C97 | 9…45 | 193-EC2DE |
| 18…90 | 193-EC2EE | |
Electronic Overload Relays 193-EC3 / -EC5 Direct Contactor Mount
| Mounts to Contactor | Adjustment Range [A] |
Bul. 193-EC3 | Bul. 193-EC5 | |
| Cat. No. | Cat. No. | |||
| 100-C09…100-C23 | 0.4…2.0 | 193-EC3PB | 193-EC5PB | |
| 1…5 | 193-EC3AB | 193-EC5AB | ||
| 3…15 | 193-EC3BB | 193-EC5BB | ||
| 5…25 | 193-EC3CB | 193-EC5CB | ||
| 100-C30…100-C43 | 5…25 | 193-EC3CD | 193-EC5CD | |
| 9…45 | 193-EC3DD | 193-EC5DD | ||
| 100-C60…100-C97 | 9…45 | 193-EC3DE | 193-EC5DE | |
| 18…90 | 193-EC3EE | 193-EC5EE | ||
| 100-D115…100-D180 | 28…140 | ⋆ | 193-EC3FF | 193-EC5FF |
| 42…210 | ⋆ | 193-EC3GF | 193-EC5GF | |
| 100-D210…100-D420 | 42…210 | ⋆ | 193-EC3GG | 193-EC5GG |
| 60…302 | ⋆ | 193-EC3HG | 193-EC5HG | |
| 84…420 | ⋆ | 193-EC3JG | 193-EC5JG | |
| 100-D630…100-D860 | 125…630 | ⋆ | 193-EC3KH | 193-EC5KH |
| 172…860 | ⋆ | 193-EC3LH | 193-EC5LH | |
| ⋆ Does not include terminal lugs. Rated operating voltage IEC: 1000V AC. |
||||
Panel Mount Devices for use with External Current Transformers
| For Use With | Adjustment Range [A] ♣ | Cat. No. |
| 193-ECPM2 DIN Rail/Panel Adapter (Order panel adapter 193-ECPM2 separately) |
9…5000 | 193-EC1ZZ |
| 193-EC3ZZ | ||
| 193-EC5ZZ | ||
| ♣ Current transformers supplied by customer. Refer to CT chart for proper current transformer selection. | ||
Accessories
CT Ratio to FLA Setting Range Correlation
| CT Ratio | FLA Setting Range [A] | CT Ratio | FLA Setting Range [A] | CT Ratio | FLA Setting Range [A] |
| 50:5 | 9…45 | 300:5 | 60…302 | 1200:5 | 240…1215 |
| 100:5 | 18…90 | 500:5 | 84…420 | 2500:5 | 450…2250 |
| 150:5 | 28…140 | 600:5 | 125…630 | 5000:5 | 1000…5000 |
| 200:5 | 42…210 | 800:5 | 172…860 | — | — |
Note:For labeling materials, see Marking Systems.