| Mounts to Contactor
|
Setting Range [A] ⋆
|
Max. Current Rating Backup gL Fuse [A] IEC Coordination Type
|
Cat. No.
|
| Type 1
|
Type 2
|
| 100-K05…100-K12
|
0.10…0.16
|
35
|
1
|
193-KA16
|
| 0.16…0.25
|
35
|
1
|
193-KA25
|
| 0.25…0.40
|
35
|
2
|
193-KA40
|
| 0.35…0.50
|
35
|
2
|
193-KA50
|
| 0.45…0.63
|
35
|
2
|
193-KA63
|
| 0.55…0.80
|
35
|
4
|
193-KA80
|
| 0.75…1.0
|
35
|
4
|
193-KB10
|
| 0.9…1.3
|
35
|
6
|
193-KB13
|
| 1.1…1.6
|
35
|
6
|
193-KB16
|
| 1.4…2.0
|
35
|
10
|
193-KB20
|
| 1.8…2.5
|
35
|
20
|
193-KB25
|
| 2.3…3.2
|
35
|
20
|
193-KB32
|
| 2.9…4.0
|
35
|
20
|
193-KB40
|
| 3.5…4.8
|
35
|
20
|
193-KB48
|
| 4.5…6.3
|
35
|
20
|
193-KB63
|
| 100-K09…100-K12
|
5.5…7.5
|
35
|
20
|
193-KB75
|
| 7.2…10.0
|
35
|
20
|
193-KC10
|
| 100-K12
|
9.0…12.5
|
35
|
20
|
193-KC12
|
|
|
| ⋆ To select the setting range for use in Y-D Starters, multiply the rated operating current of the motor by a factor of 0.58.
|
| For motors with service factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor nameplate full load current.
|