Catalogs > Essential Components Catalog (Europe) > Power > Motor Protection > Miniature Thermal Overload Relays 193-K
Miniature Thermal Overload Relays 193-K
| Mounts to Contactor | Setting Range [A] ⋆ | Max. Current Rating Backup gL Fuse [A] IEC Coordination Type |
Cat. No. | |
| Type 1 | Type 2 | |||
| 100-K05…100-K12 | 0.10…0.16 | 35 | 1 | 193-KA16 |
| 0.16…0.25 | 35 | 1 | 193-KA25 | |
| 0.25…0.40 | 35 | 2 | 193-KA40 | |
| 0.35…0.50 | 35 | 2 | 193-KA50 | |
| 0.45…0.63 | 35 | 2 | 193-KA63 | |
| 0.55…0.80 | 35 | 4 | 193-KA80 | |
| 0.75…1.0 | 35 | 4 | 193-KB10 | |
| 0.9…1.3 | 35 | 6 | 193-KB13 | |
| 1.1…1.6 | 35 | 6 | 193-KB16 | |
| 1.4…2.0 | 35 | 10 | 193-KB20 | |
| 1.8…2.5 | 35 | 20 | 193-KB25 | |
| 2.3…3.2 | 35 | 20 | 193-KB32 | |
| 2.9…4.0 | 35 | 20 | 193-KB40 | |
| 3.5…4.8 | 35 | 20 | 193-KB48 | |
| 4.5…6.3 | 35 | 20 | 193-KB63 | |
| 100-K09…100-K12 | 5.5…7.5 | 35 | 20 | 193-KB75 |
| 7.2…10.0 | 35 | 20 | 193-KC10 | |
| 100-K12 | 9.0…12.5 | 35 | 20 | 193-KC12 |
| ⋆ To select the setting range for use in Y-D Starters, multiply the rated operating current of the motor by a factor of 0.58. | ||||
| For motors with service factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor nameplate full load current. | ||||