Soft Starters

Catalogs > Essential Components Catalog (Europe) > Power > Soft Starters > SMC-Flex Controller

SMC-Flex Controller

Introduction Product Selection Optional Configurations Accessories
Product Selection

Up to 480V AC

Line Connection
⋆ ‡ § 
Delta Connection
⋆ ‡ § 
100…240V AC 50/60 Hz Control ♣ 
Without
Option
With Pump
Control Option
Motor Current [A] 400V [kW] Motor Current [A] 400V [kW] Cat. No. Cat. No.
1…5 2.2 1.7…8.7 4 150-F5NBD 150-F5NBDB
5...25 11 8.7…43 22 150-F25NBD 150-F25NBDB
8.6...43 22 14.9…74 37 150-F43NBD 150-F43NBDB
12...60 30 20.8…104 55 150-F60NBD 150-F60NBDB
17...85 45 29.4…147 75 150-F85NBD 150-F85NBDB
27…108 55 47…187 90 150-F108NBD 150-F108NBDB
34…135 75 59…234 132 150-F135NBD 150-F135NBDB
67…201 110 116…348 160 150-F201NBD 150-F201NBDB
84…251 132 145…435 250 150-F251NBD 150-F251NBDB
106…317 160 183…549 315 150-F317NBD 150-F317NBDB
120…361 200 208…625 355 150-F361NBD 150-F361NBDB
160…480 250 277…831 450 150-F480NBD 150-F480NBDB
208…625 355 283…850 500 150-F625NBA 150-F625NBAB
260…780 450 300…900 500 150-F780NBA 150-F780NBAB
323…970 560 400…1200 710 150-F970NBA 150-F970NBAB
416…1250 710 533…1600 900 150-F1250NBA 150-F1250NBAB
  
⋆ Controllers rated 108 A and greater are not equipped with line and load terminal lugs.
‡ Motor FLA and motor running current must fall within the running current range of the device to operate properly.
§ Utilization category: 5…480 A: AC-53b: 3-50: 1750 / 625…1250 A: AC-53b: 3.0-50: 3550
♣ Reduced control voltage range for devices from 625…1250 A. See configuration table in section "b".