| Frame Reference
|
H-Frame
|
J-Frame
|
L-Frame
|
M-Frame
|
N-Frame
|
| Current Range
|
20…160 A
|
70…250 A
|
100…630 A
|
300…800 A
|
600…1250 A
|
| No. of Poles
|
3, 4
|
3, 4
|
3, 4
|
3
|
3, 4
|
| Dimensions (mm)
|
Height
|
140
|
178
|
258
|
406
|
406
|
| Width
|
76
|
105
|
140
|
210
|
210
|
| Depth
|
76
|
103
|
104
|
140
|
140
|
| Interrupting Ratings: kA
|
Icu
|
Ics
|
Icu
|
Ics
|
Icu
|
Ics
|
Icu
|
Ics
|
Icu
|
Ics
|
| 50 Hz
|
220…240V
|
25, 35, 85, 100
|
50%
|
65, 85, 100
|
100%
|
65, 85, 100
|
100%
|
65, 100
|
100%
|
200, 200
|
100%
|
| 380…415V
|
18, 25, 40, 70
|
50%
|
23, 40, 70
|
100%
|
35, 50, 70
|
100%
|
50, 70
|
100%
|
70, 100
|
100%
|
| 690V
|
6, 6, 7, 8
|
50%
|
6, 6, 7, 8
|
50%
|
2, 20, 25
|
50%
|
20, 25
|
100%
|
35, 50
|
50%
|
| 60 Hz NEMA
|
On request
|
| Protection Type
|
| Thermal-Magnetic
|
FF, AF
|
AA
|
AA
|
AF
|
—
|
| Electronic
|
—
|
ü
|
ü
|
ü
|
ü
|
| Internal Accessories
|
| Alarm (Trip) Contact
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Auxiliary Shields
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Aux/Alarm Combination
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Shunt Trip
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Undervoltage Release
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Field Installable
|
ü
|
ü
|
ü
|
ü
|
ü
|
| External Accessories
|
| Padlockable Hasp
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Terminal Covers
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Flex-Cable Operating Mech.
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Variable Depth Rotary Operating Mechanism
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Direct Coupler Rotary Operating Mechanism
|
ü
|
ü
|
ü
|
ü
|
—
|
| Plug-in Base
|
ü
|
ü
|
ü
|
—
|
—
|
| Slide Bar Interlock
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Standards Compliance
|
| IEC 60947-2
|
ü
|
ü
|
ü
|
ü
|
ü
|
| CE
|
ü
|
ü
|
ü
|
ü
|
ü
|
| KEMA-KEUR
|
ü
|
ü
|
ü
|
ü
|
ü
|
| Product Selection
|
See 140UE, H-Frame
|
See 140UE, J-Frame
|
See 140UE, L-Frame
|
See 140UE, M-Frame
|
See 140UE, N-Frame
|
|
|