140UE, H-Frame
Circuit Breakers 140UE — 160 A, H-Frame
|
- Thermal Magnetic Trip
- 18, 25, 40, 70 kA Breaking Capacity @ 415V (50 Hz)
- 3-pole, 4-pole
Approvals
- IEC 60947-2, CE, KEMA-KEUR
Note: Terminal box lugs and mounting hardware provided as standard
Product Selection
25 kA, Thermal-Magnetic, Adjustable Thermal-Fixed Magnetic
| Rated Operational Current (In) | Thermal Trip (Ir = 0.8…1.0 x In) |
Magnetic Trip (Im = 10 x In) |
Breaking Capacity (50 Hz) Icu /Ics [kA] |
3-Pole | |||||
| [A] | [A] | [A] | 380…415V | 500V | 690V | Cat. No. | |||
| 20 | 16…20 | 500 | 25 | 13 | 140UE-H2E3-C20 | ||||
| 25 | 20…25 | 500 | 25 | 13 | 140UE-H2E3-C25 | ||||
| 32 | 25…32 | 500 | 25 | 13 | 140UE-H2E3-C32 | ||||
| 40 | 32…40 | 500 | 25 | 13 | 140UE-H2E3-C40 | ||||
| 50 | 40…50 | 500 | 25 | 13 | 140UE-H2E3-C50 | ||||
| 63 | 50…63 | 630 | 25 | 13 | 140UE-H2E3-C63 | ||||
| 80 | 63…80 | 800 | 25 | 13 | 140UE-H2E3-C80 | ||||
| 100 | 80…100 | 1000 | 25 | 13 | 140UE-H2E3-D10 | ||||
| 125 | 100…125 | 1250 | 25 | 13 | 140UE-H2E3-D12 | ||||
| 160 | 125…160 | 1600 | 25 | 13 | 140UE-H2E3-D16 | ||||
Isolation Disconnector — IEC 60947-3
| Rated Operational Current (In) | Thermal Trip (Ir = In), Fixed |
Magnetic Trip (Im = 10 x In) |
Breaking Capacity (50 Hz) Icu /Ics [kA] |
3-Pole | |||||
| [A] | [A] | [A] | 380…415V | 500V | 690V | Cat. No. | |||
| 160 | — | 1600 | 25 | 25 | 3 | 3 | 140UE-H2S3-D16 | ||
See Publication 140UE-SG001… for 4-pole types and different breaking capacity.
Internal Accessories — Field Installed
External Accessories