140UE, J-Frame
Circuit Breakers 140UE — 250 A, J-Frame
|
- Thermal Magnetic Trip
- Electronic Trip LS, LSI, LSG and LSIG
- 25, 40, 70 kA Breaking Capacity @ 415V (50 Hz)
- 3-pole, 4-pole
Approvals
- IEC 60947-2, CE, KEMA-KEUR
Note: Terminal box lugs and mounting hardware included.
Product Selection
40 kA, Assembled Circuit Breakers, Thermal-Magnetic Trip Units
| Rated Operational Current (In) | Thermal Trip (Ir = 0.8…1.0 x In) |
Magnetic Trip (Im = 5…10 x In) |
Breaking Capacity (50 Hz) Icu /Ics [kA] |
3-Pole | |||||
| [A] | [A] | [A] | 380…415V | 500V | 690V | Cat. No. | |||
| 80 | 64…80 | 400…800 | 40 | 40 | 35 | 20 | 12 | 6 | 140UE-J4F3-C80 |
| 100 | 80…100 | 500…1000 | 40 | 40 | 35 | 20 | 12 | 6 | 140UE-J4F3-D10 |
| 125 | 100…125 | 625…1250 | 40 | 40 | 35 | 20 | 12 | 6 | 140UE-J4F3-D12 |
| 160 | 128…160 | 800…1600 | 40 | 40 | 35 | 20 | 12 | 6 | 140UE-J4F3-D16 |
| 200 | 160…200 | 1000…2000 | 40 | 40 | 35 | 20 | 12 | 6 | 140UE-J4F3-D20 |
| 250 | 200…250 | 1250…2500 | 40 | 40 | 35 | 20 | 12 | 6 | 140UE-J4F3-D25 |
Isolation Disconnector — IEC 60947-3
| Rated Operational Current (In) | Thermal Trip (Ir = 0.8…1.0 x In) |
Magnetic Trip (Im = 10 x In) |
Breaking Capacity (50 Hz) Icu /Ics [kA] |
3-Pole | |||||
| [A] | [A] | [A] | 380…415V | 500V | 690V | Cat. No. | |||
| 250 | — | 2500 | 70 | 70 | 25 | 10 | 14 | 7 | 140UE-J7S3-D25 |
See Publication 140UE-SG001… for 4-pole types, electronic trip units and different breaking capacity.
Internal Accessories — Field Installed
External Accessories