Molded Case Circuit Breakers

Catalogs > Essential Components Catalog (Europe) > Power > Molded Case Circuit Breakers > 140UE, J-Frame

140UE, J-Frame

Introduction Product Selection Isolation Disconnector — IEC 60947-3 Accessories
Product Selection

40 kA, Assembled Circuit Breakers, Thermal-Magnetic Trip Units

Rated Operational Current (In) Thermal Trip
(Ir = 0.8…1.0 x In)
Magnetic Trip
(Im = 5…10 x In)
Breaking Capacity (50 Hz)
Icu /Ics [kA]
3-Pole
[A] [A] [A] 380…415V 500V 690V Cat. No.
80 64…80 400…800 40 40 35 20 12 6 140UE-J4F3-C80
100 80…100 500…1000 40 40 35 20 12 6 140UE-J4F3-D10
125 100…125 625…1250 40 40 35 20 12 6 140UE-J4F3-D12
160 128…160 800…1600 40 40 35 20 12 6 140UE-J4F3-D16
200 160…200 1000…2000 40 40 35 20 12 6 140UE-J4F3-D20
250 200…250 1250…2500 40 40 35 20 12 6 140UE-J4F3-D25