Solid State Devices

Catalogs > Essentials Catalog (Europe) > Logic > Solid State Devices > Product Line Overview

Product Line Overview

Solid State Devices 700-SH, -SE, -SC Solid State Devices 700-SA, -SK
Solid State Devices 700-SH, -SE, -SC

  Click to enlarge - 700_SH_relay_4c Click to enlarge - 700_SE_relay_4c Click to enlarge - 700_SC_relay_4c
Bulletin 700-SH 700-SE 700-SC
Type Hockey Puck Flat Pack Miniature, Ice Cube Socketed
Features Panel/DIN Mount, High Current, Protective Cover, LED Status Panel/DIN Mount, Low Profile Compatible with 700-HN103 or 128 socket, LED Status & Zero-cross AC Switching Options
Load Type AC (47…63 Hz)
3…60V DC
AC (47…63 Hz) AC (47…63 Hz) DC
Load Voltage Range 3…50V DC, 24…265V AC
42…530V AC, 42…265V AC,
42…660V AC
75…264V AC 75…264V AC 3…52.8V DC or 3…125V DC
Load Current Max. (Continuous) 10 A/100 A ¬  5 A/20 A ¬  3 A 3A @ 48V DC or 2A @ 110V DC
Max Leakage Current to Load <3 mA 5 mA @ 100V, 10 mA @ 200V 5 mA @ 100V AC 10 mA @ 200V AC, 5 mA @ 50V DC or 0.1mA @ 100V DC
Zero Cross Load Switching Yes Yes (optional) Yes (optional) N/A
Equivalent Electromechanical Relay Contact Arrangement 1 N.O.
Form A
1 N.O.
Form A
1 N.O.
Form A
Rated Control (Input) Voltage 3…32V DC, 4…32V DC,
80…130V AC, 20…260V AC
20…280V AC/22…48V DC
5V DC, 12V DC, 24V DC 5…24V DC, 100…110V AC, 200/220V AC 5...24V DC
LED Indicator Yes No Yes (optional) Yes (optional for 48V DC)
Mounting Method Panel without heat sink, Panel or DIN with heat sink Panel without heat sink, Panel or DIN with heat sink Panel or DIN with socket
Dielectric Strength >4000V AC RMS 2000V AC, 50/60 Hz, 1 min. 1500V AC, 50/60 Hz, 1 min.
Certification cURus, CE , CSA ¬  cURus, CE, TÜV cURus, CE, VDE
Max. Ambient Operating Temperature -20…70 °C (no condensation) -30…80 °C (no condensation) -30…80 °C (no condensation)
Product Selection See Hockey Puck Relays for DIN Rail Mounting 700-SH See Flat Pack Relays for DIN Rail Mounting 700-SE See Ice Cube Relays with Blade Style Terminals 700-SC
  
¬ With heat sink.