Catalogs > Essential Components Catalog (Europe) > Logic > Circuit Protection > Product Line Overview
Product Line Overview
| Residual Current Devices 1492-RCD Miniature Circuit Breakers 1492-SP |
Miniature Circuit Breakers 1489 Fuse Holders 1492-FB |
Fuse Holders 140F |
Fuse Holders 1492-FB
|
|
|
|||||||
| Bulletin | 1489 | 1492-FB | ||||||
| Type | 480Y/277V AC | 240V AC | For Class CC Fuse | For Class J Fuse | For Midget Fuse | |||
| 0.5…25 A | 0.5…40 A | 30 A | 30 A | 60 A | 30 A | |||
| Features | - 0.5...40 A @ 240, 415V AC - 15,000 A interrupting |
|||||||
| Certifications | UL 489 Listed (CSA C22.2 No. 5.1), UL File Number E197878 VDE (SEC 60 947-2) |
CE, ULus, CSA | CE, URus, CSA | |||||
| Maximum Voltage Rating | 480Y/277V AC | 600V AC/DC | ||||||
| Shock | 25 G Half Sine Wave for 11 ms (Three Axes) | 25 G Half Sine Wave for 11 ms (Three Axes) | ||||||
| Tripping Characteristic Reference Temperature | 40°C (UL/CSA) 30°C (IEC) |
NA | ||||||
| Tripping Characteristic | C Curve: 5…10 D Curve: 10…20 |
NA | ||||||
| Vibration | 100...500 Hz for 1 hour Amplitude — 10...57 Hz; 0.030 inches peak to peak; 57...500 Hz; 5 G peak |
5 G peak or 0.030 "peak-to-peak" displacement for 2 hours in each perpendicular direction. Vibration sweep 10 to 2000 to 10 Hz (15 minutes long) | ||||||
| Operating Temperature | -13...140°F (-25...+55°C), non-condensing |
-4...130°F (20…+55°C) | ||||||
| Housing Material | Nylon | Nylon | ||||||
| Working Voltage | — | 110…600V AC/DC or 12…72V AC/DC | 110…600V AC/DC | 110…600V AC/DC or 12…72V AC/DC | ||||
| With Indicator | Leakage Current | LED | — | 2.0 mA | ||||
| Wire Size | 0.8...13 mm2/#18...6 AWG Cu | #16…4 AWG Cu | #14…1 AWG Cu | #10…1 AWG Cu | #16…4 AWG Cu | |||
| Interrupt Rating | 10 kA @ 240V AC and 480Y/277V AC (UL/CSA) |
200 kA | 50 kA | |||||
| Product Selection | See Miniature Circuit Breakers Bulletin 1489 | See DIN Rail Mounting Fuse Holders 1492-FB | ||||||