Catalogs > Safety Products Catalog > Other Safety Related Products > Explosion Proof Switches > Ex Range
Ex Range
Specifications| All switches excluding Ferrogard GS2 | |
| Contact Block Electrical Specifications | |
| Certifications | 112G EExd 11C T6 or T5 112D T80°C IP 66 under ATEX |
| Safety Contacts | 1 N.C. & 1 N.O. or 2 N.C. |
| Enclosure Protection | IP 66 |
| Rated Voltage | 250V AC and 250V DC |
| Rated Current | 5 A AC and 0.25 A DC |
| AC Ratings, Resistive | 6 A @ 250V, 6 A @ 125V |
| AC Ratings, Inductive | 2.5 A @ 250V, 3 A @ 125V |
| DC Ratings, Resistive | 0.25 A @ 250V, 0.5 A @ 125V, 1 A @ 75V, 7 A @ 30V |
| DC Ratings, Inductive | 0.1 A @ 250V, 0.2 A @ 125V, 1 A @ 75V, 5 A @ 30V |
| Contact Block Technical Specifications | |
| Operating Force | 1.6 N - 0.4/ - 0.2 N |
| Release Force | 0.4 N |
| Pre-travel | 0.8 mm (0.03 in) |
| Over Travel | 0.6 mm (0.02 in) |
| Return Travel | 1.1 mm (0.04) |
| Differential Travel | 0.5 mm (0.19 in) |
| Release Travel | 0.2 mm (0.007 in) |
| Positive Break Travel | 0.4 mm (0.01 in) |
| Repeatability | +0.01 mm (0.0003 in) |
| Switching Speed, Min. | 1 mm (0.039 in) |
| Switching Frequency, Max. | 3000 operations/hour |
| Mechanical Life | 2,000,000 operations |
| Electrical Life | Dependent on loading |
| Operating Temperature [C (F)] | -25…70° (-10…284°) |
| Electrical Connection | Potted in leads. Flexible 4 x 0.75 mm2, 2 m long |
| Ferrogard GS2 | |
| Certifications | EExd IIC T6 Baseefa. Not suitable for Group 1 gases |
| Safety Contacts | 1 N.C. |
| Enclosure Protection | IP 68 |
| Rated Voltage | 250V AC |
| Rated Current | 2 A |
| Rated VA | 100V A max @ 50V 200V A max @ 110V 500V A max @ 250V |
| Operating Distance, Make [mm (in.)] | 15 (0.59) |
| Operating Distance, Break [mm (in.)] | 26 (1.02) |
| Closing Time | 3.0 ms |
| Drop-Out Time | 2.1 ms |
| Bounce Time | 0.7 ms |
| Shock | <50 g |
| Vibration | 15 g, 20…1000 Hz |
| Contact Resistance, Initial | 0.07 W (excluding cable) |
| Mechanical Life | 100,000,000 operations |
| Electrical Life | 5,000,000 operations |
| Operating Temperature [C (F)] | -10…40° (14…104°) |
| Housing Material | Brass or Stainless Steel |
| Cable Length | 3 m (9.8 ft), 5 m (32.8 ft), or 10 m (32.8 ft) |
| Cable Type | Termorad |