Catalogs > Safety Products Catalog > Principles, Standards and Implementation > Introduction to Functional Safety of Control Systems
Introduction to Functional Safety of Control Systems
Table 8 shows the relationship (in terms of probability of dangerous failure between PL and SIL when applied to typical circuit structures.
| PL (Performance Level) | PFHD (Probability of Dangerous Failure per Hour) | SIL |
| a | ³105 to <104 | None |
| b | ³3 x 106 to <105 | 1 |
| c | ³106 to <3 x 106 | 1 |
| d | ³107 to <106 | 2 |
| e | ³108 to <107 | 3 |
| Table 8: Approximate correspondence between PL and SIL | ||
|
|
Table 8 is for general guidance and must NOT be used for conversion purposes. The full requirements of the standards must be taken into account. |