Safety Applications and Wiring Diagrams

Catalogs > Safety Products Catalog > Safety Applications and Wiring Diagrams > Notes for Use with Application Circuit Examples

Notes for Use with Application Circuit Examples

Notes

Note 1

In the following circuits the type of Allen-Bradley/Guardmaster device is shown as an example to illustrate the circuit principle. For specific applications the choice of device type should be based on the suitability of its characteristics for its intended use.

Note 2

In most of the following examples showing dual channel applications, one interlock switch is shown switching both channels (one contact set per channel). If it is foreseeable that damage to the guard (e.g., at the actuator mounting point) could allow it to be opened without operating the switch then two separate switches may be required. The electrical principle of the circuit will remain the same.

Note 3

In most cases the circuits are shown with the guard door closed and ready for motor starting by operating the normal start control.

It must be possible to start the machine only by voluntary actuation of the control provided for the purpose (see ISO 12100-2 4.11.8). For the purposes of these examples the use of a conventional contactor latching circuit has been assumed. If this is not the case, then a restart interlock will be required to prevent an automatic or unintended starting of the motor when the guard is closed. For example, a Minotaur safety relay with a momentary action push button installed in the output monitoring circuit can be used to achieve this.

If the guard is designated as a Control Guard (see ISO 12100-2 5.3.2.5) these requirements do not apply but the use of control guards is only allowed under certain conditions including:



Note 4

Safety monitoring relay units used in dual channel circuits with infrequent operation or with more than one switching device connected. This note applies to all monitoring devices which use the technique of comparing the signal at the change of state of dual channels.

Certain faults are only detected at a change of state of the input switching device (interlock switch or E-Stop switch). If there are long periods (e.g. months as opposed to days) between switching actions, it may be possible for multiple faults to accumulate which could lead to a dangerous situation. Therefore a regular check should be performed on the system in order to detect single faults before an accumulation occurs. This check may be manual or initiated by part of the machines control system.

If, for example, 3 interlock switches are connected to the monitoring unit, certain faults will only be detected at the switch on the first guard to be opened and the switch on the last guard to be closed. This is because any switching between the first opening/last closing will not change the state of the monitoring unit input circuits. Therefore in some applications it may be necessary to use one monitoring device per switch.

Most of the following examples show an interlock switch and an emergency stop switch combined in the circuit. When a monitoring safety relay (e.g. Guardmaster Minotaur) is used for fault detection it is important to note the following:



Note 5

Click to enlarge - CircleArrow This symbol indicates that the associated component or device features direct opening (positive opening) operation. In the event of a fault, welded contacts will be forced open by the motion of the safety guard.
Click to enlarge - SlavedCircuit This symbol denotes mechanically linked contacts; if one contact welds closed, all other dependent (auxiliary) contacts remain in position, i.e. they cannot change state.

General Safety Information

Click to enlarge - IMPORTANT      This application example is for advanced users and assumes that you are trained and experienced in safety system requirements.
 

Click to enlarge - ATTENTION      A risk assessment should be performed to make sure all tasks and hazard combinations have been identified and addressed. The risk assessment may require additional circuitry to reduce the risk to a tolerable level. Safety circuits must take into consideration safety distance calculations which are not part of the scope of this document.

Contact Rockwell Automation to find out more about our safety risk assessment services.
Click to enlarge - Warning-Exclamation_GS
 

For other Important User Information and Safety Guidelines, please review pages G-2 and G-3 in the General section of this catalog.